Document zzLaxJKO44GgOanwKmvZBkZY0

American Society of Heating and Ventilating Engineers Guide, 1934 Table 1. Heat Losses from Horizontal Bare Iron Pipes Expressed in Btu per linear foot per degree: Fahrenheit difference in temperature between the pipe and surrounding still air at 70 F Nominal Pipe Size (Inches) 120 F Hot Water 150 F 180 F 210 F 227.1 F (S Lb) Temperature Difference Steam 297.7 F (50 Lb) 337.9 F (100 Lb) % 1 ilA 2 VA 3 314 4 4)4 5 6 8 9 12 S0F 0.543 0.660 0.791 0.979 1.09 1.34 1.58 1.88 2.13 2.36 2.60 2.87 3.39 4.32 4.80 6.25 80 F 0.573 0.690 0.829 1.02 . 1.15 1.40 1.67 1.99 2.24 2.50 2.75 3.02 3.56 4.55 5.05 6.62 no F 0.605 0.729 0.878 1.087 1.220 1.491 1.778 2.100 2.380 2.650 2.920 3.200 3.775 5.050 5.350 6.995 140 F 0.638 0.762 0.920 1.15 1.29 1.58 1.87 2.22 2.51 2.78 3.08 3.38 4.01 5.14 5.71 7.46 157.1 F 0.656 0.781 0.953 1.184 1.335 1.637 1.937 2.301 2.585 2.873 3.170 3.493 4.115 5.270 5.885 7.670 227.7 F 0.742 0.886 1.084 1.345 1.520 1.866 2.215 2.641 2.972 3.312 3.655 4.030 4.755 6.120 6.824 8.900 267.9 F 0.796 0.955 1.166 1.450 1.640 2.015 2.388 2.853 3.215 3.582 3.956 4.368 5.153 6.635 7.400 9.670 Table 2. Radiating Surface per Linear Foot of Pipe Nominal Pipe Size (Inches) 14 %A l V/i lH Surface Area (Sq Ft) 0.22 0.275 0.344 0.435 0.498 Nominal Pipe Size (Inches) 2 2H 3 3a 4 Surface Area (Sq Ft) 0.622 0.753 0.917 1.047 1.178 Nominal Pipe Size (Inches) 5 6 8 9 12 Surface Area (Sq Ft) 1.456 1.734 2.257 2.519 3.338 Table 3. Areas of Flanged Fittings, Square Feet* Nominal Pipe Size (Inches) i 1M VA 2 2A 3 3)4 4 iA 5 6 8 9 12 Flanged Coupling 90 Deg Ell Long Radius Ft.t. Tee Cross Standard Extra Heavy Standard Extra Heavy Standard Extra Heavy Standard Extra Heavy Standard Extra Heavy 0.320 0.383 0.477 0.672 0.841 0.945 1.122 1.344 1.474 1.622 1.82 2.41 3.00 4.41 0.438 0.795 1.015 0.892 1.083 1.235 1.575 1.622 2.07 0.510 0.957 1.098 1.084 1.340 1.481 1.925 1.943 2.53 0.727 1.174 1.332 1.337 1.874 1.815 2.68 2.38 3.54 0.848 1.65 2.01 1.84 2.16 2.54 3.09 3.32 4.06 1.107 2.09 2.57 2.32 2.76 3.21 4.05 4.19 5.17 1.484 2.38 3.49 2.68 3.74 3.66 5.33 4.77 6.95 1.644 2.98 3.96 3.28 4.28 4.48 6.04 5.83 7:89 1.914 3.53 4.64 3.96 4.99 5.41 7.07 7.03 9.24 2.04 3.95 5.02 4.43 5.46 6.07 7.72 7.87 10.07 2.18 4.44 5.47 5.00 6.02 6.81 8.52 8.82 10.97 2.78 5.13 6.99 5.99 7.76 7.84 10.64 10.08 13.75 3.77 6.98 9.76 8.56 11.09 10.55 14.74 13.44 18.97 4.44 8.71 11.44 10.57 13.17 13.18 17.23 16.78 22.10 6.71 13.08 17.73 16.35 18.76 19.67 26.65 24.87 34.11 Including areas of accompanying flanges bolted to the fitting. 504 Chapter 35--Heat Losses from Bare and Insulated Pipes Fig. 1. Chart for Estimating Dollar Value of Heat Loss from Bare Iron Pipes. (See Table l)a This chart is based on 100. linear feet per 1000 hours. For fractions or multiples of these factors, multiply by proper percentage. heat equivalent to more than a ton of coal per year shows the necessity for insulating such surfaces. Table 3 shows the areas of both standard and extra heavy flanged fittings including the accompanying 'flanges bolted to the fittings. STEAM AND HOT WATER LINES The conductivities of various materials used for insulating steam and hot water pipes are given in Table 4. In this table the conductivities are given as functions of the mean temperatures or the mean of the inner and outer surface temperatures of the insulations. This method of stating 505