HEATING VENTILATING AIR CONDITIONING CUIDE 1940
CHAPTER 15. STEAM HEATING SYSTEMS
discharge the air to atmosphere and return the condensate to the boiler. Some type of hydraulic action is utilized to produce the suction. Such hydraulic evacuating devices may be classified as:
a. Water ring centrifugal displacement pumps.
f>. Water piston pumps. c. Stationary kinetic exhauster .pumpsd. Rotary kinetic ejector pumps.
The-evacuating element is generally combined with a centrifugal water impeller for the delivery of the condensate to the boiler or feedwater heater.
The assembled units may be further grouped under two general classifications:
. Those which perform the function of air separation under atmospheric pressure. . Those which perform the function of air separation under a partial vacuum.
drips, etc. It is for this reason that the condensate from equipment using
steam at high pressures should not be connected directly to a vacuum
return line but should drain to a receiver through a high pressure trap.
The receiver should have an equalizing connection to a low pressure steam
main and drain through a low pressure trap to the vacuum return main as
indicated in Fig. 17. :.
:; -
.
Vacuum Pump Controls
In the ordinary vacuum system, the vacuum pump is controlled by a vacuum regulator'which cuts in when the vacuum drops to the lowest point desired and cuts out when it has been increased to theTiighest point, these points being varied to suit the particular system* or operating conditions.. In addition to this vacuum control, a float control is included
Pumps coming under the first classification remove both the air and condensate from the returns by means of the hydraulic- evacuator and deliver both to a separating tank under atmospheric pressure. From this tank the air and non-condensable vapors are vented to atmosphere while the condensate is removed and delivered to the boiler by means of
the built-in boiler feed pump impeller.
In the second classification, the air and condensate are first separated under vacuum by means of the receiver which is directly connected to the returns. The hydraulic evacuator withdraws only the air and non condensable vapors from the. top of the receiver and delivers them to atmosphere. The built-in condensate pump impeller removes the con densate from the bottom of the receiver and delivers it direct to the
boiler or feed-water heater. Under special conditions such as returning-the condensate to a high
pressure boiler or the furnishing of large air removal units for high vacuum systems, it is customary to supply separate motor-driven air
and water pumps. For rating purposes1 vacuum pumps are classified as low vacuum and
high vacuum. Low vacuum pumps are those rated for maintaining 5^ in. Hg. vacuum on the system, and high vacuum pumps are those rated to
maintain vacuums above in. The vacuum that can be maintained on a system depends upon the
relationship of the air leakage rate into the system to the operating air capacity of the hydraulic evacuator when operating at any given return line temperature. The hotter the returns, the lower will be the possible vacuum for a given air leakage rate into the system. It is particularly essential on high vacuum installations To see that the entire system is
tight in order to reduce the amount of inward air leakage and, further more, to see that relatively higher temperature steam is prevented from entering the vacuum return lines through leaky traps, high pressure
Fig. 17. . Method of Discharging High-Pressure Apparatus into Low-Pressure - ; Heating Mains and Vacuum Return Mains through
a Low-Pressure Trap
which wiUautomatically start the pump whenever sufficient condensation accumulates in the receiver, regardless of the vacuum on the'system. A selector switch is usually provided to allow operation at night as a con densation pump only5, also to give manual or continuous operation when desired.
There are several variations in the'control' of the vacuum maintained on the system by the pump. In' some sub-atmospheric systems where orifices areused, the vacuum pump control maintains a pressure difference between'the supplyand the return piping,.which is held within relatively close limits.: There are other, sub-atmospheric systems^which Utilize special temperature-pressure actuatedTontrols^for maintaining the desired conditions in the return lines. Where'various zories are connected to the same return' main, the return vacuum must be controlled to meet the requirements of the zone operating at the lowest steam supply'pressure.
Piston Displacement Vacuum Pumps
1A.S.H.V.E. Standard Code for Testing and Rating Return Line Low Vacuum Heating Pumpa. (A.S. H.V.E. Transactions, Vol. 40, 1934, p. 33).
Piston displacement return vacuum heating pumps may be'either'electric or steam driven. They should be provided with mechanicallubricators