CHAPTER 34
1962 Guide And Data Book
There are also self-contained coolant units using low tem perature cooling mixtures such as 20 F glycol for circulation through the jacket.
Mixer manufacturers usually specify the condensing unit for use with their various mixers.
Dough Capacity, Lb
800 1000 1300 1600 2000.
Refrigerant It Condensing Unit Hp
5 7^-10 10 -15 IS -20
20
Formulas, batch sixes, mixing times and almost every other part of the mixing process vary considerably from bakery to bakery and must be determined for each application. These variations usually fall within the following limits:
Final dough weights Ratio of sponge to final dough weight Ratio of flour to final dough weight Ratio of water to flour Sponge mixing time Final dough mixing time Number of mixes per hr
1000-3000 lb 50-75% 50-05% 50-65% 6-10 min 8-12 min 2-5
To calculate refrigeration requirements for the mixing process, the following factors are used:
1. Specific heat of flour =0.42 Btu per (lb) (F deg). 2. Specific heat of dough *0.60 Btu per (lb) (F deg). 3. Average specific heat of other ingredients **0.40 Btu per (lb)
(F deg). 4. Average heat of hydration * 6.5 Btu per lb. 5. Heat generated by mixer motor=42.4 Btu per (min) (bp).
In larger operations the sponge and final dough are mixed in different mixers, and the refrigeration requirements have to be determined separately for each process.
In smaller operations a single mixer is used for both the sponge and final dough.
The cooling load for the final dough mix is greater than that for tbe sponge mix, and is used to establish the refrigerationrequirements.
The cooling load for a final dough mix may be calculated from Equations 1 to 7.
Q. = 0.60w.(4 - 4) Q, * 0.42uy((/ - 4)
(1)
(2)
Qk " 6.5 w/
Q< - Q.Wviiti - Q)
(3) (4)
Qm = 42.4 P
(5)
Q - .(*. - 4)
(6)
tohen '
0- =.+<},+<?(+ Q_ - Q. Qt - NQm
(7) (8)
Q, -- sensible heat gam from sponge, Btu per mix. u>, = weight of sponge after fermentation, pounds' per mix. 4 = temperature of sponge after fermentation, Fahrenheit.
U = temperature of final dough, Fahrenheit. Qf = sensible beat gain from flour, Btu per mix. tDf => weight of flour in final dough mix, pounds per mix. tj s temperature of Sour, Fahrenheit. Qk 0 heat of hydration, Btu per mix. Qi 0 sensible heat gain from other ingredients, Btu per m,T to< 0 weight of ingredients other than flour and water, pound:
per mix. 4 0 temperature of other ingredients, Fahrenheit. Qm 0 heat of friction from motor, Btu per mix. P * motor horsepower. 8 0 miring rimA minUtiSL
Qm 0 beat absorbed by ingredient water, Btu per mix. u. 0 weight of water used in final dough mix, pounds per mi* t, 0 temperature of water used in final mix, Fahrenheit. Qm 0 net heat gain per dough mix, Btu per mix. Qt 0 total theoretical cooling requirements, Btu per hour. N 0 number of dough mixes per hour.
FERMENTATION
After completion of the sponge mix, the sponge is placed in large troughs which are rolled into an enclosed conditioned space for a period of fermentation. This period lasts for three and one half to five hours, depending on the dough formula.
The sponge comes out of the mixer at a temperature of 76-78 F and during the fermentation period, the sponge tem perature will rise from 8-10 F deg as a result of the heat pro ducing yeast action.
In order that the temperature may be substantially equal ised throughout the dough mass, the room temperature is maintained at the approximate mean sponge temperature of 80 F. Even temperatures throughout the batch produce even fermentation action and a uniform product.
Water makesup a large partof the sponge and uncontrolled evaporation causes significant variations in the quality and weight of the bread. A certain amount of evaporation is re quired to remove excess alcohols and esters which produce too strong a flavor. The rate of evaporation from the surface of the sponge varies with the relative humidity of the ambient air and also with the rate of air flow over the'surface. The rate of movement of moisture from the inside of the sponge to the surface does not react similarly to the same external condi tions, and the net result is the drying out of the surface and formation of a crust. The formation of the crust produces an inactive - area which causes undeveloped portions, which when later folded into the dough mass produces the hard, dark streaks that show up in the finished bread.
To control the rate of evaporation from the surface of the sponge, the air is maintained at a relative humidity of 75 percent and air movement over the surface is restricted. Con trol of air movement requires an efficient means of introducing conditioned air into the process room and the use of a multi plicity of return air openings spaced around the entire pe riphery of the room. With the use of perforated ceiling panels at an 8 ft level, an air quantity of as much as 18 changes of the room volume per hour has been successfully used. Less efficient methods of air introduction make it necessary to reduce the air volume substantially.
In older installations, cooling of the air in the process room is accomplished with pipe coils suspended from the ceiling together with open humidifiers within the room which provide the humidity control. The high relative humidity require ment causes a large amount of condensation on the pipe coils which is very hard to collect without some detrimental drip ping on the products.
