CHAPTER 40
1960 Guide
Toble 3____Sequence of Mechonicol Integration Tower Performance
2
Enthalpy of fifa
b*
3 Enthalpy of Air
5.
4 Enthalpy PiS.
b'-h.
5
1 h'-h.
6 AB Aih'-hJ
7 X
fc'-A.
48.22 49.43 50.66 51.93 53.23 54.56 55.93 63.32 71.73 81.34 92.34
38.61 39.81 41.01 42.21 43.41 44.61 45.81 51.81 57.81 63.81 69.81
9.61 9.62 9.65 9.72 9.82 9.95 10.12 11.51 13.92 17.53 22.53
0.1042 0.1041 0.1038 0.1030 0.1020 0.1006 0.0988 0.0868 0.0718 0.0570 0.0445
0.1042 0.1039 0.1034 0.1025 0.1013 0.1002 0.4640 0.3965 0.3220 0.2537
0.1042 0.2081 0.3115 0.4140' 0.5153 0.6155 1.0795 1.4760 1.7980 2.0517
e Cooling Rang*
1 2 3 4 5 6 11 16 21 26
W. Air enters the tower at wet-bulb temperature having an enthalpy of ht, which is plotted vertically below hi. Since the heat removed from the water equals the beat added to the the enthalpy increase per pound of dry air equals the
temperature change of the water multiplied by the liquid/gas (L/G) ratio. The enthalpy of the air, therefore, increases along a straight jin* having a slope equalling L/G and terminating at h% which is vertically below h%. The driving force at any section of the tower is A' - K , the vertical distance be tween the two operating curves.
Example l: It is desired to cool 300 gpm (150,000 lb of water
Gr hr) from 110 to 84 F with 3050 cfm (125,000 lb of dry ait per ) with an entering wet-bulb temperature of 75 F. Calculate the (NTU) showing the successive steps in tabular form.
Solution; The sequence of steps in the mechanical integra
tion is shown in Table 3.
Water temperature is entered in Column 1 in even, but not necessarily equal, increments. One-degree increments are used from 84 to 90 r where the potential difference is small, and the effect of the reciprocal is large- Little accuracy is sacrificed by lifting 5-degree increments from 90 to 110 F where the potential difference Is larger and its reciprocal smaller. Column 2 shows the enthalpy of saturated air corresponding to the tempera tures in Column 1. Air enters the tower at a wet-bulb tempera ture of 75 F, having an enthalpy of 38.61 Btu per lb of dry air. This value is entered at the top of Column 3. The enthalpy of
the air increases by AA --
The L/G ratio is j^'oOO ^ ^
so Ah equals 1.2 Btu from 84 to 90 F and 6 Btu from 90 to 110 F. These increments are added to the initial enthalpy to obtain
the successive values in Column 3. The enthalpy potential dif
ference in Column 4 is the difference between Columns 2 and 3. This driving force appears in the denominator of Equation 2
so the reciprocal of Column 4 is entered in Column 5. The (NTU) within each increment equals the temperature change multiplied by the average of the entering and leaving values
from Column 5. The products are entered in Column 6. The
summation of Column 6 in Column 7 gives the (NTU) for the cooling ranges in Column 8. Hence, the mechanical integration reduces the given conditions to the numerical value of 2.0517 Transfer Units.
Example t: The cooling tower designed to handle the condi tions in Example t has a fill height of 8 ft and a plan area of 96 sq ft. Calculate the unit-volume and overall coefficients and explain their significance.
Solution: The (NTTJ) of 2.0517 as determined in Example 1 signifies the tower must cool the water 2.0517 deg perf Btu of piaftn driving force. This cooling is accomplished in 8 ft of fill
height, so the unit-volume coefficient is --g-- " 0.2565. This
mftng that each cubic foot of tower must cool the water 0.2565 degrees per Btu of mean driving force. The water loading w
. 1563 lb per (sq ft) (hr). The overall coefficient is
0-2565 X 1563 * 400.91. This signifies that the tower must trans fer 400.91 per cu ft (hr) (Btu of mean driving force).
Column 7 of Table 3 shows how the (NTU) increases with cooling range. A plot of Columns 7 vs. 8 can be used to de termine the (NTU) for intermediate cooling ranges. This curvd can also be used to determine temperature distribution be cause equal increments of transfer unite correspond to equal increments of tower height. The linear relationship between
(NTU) and height provides the bass of the procedure used to analyze crossflow cooling towers.11
Since the water temperature varies both horizontally and vertically in a cross-flow tower a double integration is re quired. This is accomplished by using equal increments of transfer units, representing equal increments of distance, and calculating the corresponding temperatures. Counter-flow integration progresses from the bottom of the tower upward. The cross-flow integration starts at the top of the air inlet,
and progresses downward and inward.
