than comparable oil-filled units; the average cost is $12,000 per magnet. In addition, Eriez offers a proprietary air-cooled electromagnet which has underwriters laboratory approval for use in dirty and dusty environments. These wits cost an average of $10,000 each.
Servicing; The PCB electromagnets are similar in construction to askarel transformers, and it is anticipated that the magnets are subject to the same failure mechanisms, expected service life, and service practices as the transformers. If the average remaining service life of the PCS electromagnets is ten years, the magnets would be expected to fall at the rate of twenty wits per year. Although rewinding failed magnet coils would probably cost 60% of the cost of a new magnet, rebuilding Is bamed by the regulation. The transportation and labor costs would be expected to be the same whether a magnet is replaced or rebuilt, so the effect of the ben on rebuilding is to forego a potential savings of 40% of the purchase cost of a new magnet each time a PCB magnet fails. Total annual coats would be expected to be (20 aagnets per year x 40% of $12,000 per magnet ) $96,000 per year. Tbtal costs attributable to the bm on rebuilding PCB electromagnets will be $960,000.
Disposal; The PCB Ban Regulations authorize the disposal of drained PCB electromagnets in chemical waste landfills. The previous PCB Disposal and Harking Regulations (EPA, 1978a) authorized only incineration. Since incineration is not available for magnets, a petition for alternating disposal means would have had to have been submitted to the DA each time a magnet required disposal. There is no information in the record on which to base an estimate of the cost of preparing and processing such petitions, but this cost has been eliminated by the Ban Regulations.
9.4 PCBa Controlled by the Regulation The PCB electromagnets presently in use contain about 207,900
pounds of PCBs. The regulations do not affect the continued uae of these
84
HONS 013296
nyiiTT Ihe effect of the ban on rebuilding these magnets will be to eliminate the loss of KBs to the atmosphere that might occur during the rebuilding process. If these losses were 1 to 10 pounds per magnet, as estimated in Chapter 4 for aakarel transformers, the regulations would be aspectad to reduce the amount of KSs entering the environment by (300 septets x 1 to 10 pounds KBs per magnet - ) 200 to 2000 pounds of KBs.
9.5 Sumasrv - Economic Inpacts
Ban on rebuilding} $96,000 per year; $960,000 total.
Disposal; Elimination of costs of preparing and processing petitions Cor disposal by means other than incineration.
9.6 Post Per Pound of KBs Kept from the Environment
Cost per pound
$960,000_______ 266 to hodto pounds
$480 to $4800 par pound PCBs
85 HONS 013297
10.0 HYERAUUC SYSTEMS
10.1 Present Use of PCBs in Hydraulic Systems
Prior to 1972, PCB baaed hydraulic fluids were marketed by Monsanto undar the trade nans Pydraul* for uss in.hydraulic systems where suparlor fire resistance was necessary for protection of life and
property.* A previous EPA sponsored study reported that sales of Pa bMed hydraulic fluids during the period 1970-1971 totaled over 13.5 million
pounds to 585 different firms (Versar, 1978, p. 65). General Motors
Corporation reported that GM used PCB baaed fluids in the following types of systmns:**
Metal die-casting equipment Trim press hydraulics Plastic injection molding machines Metal melting furnace tilt hydraulics Industrial elevators Iron foundry pouring equipment Molten iron holding furnace equipment Induction hardening machine hydraulics Plane hardening equipment Heat-treating furnace hydraulic systems forge furnace hydraulic systems forge press hydraulic systems High tension welding machines loading dock levelers fork lift trucks Other nail miscellaneous systems.
Uses of PCBs by GM were reported to be: Die-casting - 56t>
foundry - 35%; other uses - 9%. A review of Monsanto's customer list for 1970-71 indicated that 80% of the purchasers of hydraulic fluid were
primarily die-casting operations and the other 20% were primarily steel ocapanies (Versar, 1978, p. 65).
