CHAPTER 44
1950 Guide
where-
Q = quantity of air circulated, cubic feet per minute. V = rate of generation of contaminant, cubic feet per minute. MAC = maximum allowable concentration, ppm by volume. SAC = concentration in eupply air, ppm by volume.
The rate of generation of the contaminating vapor will often be available as a weight or volume of liquid evaporated into the space per unit time. These may be converted to the units of Equation 1 by applying the principle that a pound-mol of a gas or vapor will occupy approximately 359 cu ft at standard pressure and tempera
ture. Thus,
W t 4- 4110
cfm (vapor) =' jj- X 359 X
-
(2).
where
W = rate of generation of contaminant, pounds of liquid solvent per minute. Mw = molecular weight..
t = air temperature, Fahrenheit.
A special case occurs where local concentrations of solvent vapors at the breathing zone, resulting from concentrated sources of: contamination, are intolerably higher than the average design concentration when using dilution methods. Data are available for calculations, but involve many assumptions regarding boundary condi
tions, such as convection area and random air movement in the vicinity. 2. Dusts and Fumes. Maximum allowable concentration of various dusts, fumes
and mists are also tabulated in Chapter 8. However, the dilution method as a means of treating particulate contaminating agents should be used with care, since the
allowable air movement in spaces will ordinarily be lower than the capture velocity required for such particles. Exhausting at the source (see Chapter 45) will generally be the recommended treatment for these particulate contaminants.
3. Sensible Heat. Excessive sensible heat contamination is subject to treatment,
similar to that for vapors, by the dilution method, the difference being that the rate of generation of the contaminant must be expressed in units of energy rather than volume or weight, and that the effect will be expressed-as excessive tempera ture. In this case, the circulated air required will be:
H Q \ (l, - fo) X d X e
(3)
where
Q *= quantity of air circulated, cubic feet per minute. H = rate of generation of heat, Btu per minute. U = allowable temperature in the space, Fahrenheit. f,, = temperature of supply air, Fahrenheit. d = density of air in pounds per cubic foot,
e = specific heat of air.
In some cases, such as ventilation systems not employing refrigeration, unusually large and uneconomical air quantities may be required when the desired or tolerable temperature approaches too closely the temperature f,, of the dilution air. This condition may sometimes he corrected by a. combination of treatment by dilution and central exhaust, large sources of heat load being eliminated by exhaust through hoods at the source.
Heat Storage in Structure
A special condition is sometimes encountered in large masonry struc- i tures when, due to the heat storage capacity and time lag of the structure, i a prolonged period of hot weather may cause storage of such large quanti- \
Industrial Air Conditioning
917
ties of heat in the structure that they continue to be a source of heat-load after the outside weather has moderated.
In general, the solution to ventilation problems by the simple dilution method is limited to cases where a practical and economical equilibrium may be established between the maximum rate of generation of the con taminant distribution and cost of the air required for its removal.
Control of Radiant Heat
One of the most difficult problems of ventilation engineers is found in the so-called hot industries (steel mills,, paper mills, foundries, etc.) where radiant heat from high temperature surfaces is a. most important factor, the magnitude of which is not always appreciated. Since ventilation cannot remove radiant heat, it is worthwhile to consider using low. emissivity materials and shielding to minimize conversion to sensible heat' due to interaction with surfaces within sight of the radiant source.
Odors
There is little information available either on the rate of generation of common odors, or on the maximum concentration which would be tolerated by a majority of persons. Thus a quantitative- specification covering systems for locker rooms and toilet rooms, or other applications where odors constitute the contaminant, is not now possible. Pending research in this important field, it is suggested that the data in Table 1, Chapter 6, showing the outside air supply required per person, at various socio economic levels, be used.
BIBLIOGRAPHY
Processing
Refrigerating Data Book, Refrigeration Applications Volume, Second Edition. 1948. Section VIII. In dustrial Air Conditioning, Chapters 67 to 76, and Section HI. Refrigeration in Food Manufacture..Chapters 25 and 26, American Society of Refrigerating Engineer*...
Air Conditioning in the Bakery, by W. L. FIeither (A.S.H.V.E. Transactions, Vol. 37, 1931, p 141)
^Co^i.VOI1^e Bakery Throughout, by-W. W. Reece (Heating,,Pipingand Air Conditioning, August,
1936, p. 419). The Air Conditioning of Processes in the Bread Bakery, by H. R. Gable (A.S.H.V.E. Journal
Section^ Heating, Pipirui and Air-Conditioning, October 1947,.p. 107).
. Cpuditioning in Candy Manufacture, by H. Cl Hoffmann (Section 39, Refrigerating Engineering
Application Data, Refrigerating Engineering, April, 1947). Proper Air Conditions for the Manufacturing of
Confections, by A. E. Stacey, Jr. (A.S.H.V.E. Journal Section, Heating, Piping and-, Air Conditioning.
October, 1937, p. 640).
.
v i^Co^ikoaing for Sausage Manufacturing Plants, by M. G. Harbula (A.S.H.V.E. Transactions, Voi. 28, 1922, p. 343).
Relation of Air Conditions to Tobacco Curing, by J. Johnson and W. B. Ogden (Wisconsin Agricultural Research Bureau 110: 1-48, 1931).
. Heating, Air Conditioning and Insulation for Penicillin Production, by J. C. Siegesmund (Heating. Pip. ing and Atr Conditioning, August, 1944, p. 475).
Air Conditioning in Textile Mills, Research Department Technical Report, Textile Workers Union of America, C.l.O. Air Conditioning for Textile Plants Making and;Using Synthetic Yarns, by L. L. Lewis (/Catron Textile Monthly, July, August, September,. 1930). Refrigeration for Textile Mill Air Conditioning, by P. L. Davidson (Heating and Ventilating, May, 1947. p. 57).
Bureau of Standards Studies Determine Press Room Conditioning Requirements, by C. G. Weber (Heating. Piping and Air Conditioningf March, 1936, p; 137),. Humidity'in the Pressroom (Heating and VentiWWW. May, 1932, p. 35). Dehumidifying with Gas in a Printing,Plant .(Heating and Ventilating, May, 1935.
P* Air Conditioning the Newspaper. Plant,.by .R.T..Williams (Heating and Ventilating, September,
1937, p. 63).
'' -
Air Conditioning in the Paper Industry (Heating and Ventilating, October, 1935, p. 23). -- Air Conditioning Requirements of Multioolor Offset Printing, by C. G. Weber (Refrigerating Engineering,
P* G); Reactions of Lithographic Papers to Variations in Humidity and Temperature, by Weber and L. W. Snyder (U. S. Bureau of Standards Journal of Research, January, 1934). The Treat ment of Offset Papers for Optimum Register, by C G. Weber and M. N. V. Geib (U. S. Bureau of Standards Journal of Research, February. 1936). Silica Gel Air Conditioning System Seizes Rotogravure Printing riant, by H. E. Ryerson (Heating, Pi-ping and Air Conditioning, August, 1937, p. 497).
. Air Conditioning for Clothing Research Laboratory (Heating and Ventilating, July, 1943, p. 69). Re1nMj^, tpi.o7n9).Insures Quality of Clothing for the Army, by A. J. Mallinckrodt (Heating ana Ventilating, March,
Controlled Air Supply for Supercharger, Carburetor and Engine Testing, by C. S. Leopold (Refrigerating
Engineering, August, 1943, p. 85).
- ^"
i , Machine Tolerances Possible Through Temperature Control, by R. P. Dewey (Heating and Venti lating, April, 1944, p. 60).