Evaporative Apparatus for Heat Rejection
603
Required and Available Coefficients
Any set of performance conditions can be accomplished by an infinite number of cooling tower designs. Calculating the (NTU) serves to evaluate the degree-of-difficulty of the prob lem. The xcmt-oolume coefficient is more specific, but it also applies to an infinite number of towers of a given height. The overall coefficient has the most significance when comparing towers of different designs that are being considered for a given duty. It evaluates the effect of variations in air rate, height, and plan area on the required coefficient. A higher required coefficient indicates that more effective filling is needed. The effectiveness of a filling is determined almost entirely by the density of the splash surface and wetted surface per cubic foot of filled volume.
These calculations evaluate the problem, not the tower. The available coefficient of a specific cooling tower is deter mined from its operating characteristics. The tower must be . tested at various conditions and the data from each test re duced to a corresponding coefficient. A cooling tower coeffi cient is not constant, but varies with operating conditions. Its characteristic is established by correlating variations of the coefficient with corresponding operating conditions.
The characteristic of a cooling tower closely approximates the relationship expressed by the general equation:
Ka = cL*<?
(7)
The cooling tower manufacturer uses this procedure to de termine the characteristic of each cooling tower design.
An examination of the steps taken in the solution of Ex ample 1 will show that various air rates could have been speci fied. Increasing the air rate would have reduced the degreeof-difficulty and resulted in a smaller (NTU) for a given set of conditions. Decreasing the air rate would have the opposite effect. Therefore, the required coefficient for a given set of conditions varies with the air rate. A tower will operate at'a given set of conditions when the required coefficient equals the available coefficient as determined from Equation 7.
DESIGN CONDITIONS
The design conditions used in selecting a cooling tower are (I) the circulating water rate, (2) cooling range, (3) entering wet-bulb temperature, and (4) the approach of the coldwater to the wet-bulb temperature. These conditions are se-
Fig. 9 .... Relation of Cooling Tower to Process
Iected by considering the function of the cooling tower in the overall system. The system includes a process having a heat load that is to be transmitted to the circulating water through a heat exchanger. The cooling tower rejects the heat load to the atmosphere. Certain design conditions of the system affect the design of the cooling tower. They include (1) the heat load, (2) the temperature at which it is to be removed, and (3) the wet-bulb temperature of the atmosphere to which the heat is finally rejected. The cooling tower and heat exchanger are then selected to serve these conditions. The relationship of the cooling tower to the system is shown schematically in Fig. 9, with the process represented by two heat sources op erating in series.
Heat Load
No definite sequence can be followed in selecting the design conditions because each item affects the choice of the others. The heat load comes closest to being a fixed quantity so ran be considered first.
The amount of heat rejected by typical processes is shown in Table 4. The heat is rejected at a constant temperature when vapors are condensed, as illustrated by Q* in Fig. 9. A second type of heat load, represented by Qt, consists of reducing the temperature of a fluid. Each type of heat load has specific requirements that affect overall design. The tem perature at which the heat is removed from a process may be as important in the overall design as the heat load itself. As this temperature level decreases, the degree-of-difficulty increases at an accelerated rate, calling for larger and more expensive equipment. Higher temperatures usually result in higher operating costs, and loss of capacity in the process.
Table 4 .... Heat Rejection of Typical Processes
Equipment
Blu par
orinpar too
Btv par kw hr
Bfv par bhp-fcr
Refrigeration Compressors (reciprocating)...................................
Refrigeration Compressors (centrifug&l)..........................................
Refrigeration Absorption System.. Steam Jet Refrigerating System.... Steam Electric Power Plant:
500 kw............................................ 1000 kw............................................ 5000 kw............................................ 7500 kw............................................ 10,000 kw............................................ Diesel Engine Jacket A Lube Oil: Four-cycle, Supercharged.............. Four-cycle, Non-supereharged... Two-cycle, Crank-case Compressor..................................................... Two-cycle, Pump Scavenging (large unit).................................... Two-cycle, Pump Scavenging (high speed).................................. Natural Gas Engine: Four-cycle.......................................... Two-cycle...........................................
250
300 550 550
11,210 10,750 8,150 7,700 7,020
2600 3000
2000
2500
2200
4500 4000