Hesse, John L. 1975. "Polychlorinated Biphenyl Usage and Sources of Loss to the foviroramnt in Michigan." National Conference on Polychlorinated Biphenyls, Hoipembu- 19-21, 1975. Chicago, Illinois. MMhington, 0. C.: ' office of toxic Substances, u. S. fovirormmntal Protection Agency (Report NO. EPA-560/67-75-004), p. 129.
""Letter from Mr. W. R. Johnson (General Motors Corporation) to EPA dated August 7, 1978.
86
MQNS 013298
Whan Monsanto discontinued the sale of PCB baaed hydraulic fluids in 1972, they racomaandad to their customers (1) that there mbs no need to drain the systems and (2) that compatible Monsanto hydraulic fluids could be used to replace leakage. Mast hydraulic systems require the addition of new or reclaimed fluid at a rate of two to ten times the systma capacity each year to replace leakage losses. It is fairly common practice to recover leaked fluid and to process it for reuse. Availtole data on residual PCB levels in hydraulic systems Indicate that the concentration of VCBs ranges from 60 ppa to as high as SOt in a few machines (Versar 1978, p. 66). the differences in concentration apparently reflect differences in the rate of leakage fro* various machines and differing company maintenance policies regarding periodic total replacement of hydraulic fluid.
Mr. Owain Powkea of RADCO Gorp. reported that the hydraulic fluid which ia camaercially reclaimed aometimes contains up to 6000 ppa PCBe.* Therefore, it is possible that the use of reclaimed hydraulic fluid has resulted in the PCB contamination of hydraulic systovs which never contained PCB baaed pydraul* fluids.
Oie-cestlng machines! The analysis of the proposed PCB Ban Regulations suggested that PCB baaed hydraulic fluid may have been used in as many 1000 die casting machines. This estimate was based on the assumptions that 80% of the hydraulic fluid sold during 1970-71 was used in die-casting machines, that the annual makeup requirement of new fluid to replace leakage is equal to the liquid capacity of the hydraulic system, and that the average die-casting machine has a capacity of 500 gallons of hydraulic fluid (Versar, 1978, pp. 65-66). Mr. Johnson of General Motors suggested that this estimate may be in error because not all of the hydraulic fluid parchseed by companies classified as primarily die-casting concerns was used in die-caating machines; Qt used only 56% of their PCB
`Telephone conversation with L. POurt (Versar), September 19, 1977, as rsportad in versar, 1978.
87
MQNS 013299
hydraulic fluid in die-casting machines and the rest in associated equipment and in their steel foundry operations.* The Outboard ferine Corporation plant in Waukegan, Illinois, contains 135 die-casting machines, 60 associated trim presses, 30 electric melting furnaces, and several ocher furnaces plus numerous other systems, all of which contained FCB based hydraulic fluid prior to 1971.** The average capacity of the die-casting machines at Outboard Narine is 350 gallons: Qi reported that its die-casting machines had an average capacity of 460 galIona at one plant and 1580 gallons at another plant.
Mr. Willias Sharp of the Society of Die Casting fegineers stated that die-castinq machines are long-lived pieces of equipment with some 35- to 40-year-old machines still in operation. These machines are in use by 1500 to 1800 separate companies, and perhaps 35% of the ocmpanies used synthetic hydraulic fluids (not necessarily FCB based). There Is a very active market for used machines.***
Based on the available information and assuming that 80% of the ocmpanies buying fluid had die-casting machines, that 60% of the fluid purchased by these companies was used in this type of machine, and that the average annual requirement for makeup fluid was equal to the system capacity of 400 gallons, the number of die-casting machines that once used FCB baaed fluid may have been as high aa 700 machines as calculated in Table 10.1-1. Na Information la available on the meter of companies that own FCB contaminated die casting machines. However, it should be noted that not all the machines that used FCB based hydraulic fluid can be identified from the records because many machines have been resold since 1971. If the total mater of die-casting machines In use Is 10,000 to 15,000 (setirate based on an average annual production of 500 machines and an aasuaad average ownership of 6 to 10 machines per company), only 5 to
`Letter froo Hr. w. R. Johnson (General Motors Corporation) to Oft dated ftuagust 7, 1978. **0ral testimony of Hugh Thomas (Outboard Marine corporation) at the hearings on the FCB Ban Regulations, August 25, 1978. Oral testimony by Millias Sharp (Society of Die Casting Engineers) at the hearings on the FCB Ban Regulations, August 25, 1978.