Bakeries
387
Modern installations use an. air-conditioning unit with air temperature control and humidification handled within the unit, allowing conditioned air without free moisture to be circulated through the room to pick up the heat load.
In calculating the cooling load, the product is not consid ered, as the air temperature is being maintained at approxi mately the mean of the temperatures of the various doughs in the room. Transmission heat loss through walls, ceiling and floor is the principal load source. Infiltration is estimated as
times the room volume per hour. Usually the light re quirements for a fermentation room are approximately 75 watts per 400 sq ft of floor.area. The conditioning units are often placed within the conditioned space, and the full motor
heat had must be considered. The only possible source of latent heat would be about 0.5
percent weight loss in the sponge. Under full operating load this could account fora 1.5 F deg increase dew-point tempera ture. For conditions of SO F db and 75 percent rh, the dew point temperature would be 71.5 F, and the supply air would be introduced into the conditioned space at 72 F dry-bulb and
70 F dew point. In large rooms sufficient air volume can be introduced to
pick up the sensible heat load with an 8 F deg rise in air tem perature. In smaller rooms it is often necessary to introduce a latent heat load by spraying water directly in the room by means of compressed air atomizing nozzles. The introduction of free moisture into the open air always presents a condensa tion problem and consequently is only employed when abso lutely necessary. Water sprays have been most successfully used when a relatively large number of small nozzles have been
spaced around the periphery of the room. Due to the importance of the relative humidity control,
the cooling is usually controlled by a wet-bulb, thermostat. This can cause serious 6hort cycling if the refrigeration con densing unit is oversized. To maintain a high removal ratio of sensible heat to latent heat, the condensing unit is usually specified for operation as close to 60 F evaporator temperatore as is practicable with the temperature and quantity of
condensing water available.
BREAD COOUNG
The baked loaves come out of the oven with an internal temperature equalized at 212 F due to the evaporative cool ing effect of the moisture being driven off during baking. The
crust temperature is closer to 450 F. To cool the loaves for handling and slicing, they are re
moved from the pans and allowed to cool to an internal tem perature of 90-95 F. The cooling of a hygroscopic material takes place in two stages or phases, which are not distinct periods. When the bread first comes out of the oven, the vapor pressure of the moisture in the loaf is high in comparison to the vapor pressure of the moisture in the surrounding air. A rapid displacement of moisture takes place with a resultant evapora tive cooling effect, which, combined with heat transmission at a relatively high temperature differential from bread to air, causes rapid cooling as indicated by the steepness of a timetemperature reduction curve (Fig. 1) in the early stage of cooling. As the vapor pressure begins to approach equilibrium, the heat transfer is mainly by transmission and the cooling
curve flattens out rapidly. Many bakeries carry out the cooling on racks standing on
the open floor and cooling times vary from l$^-3 hr, depend ing on seasonal air conditions in the bakery. Where time con trol becomes an important factor, due mainly to present day delivery schedules, tunnel-type cooling enclosures are used
with controlled temperature counterflow air cooling being em ployed.
The cooling tunnel may be a prefabricated insulated room similar in design to the proofing room with doors at both ends of a series of aisles. The racks of baked bread are moved through the room in one direction while the conditioned air flows in the opposite direction.
Other types of cooling arrangements employ travelling trays carrying the bread back and forth in descending tiers, or a descending spiral conveyor. These coolers are usually automatically loaded and unloaded for handling large steady productions. Conditioned air in these arrangements is usually introduced into the bottom of the enclosures and exhausted from the top to approach as close as possible the counterflow cooling action. *
Bread can most satisfactorily be sliced and wrapped without
Fig. 1 .... Moisture Loss and Air Temperature Rise in Counterflow Bread Coding Tunnel
successive condensation on the inside of the wrapper at 9095 F. Excessive condensation can encourage mold spore de velopment.
Approximately 90 min of cooling time is required to bring the internal loaf temperature to 90 F because of the more or less fixed time factor for cellular movement of beat and mois ture from the center of the loaf to the surface (Fig. 1).
In counterflow cooling the optimum temperature for the air introduced into the cooling tunnel is about 75 F. A relative humidity for the entering air of80-85 percent will control the moisture loss from the bread during the latter stage of cooling and will improve the keeping quality of the bread.
Attempting to shorten the cooling time by forced cooling with air temperatures below 75 F is not satisfactory because the rate of heat and moisture loss from the surface, and the movement of the heat and moisture from the interior to the surface as a replacement, becomes so unequal that shrivelling and cracking of the crust results.
Cooling time, however, is often shortened when mold inhibitors are used, by taking the bread to the slicers at 105110 F.
The cooling load is calculated on the basis ofa sensible heat transfer based on a specific heat of 0.74 Btu per (lb) (F deg) for bread, and a temperature reduction from 180 F to 90 F. The evaporation of moisture from the bread may be consid ered as being responsible for reducing the bread temperature to 180 F for calculating purposes. The heat transmission