Document zzmG52gGd8Mnx2GRrLJZnEQbn

SECTION V A-la.44 CALCIUM SILICATE SINGLE LAYER: FIG. 53 D APPLICATION ^ASIC INSULATION PIPE AND FITTINGS 4th Step The cover is secured and the line insulation continued. jf K. Securing Portable Fitting Covers K. 1. Indoor covers having an O.D. less than 11 inches or a perimeter less than 30 inches shall be secured with 1 inch wide metallic - asbestos tape and 1 inch wide Velcro fasteners. Seefigures 54 A. 1.2 The method for fabricating Velcro-asbestos tape portable cover straps is described in Section VII-B, instruction sheet 6 page 6. 1.3 Indoor covers 11 inches O.D. up to 15 inches O.D. or having a perimeter of 30 inches up to 42 inches, shall be secured with 2 inch wide metallic - "A" tape and 2 inch wide Velcro fastener. 1.4 Indoor covers 15 inches O.D. up to 20 inches O.D., or having a perimeter of 42 inches up to 60 inches, shall be secured with 3/4 inch wide s/s bands and #204 case latch fasteners. Seefigure 54 B. 1.5 Indooi; covers having an O.D. above 20 inches or a perimeter of 60 inches or more shall be secured with 1-1/4 inch wide s/s bands and #210 case latch fasteners