88 HONS 013300
Figure 10.1-1
Calculation of timber of Pie-Casting Machines that Used : KB Based Hydraulic Fluids
Total sales of PCB hydraulic fluid, 1970-1971
+ Number of years
Annual sales of PCB hydraulic fluid
4- Weight of fluid per gal
Gallons FCBs per year
x Asaimed fraction purchasing companies owing die-casting aachines
Gallons FCBs purchased by companies owing die-casting machines
x Asaused: 60% used in die-casting aachines as makeup fluid
Gallons per year uaed as makeup fluid
4 Assaned; 400 gallons per year per die-casting machine required as makeup fluid
Maher of die-casting machines using PCB baaed hydraulic fluid
13,500,000 pounds FCBs
2 6,750,000 pounds per year
11.5 pounds per gal 587,000 gallons per year
x .8 470,000
x .6
282,000 i 400
704
89 HONS 013301
7t of the Machines presently in service ever used PCB based hydraulic fluid. However, many of the other machines may presently be oonUsdnatad with PCBs because of the practice of reclaiming hydraulic fluid.
Other hydraulic systems; General Motors reported use of FCB baaed hydraulic fluids in systros ranging from SO gallons to 4000 galloro, with most of the systems being in the 300 gallon range.* Oossmnts submitted by Aneco, Inc., (dated August 3, 1978) slinearized the results of testing 50 heat transfer and hydraulic systems with an average capacity of 422 gallons. This is reasonably consistent with an average hydraulic system capacity of 3S0 gallons. It implies that perhaps 1,000 other hydraulic systass used PCB baaed fluids in the years 1970-71, srosiliij these systems require proportionately as much hydraulic fluid for ssfcaupi as do Ale-casting machines. These systems were probably owned by all of the companies having die-casting machines plus perhaps an additional 100 steel companies.
total PCBs presently in use: total capacity of all of the hydraulic systarns that at one tiro used PCB based hydraulic fluids nay be (700 die-casting machines x 400 gallons per machine + 1000 other aystroa x 3S0 gallons per system - ) 630,000 gallons. (X repotted that 804 of their die casting systwa have FCB concentrations below 500 pp*i Outboard Mrlme reported that racent spot checks of their machine show PCB levels aromd 100 ppm, ooaparad to a range of 210 to 1400 ppm in 1976 and 1977**. It Is therefore likely that the average concentration of PCBs in hydraulic Quid ia between 100 ppm and 500 ppm if the single group of die casting machines known to contain 504 PCB fluid is excluded as a special cast. If the average density of the presently used hydraulic fluid is tan poinds par gallon, the total maount of PCBs in uae in hydraulic systros may be (630,000 gallons x 10 lb per gallon x 100 ppm to 500 ppm fcbb ) 630 to 3150 poinds of FCBe.
Letter from W. R. Johnson (General Motors Corporation) to EPA dated August 7, 1978. Letter from Hugh Thcmas (Outboard Marine Corporation) to EPA dated August 3, 1978.
90 HONS 013302
10.2 Requlrsmente of the PCB Ban Regulation
Continued use of hydraulic systems contaminated with FCBs in
excess of SO ppm is authorized ixitil January 1, 1984, subject to the
following requirements:
o Testing: Required for all machines that ever contained a KB based hydraulic fluid by July 1, 1979, and at least annually thereafter as well as three months after each refilling performed to reduce the concentration of FCBs to below SO ppm.
o Marking: Hydraulic systmes containing liquids oontaaonated with over 50 ppn FCBs must have the special PCB label applied.
o Retrofill: Retrofilling or topping off with a hydraulic fluid containing less than 50 ppn FCBs is required within 6 months after ary test vhich show that the concentration of FCBe exceeds SO ppm.
