250 CHAPTER 11
distribution; cannot be predicted with certainty,, and refinement in calcu lations is not justified; consequently, a simplified method can be used. This may be done by using the equations and calculating the flows produced by each force separately, under conditions of openings best suited for.co ordination of the forces. Then, by determining the ratio of the flow pro duced by temperature difference to the sum of the two flows, the actual flow due to the combined forces can be approximated from Fig.- 4.
Example 1: Assume a drop forge shop, 200 ft long, 100 ft wide, and 30 ft high. The cubical content is 600,000 cu ft, and the height of the air outlet over that of the inlet is 30 ft. Oil fuel of 18,000 Btu per lb is used in this shop at the rate of 15 gph (7.75 lb per gal). Desired summer temperature difference is 10 deg, and the prevail ing wind is 8 mph perpendicular to the long dimension. What is the necessary area for the inlets and outlets, and what is the rate of air flow through the building?
'infiltration and Ventilation
251
ft of opening in its path for inflow, and 595 in the lee side of the. monitor for, outflow with the windward side closed.' The air flow, as calculated by Equation 3,. will be:
Q = 0.60 X 400 X 704 = 168,960 cfm.
This gives 16.9 air changes per hour, which should be more than ample when there is no heat.to be removed.';
Solution for Combined Heads: Since the windward side of the, monitor is closed when the.wind is blowing, the flow due to. temperature difference must be calculated for this condition, using Fig. 3. This chart shows that, when inlets are twice the size of the outlets, in this case 1,190 sq ft in the sidewalls and 595 sq ft in the.monitor, the flow will be increased 26.5 percent over that produced by equal openings. Using
Fig. 3. Increase in Flow Caused by Excess of One Opening Over Another
Solution for Temperature Difference Only: The heat H -- 15 X 7.75 X 18,000 = 2,092,500 Btu per hr.
By Equation 5, the air flow required to remove this heat with an average temperature .; . difference of 10 deg is
H 2,092,500
Q = 1.08U, - (,,)
= 193,750 cfm. .1.08 X 10
V
This is equal to about 20 air changes per hour. opening area should be
From Equation 4, the inlet (or outlet) ;
SV i-i.
,Q
193,750
9.4\/h(t, - to) 9.4V30 X 10
4
.-ft'
The flow per square foot of inlet or outlet would be 193,750 -i- 1190 = 162.5 cfm, with all windows open.
Solution for Wind Only: With 1,190 sq ft of inlet openings distributed around the sidewalls, there will be about 400 sq ft in each long side and 195 sq ft in each endThe outlet area will be equally distributed on the two sides of the monitor, or 595. sq ft on each side. With the wind perpendicular to the long side, there will be 400 sq
Fig. 4. Determination of Flow Caused by Combined Forces of Wind and Temperature Difference
the smaller opening and the flow per square foot obtained previously, the calculated amount for this condition will be
595 X 163 X 1.265 = 122,700 cfm. Adding the two computed flows:
Temperature Difference = 122,700 = 42 percent.
Wind
= 168,960 = 58 percent.
Total
291,660 = 100 percent..
From Fig. 4 it is determined that, when the flow due to temperature difference is 1 the total, the actual flow due to the combined forces, will be about 1.6
es that calculated for temperature difference alone, or 196,300 cfm.
original flow due to temperature difference alone was 193,750 cfm with all half Use- The effect of the wind is to increase this to 196,300 cfm, even though oalf of the outlets are closed.
h{^or of judgment is necessary in the location of the openings in a
v ng, especially those in the roof, where heat, smoke, and fumes are to ...removed. Usually, windward monitor openings should be closed, but if
-ft