Document zzNbVZGMmx26nZwkVd5kapena

TABLE 16-A AMERICAN TABLE OF DISTANCES FOR STORAGE OF EXPLOSIVES* (Condensed) Explosives Pounds Over Pounds Not Over Inhabited Buildings Distances in feet When Storage Is Barricaded" Passenger Railways Public Highways Separation of Magazines 10 40 100 150 300 500 900 1,400 2,000 5,000 8,000 10.000 16,000 20,000 35,000 50,000 70,000 95,000 140,000 190,000 275,000 20 50 125 200 400 600 1,000 1,600 2,500 6,000 9,000 12,000 18,000 25,000 40,000 55,000 75.000 100,000 150.000 200.000 300.000*" 110 150 200 235 295 340 400 470 545 730 835 875 940 1,055 1,275 1,460 1,665 1.815 1,900 2,030 2,275 45 60 80 95 120 135 160 190 220 295 335 370 420 470 550 610 675 745 850 935 1,075 45 60 80 95 120 135 160 175 190 235 255 270 285 315 380 440 500 545 570 610 690 10 14 18 21 27 31 36 43 49 65 75 82 94 105 124 140 160 185 235 285 385 Adapted from table of same name approved by the Institute of Makers of Explosives, September 30, 1953 NOTES 'This table applies only to the manufacture and permanent storage of commercial explosives It is not applicable to the transportation of explosives or to any handling or temporary storage necessary or incident thereto It is not intended to apply to bombs, projectiles, or other heavily encased explosives "Barncaded. as here used signifies that the building containing explosives is screened from other buildings railways and highways, by either natural or artificial barriers Where such barriers do not exist, the distances shown in the table should be doubled '"The Institute of Makers of Explosives does not approve the permanent storage of more than 300 000 pounds of com mercial explosives in one magazine Ample space should be provided between segregated units, from such flame sources as boilers, and from shops, streets, and adjoin ing property Fig 16-3 shows a well planned layout of the structures m a lacquer manu facturing plant The codes of local and state authorities and of the National Fire Protection Association should be followed in planning the location of the units of a plant Where no legal restrictions govern the storage of explosives, magazines should be located and constructed in accordance with the recommendations of the Institute of Makers of Explosives Table 16-A specifies the quantities of explosives that may be stored safely at various distances from inhabited buildings, passenger railways, and public highways The type of retardant required m relation 399