o Disposal of contaminated fluid: Hydraulic fluid containing over 50 ppn PCBs must be disposed of by incineration in special approved PCB incinerators or by incineration in other facilities such as high efficiency boilers approved by the EPA Regional Nkoinistrators. This material can also go to Chemical Waste landfills or high efficiency boilers if'it is between 50 and 500 ppm.
o Storage: Special storage facilities required for the storage for reuse or processing of hydraulic fluid contaminated with more than 50 ppm FCBs.
o Disposal of contaminated machine after liquid is drained for incineration: Essentially not regulated (either eadvage or disposal as non-hazardoue waste allowed) provided the fluid is first drained from the machine and, if the fluid contained over 1000 ppm FCBs, the hydraulic systos is, flushed with clean solvent.
o Reclaiming of contaminated hydraulic fluid: Hydraulic fluid contaminated with more than 50 ppm FCBs may be reclaimed for reuse In the owner's hydraulic systmas only if it is treatad to reduce the concentration of FCBa to below 50 ppn. Reclaiming for purposes of resale is banned unless this activity is exempted by the EPA.
10.3 Poet Insects of the PCB Ban Regulation
Testing: Most of the hydraulic systems that once used PCB
fluids have since been refilled with fluids based on phosphate
91
HONS 013303
esters. Analysis of phosphate esters for the presence of FCBs requires a rather tine conslining treatment of the sample and extraction of the FCBs before injecting the prepared sample into a gas chromatograph. In their written comment dated August 3, 1978, to the EPA on the proposed FCB Ban Regulations, Armco Inc., stated that their average cost to analyse hydraulic fluid for FCBs "...is probably closer to $200 ttun the Wersar estimate of $300, once the OC equipment is set up to specifically analyse for FCBs. Laboratories which would only occasionally analyse such samples would probably incur costs exceeding $300 per eaqile." Only seven of the SO systems checked by Armco contained FCBs in excess of 1000 ppi.
Identification of all systems that contained FCB hydraulic fluids will require the analysis of the fluid in many systaas Oiich might have contained PCBs. As many aa 2500 die-casting machines (Versar, 1978, p. 75) and perhaps as many other hydraulic systems might have to be tested to identify the approximately 1700 systaas which used FCB fluid and to evaluate the extent of ccntmaination from the use of reclaimed fluid. The coat of the required sapling and analysis program will Include smiling and administrative costs of perhaps $20 per system in addition to the laboratory costs of perhaps $250. Costs for the analysis prograa required by July 1, 1979, might total (1700 to 5000 systems x $270 per staple ) $460,000 to $1,350,000. Since the average FCB concentration is probably in the range of 100 to 500 ppm, most of the systoes will have to be retrofilled within six months and tested again within the next year. A second retrofill and another test might be required. Tt>tal testing coots could easily exceed $1,000,000.
Since the concentration of FCBs will continually decrease in the hydraulic systems because of retrofilling, leakage, and replacement of the fluid, it Is expected that the concentration of FCBs In almost all systems will have decreased to less than 50 ppm by the end of the five years authorized for continued use of contaminated system, and that the testing requiresents would not apply to the systems after that time.
92 HONS 013304
Retrofill: Based on the experience reported by GM and Anaco, it ia expected that most of the systems that ever used PCB baaed hydraulic fluid will be fowd to be contmninated at levels exceeding 50 pps* If this is the case, retroftiling will be required for perhaps 1700 hydraulic systems having an average capacity of about 400 gallons. Anaco stated that the Versar estimate of $14 per gallon for retrofitting was reasonrtle;* & estimated the material cost alone to be $17 to $19 per gallon;** Outboard Marine estimated a cost of $8,000 for a 350 gallon system, or an average of $23 per gallon.*** Total costs of the first retrofitting program would be (175 systmes x 400 gallons per syston x $14 to $23 per gallon ) $9,800,000 to $16,100,000. According to data presented by both Armco and GM, such s retrofilling program might be expected to reduce the concentration of PCSs in the liquid by about 90%. Perhaps 104 of these systems might have PCBe in excess of 50 ppm after being retrofitled, so a aacond retrofill, and in a few caees even a third retrofill, would be required. Dotal ooets for these subeequent retrofitIs mi^it be $1,000,000 to $1,500,000.
fopping off systmas with PCB concentrations only slightly above 50 pps may result in lowering PCBe levels below 50 ppn without incurring the ooets of draining and refilling the entire system.
