Document zzLaxJKO44GgOanwKmvZBkZY0
American Society of Heating and Ventilating Engineers Guide, 1934
Table 1. Heat Losses from Horizontal Bare Iron Pipes
Expressed in Btu per linear foot per degree: Fahrenheit difference in temperature between the pipe and surrounding still air at 70 F
Nominal Pipe
Size (Inches)
120 F
Hot Water
150 F
180 F
210 F
227.1 F (S Lb)
Temperature Difference
Steam
297.7 F (50 Lb)
337.9 F (100 Lb)
%
1
ilA
2
VA
3
314
4
4)4
5 6 8 9 12
S0F
0.543 0.660 0.791 0.979 1.09 1.34 1.58 1.88 2.13 2.36 2.60 2.87 3.39 4.32 4.80 6.25
80 F
0.573 0.690 0.829 1.02 . 1.15 1.40 1.67 1.99 2.24 2.50 2.75 3.02 3.56 4.55 5.05 6.62
no F
0.605 0.729 0.878 1.087 1.220 1.491 1.778 2.100 2.380 2.650 2.920 3.200 3.775 5.050 5.350 6.995
140 F
0.638 0.762 0.920 1.15 1.29 1.58 1.87 2.22 2.51 2.78 3.08 3.38 4.01 5.14 5.71 7.46
157.1 F
0.656 0.781 0.953 1.184 1.335 1.637 1.937 2.301 2.585 2.873 3.170 3.493 4.115 5.270 5.885 7.670
227.7 F
0.742 0.886 1.084 1.345 1.520 1.866 2.215 2.641 2.972 3.312 3.655 4.030 4.755 6.120 6.824 8.900
267.9 F
0.796 0.955 1.166 1.450 1.640 2.015 2.388 2.853 3.215 3.582 3.956 4.368 5.153 6.635 7.400 9.670
Table 2. Radiating Surface per Linear Foot of Pipe
Nominal Pipe Size (Inches)
14 %A
l V/i lH
Surface Area
(Sq Ft)
0.22 0.275 0.344 0.435 0.498
Nominal Pipe Size (Inches)
2
2H 3
3a
4
Surface Area
(Sq Ft)
0.622 0.753 0.917 1.047 1.178
Nominal Pipe Size (Inches)
5 6 8 9 12
Surface Area
(Sq Ft)
1.456 1.734 2.257 2.519 3.338
Table 3. Areas of Flanged Fittings, Square Feet*
Nominal Pipe Size (Inches)
i
1M
VA
2
2A
3
3)4
4
iA
5 6 8 9 12
Flanged Coupling
90 Deg Ell
Long Radius Ft.t.
Tee
Cross
Standard
Extra Heavy
Standard
Extra Heavy
Standard
Extra Heavy
Standard
Extra Heavy
Standard
Extra Heavy
0.320 0.383 0.477 0.672 0.841 0.945 1.122 1.344 1.474 1.622 1.82 2.41 3.00 4.41
0.438 0.795 1.015 0.892 1.083 1.235 1.575 1.622 2.07 0.510 0.957 1.098 1.084 1.340 1.481 1.925 1.943 2.53 0.727 1.174 1.332 1.337 1.874 1.815 2.68 2.38 3.54 0.848 1.65 2.01 1.84 2.16 2.54 3.09 3.32 4.06 1.107 2.09 2.57 2.32 2.76 3.21 4.05 4.19 5.17 1.484 2.38 3.49 2.68 3.74 3.66 5.33 4.77 6.95 1.644 2.98 3.96 3.28 4.28 4.48 6.04 5.83 7:89 1.914 3.53 4.64 3.96 4.99 5.41 7.07 7.03 9.24 2.04 3.95 5.02 4.43 5.46 6.07 7.72 7.87 10.07 2.18 4.44 5.47 5.00 6.02 6.81 8.52 8.82 10.97 2.78 5.13 6.99 5.99 7.76 7.84 10.64 10.08 13.75 3.77 6.98 9.76 8.56 11.09 10.55 14.74 13.44 18.97 4.44 8.71 11.44 10.57 13.17 13.18 17.23 16.78 22.10 6.71 13.08 17.73 16.35 18.76 19.67 26.65 24.87 34.11
Including areas of accompanying flanges bolted to the fitting.
504
Chapter 35--Heat Losses from Bare and Insulated Pipes
Fig. 1. Chart for Estimating Dollar Value of Heat Loss from Bare Iron Pipes. (See Table l)a
This chart is based on 100. linear feet per 1000 hours. For fractions or multiples of these factors, multiply by proper percentage.
heat equivalent to more than a ton of coal per year shows the necessity for insulating such surfaces. Table 3 shows the areas of both standard and extra heavy flanged fittings including the accompanying 'flanges bolted to the fittings.
STEAM AND HOT WATER LINES The conductivities of various materials used for insulating steam and hot water pipes are given in Table 4. In this table the conductivities are given as functions of the mean temperatures or the mean of the inner and outer surface temperatures of the insulations. This method of stating
505