Fire Loss Control
steam whistle or similar device might be ade quate In any case, the alarm system is no better than the level of training given em ployees in how to respond when the alarm is sounded (See details below, and in the next two chapters)
Emergency dnlls
Regardless of what method is used to alert employees, they should thoroughly under stand what the signal means and how to re spond in the safest possible manner Train ing employees to leave their work place promptly on proper signal, and to evacuate a building speedily but without contusion, is largely accomplished through fire or emer gency drills Exit drills must be carefully planned and earned out in a serious manner under rigid discipline Periodic instruction sheets should be distributed to all employees, and an exit drill organization formed from the supervisory staff
Emergency exit drills also serve as a valua ble check on the adequacy and condition of the exits and alarm system Any deficiency should be immediately and permanently cor rected Careful plans must be made to elim inate the possibility of panic in the event of an emergency, regardless of cause, and to guarantee the smooth functioning of the emergency plan Reference should be made to the NFPA pamphlet No 7, Recommenda tions For Management Control of Fire Emer gencies
Factors Contributing to Industrial Fires
To eliminate causes of fire, we must first know the many ways in which it can start, especially the most common ones A study made by the Associated Factory Mutual Fire Insurance Company of almost 25,000 indus trial fires over a 10 year period indicates that the majority of fires can be traced to four general sources of ignition electrical, smok ing, fuction, and o\er-heatcd materials (Fig 35-7)
Electrical equipment fires
Electrical equipment should be installed and maintained in accordance with the Na tional Electrical Code Over-heating of elec trical equipment and arcs resulting from short
circuits in improperly installed or maintained electrical equipment are two of the leading causes
Only approved (or UL-listed) equipment should be used where flammable gases or vapors may be present Electrical equipment necessary in locations which are hazardous because of the presence of flammable liquids, gases or dusts, should be designed for the particular hazardous atmosphere
Hazardous locations are divided into three classes depending on the material involved Further division is by degree or severity of the hazard Complete definitions of the several classes and divisions of hazardous locations and tvpes of equipment for each are contained in the National Electrical Code, and are discussed in Chapter 33
Temporary or makeshift wiring, particularly
if defective or overloaded, is an outstanding cause of electrical fires, it should not be used unless absolutely necessary and should be removed as soon as possible Over-loaded or partially grounded wiring may also heat up enough to ignite combustibles without blowing fuses or tripping circuit breakers
Portable electrical tools and extension cords should conform to the National Electrical Code and should be inspected at frequent intervals and repaired promptly Waterproof cords and sockets should be used in damp places, and explosion-proof fixtures and lamps should be used m the presence of highly flammable gases and vapors
All electrical equipment, particularly port able electncal tools, should be grounded for the protection of persons using it Switches, lamps, cords, fixtures, and other electrical equipment should be listed by Underwriters' Laboratories, Inc , or other recognized testing and certifying agency, and should be used only in applications for which the approval or listing was granted
Lamp bulbs should be protected b\ heavv lamp guards or b\ adequately sealed trans parent enclosures, and kept awav from shaqi objects and kept from falling Bare bulbs should never be used when exposed to flam mable dusts or vapors Lamp bulbs must be considered as potential hazards in such areas, they must be safeguarded accordingly
Employees should be instructed in the use of electncal equipment and should be pro hibited from tampenng, blocking circuit