Disposal of contaminated fluid; Special high tauperature incineration of liquids oontMinsted with PCBe in excess of 500 ppa was required by the PCB Disposal and Harking Regulations. The effect of the KB Ban Regulations is to extend this requirmsent to fluids containing between 50 and 500 pps PCBe. The moat recent available price for this incineration is $55 per 55 gallon dnst (Rollins, 1978) plus drua costs of perhaps $15 par drum, transportation of $.02 per potxid, and drum disposal costs of $30, or a total cost of $.22 per pound for contaminated hydraulic
4Armco, Inc. 'Main Ocmmants,* received by EPA August 3, 1978. : *`Letter from N. R. Johnson (General Motors Corporation) to EPA dated
August 7;, 1978. "Matter from Hugh Tbonas (Outboard Marine Corporation) to EPA dated
August 3, 1978.
93
HONS 013305
fluid. If all of the fluid in the calculated systos capacity of 630,000 gallons required special disposal because of this change in the regulation, increased disposal costs of (630,000 gallons x 10 lb per gallon x $.22 per pound - ) $1.4 million would be incurred. If the use of contaminated reclaimed fluid has resulted in an increased nueber of Systems contmainatad with PCBs in excess of 50 ppn, this disposal cost might increase by a factor of 2 or 3 or more. The required retrofilling will generate a quantity of liquid equal to the calculated syston capacity, resulting in an additional disposal cost of $1.4 million.
The regulations authorize the efa Regional Administrators to approve alternative incineration facilities for liquids such as contaatinatad hydraulic fluids. It is possible that approval for the use of high efficiency boilers might lower the disposal costs substantially, but no estimate can be made of the resulting decreases In disposal costs.
Meriting: The requirasent that the special PCB label be applied to systems found bo contain from 50 to 500 ppm PCBs should not coat more than $2 per machine. Even if (as an upper bound estimate) 2500 such oentmninatad systems were found, total labeling costs would not exceed $5,000.
All of the liquid that is removed from the hydraulic systmas during the retrofill and decontamination activities will also have to be placed in labeled containers prior to being shipped for disposal. At a cost of $2 per 55-gallon drun, labeling costs for disposal oould total (630,000 gallons x 2/55 gallons per drun x $2 per label ) $46,000.
Special storage areas: Liquids contaminated with 50 to 500 ppm PCBs will be allowed to be stored in dross in temporary storage areas prior to disposed if a Spill Prevention, Control and Countermeasure Plan has been prepered for the temporary storage area in accordance with 40 CFR 112.
94 HONS 01330b
There la no Information available in the record that would support on estimate of the mrnfcer of additional SPCC plans that would have to be prepared under this raquirmnent. However, it is assumed that perhaps one third of the 585 firms that bought PCB hydraulic fluid during the period 1870-1971 will be found to have contaminated hydraulic systems and that soma of the 200 firms will therefore have to prepare SPCC plans covering temporary storage areas for PCB contaminated liquid.
Disposal of confineted machines: it is not anticipated that any of the machines will be scrapped before they are decontaminated to a level below 50 ppm PCBs. Therefore, there should be no additional disposal costs due to the PCB Ban Regulations.
Recycling of contaminated hydraulic fluid; New phosphate ester baaed hydraulic fluid costa about $7.60 per gallon (Versar 1978, p. 68). According to the ccnsaents of 91, the following treatment techniques have been found to be incapable of reducing the concentration of PCBs to below 50 ppms PRC carbon filter. Florail filter colimn, and clay. Open air distillation of contaminated phosphate ester fluid resulted in excess oxidation of the fluid. Outboard Marine has described a vacuus distilla tion procedure which reduces the PCB content of the hydraulic fluid by 50% at a cost of $3.75 to $4.00 per gallon*. - Mr. Rober Damiani of RADCO Industries in his oral comnents at the August 25, 1978 hearings, described in general terns a fractional distillation process that is "effective in ranging PCB. In fact, a nunber of runs were made in which PCB concentra tion was reduced to below 50 ppm." Mr. Damiani stated that RADCO has not developed a process that will reliably reduce the level of PCBs to below 50 ppm and that their present process achieves a reduction to 100 ppm. He stated that the result of a 50 p>pm requirement will be to "decrease process yield, and subsequent economics -- 10 to 20 percent below that expected with a 100 ppm specification."
If it is aesimwd that the total amount of contaminated fluid is available for recycling once per year and that there is presently 725,000
*0ral testimony by Hugh Thomas (Outboard Marine Corp.) at the August 25, 1978 hearings on the proposed PCB Ban Regulation.
95 HONS 013307
gallons of such fluid in service, the successful development of a reclaim ing process might reduce costs for new fluid by $2.80 per gallon (baaed an reclamation costs 20% higher than mentioned by Outboard Marine Corp.) or by a total of $350,000 to $1,700,000 per year. It is not known whether the requironent that recycled fluid contain less than 50 ppa PCBs will significantly affect the availabilty of such a reclamation service; the total impact of the regulation therefore cannot be estimated.
10.4 PCBs Controlled by the Regulation
In section 10.1, it was estimated that hydraulic system contaminated with more than 50 ppm PCBs may contain from 630 to 3150 pounds of PCBs. If the use of these systems were not regulated, all of this material would be expected to leak out of the systems and eventually enter the anviroment. The requirasent that the contaminated systws be retrofitted by the end of 1979 will reduce total losses to leeks prior to the retrofilling. Since hydraulic system often require make-up fluid squad to their voluae each year, the looses of PCBs prior to the retrofilling may equal 25% of the PCBs present in the system. The effect of the regulation, therefore, is bo prevent the loss to the environment of .75 x (630 to 3150 lbs - ) 470 to 2390 pounds of PCS.
10.5 St--ary - Economic Impacts
Testing:
1979 1960-1984
$460,000 to 1,350,000 $1,000,000 total
96 HONS 013308
Retrofill:
810,800,000 to $17,600,000*
Disposal of fluid: $1,400,000*, **
Narking:
$46,000
Special storage areas of 8FCC plans: Insufficient data available to estiaate
Ban on recycling contaminated hydrau
lic fluid:
Insufficient data available to estimate. ttaimn possible impact $350,000 to
$1,700,000 per year for one or two years.
10.6 Cost Per Pound of PCBa Kept from the Bwircnnent
Oost per pound - ($460,000 to $1,350,000 + $1 million + $10.6 to $17.6 million * $1.4 million +
$700,000 to $3.4 aillion)/470 to 2390 powds $6,000 to $53,000 per pound FCBs
Sy b. significantly higher if the use of reclaimed hydraulic fluids has contaadnatsd hydraulic systems that never used PCB baaed fluids.
**Nsy be acmeihat reduced if EPA approves alternative incinerators for hydraulic fluids.
97 HONS 013309
11.0 HEAT TRANSFER SYSTEMS
11.1 Present Ue of PCBs In Heat Transfer Systems
In his letter to the EPA dated August 4, 1978, Mr. W.R. CDrey of Monsanto estimated that there were 450 heat transfer systaaa using PCB based fluid in 1972 when Monsanto discontinued sales of KBs for tines systems. A review of a Monsanto customer list, however, indicated that sales of KB heat transfer fluids were made to 533 different companies during the years 1970 and 1971 (Versar, 1978, p. 76). Mr. Oorey estimated that one half of the heat transfer systems had capacities between 50 and 500 gallons and that the other half had capacities averaging 2000 gallons. This implies that the average system capacity was 1300 gallons, or about 15.000 pounds of KB. The total Monsanto sales of beat transfer liquid during 1970 and 1971 was 8.2 million pounds, or enough liquid to fill about 550 average systems. Tbtal use of KB heat transfer liquid in the united States since 1929 has been estimated at 21 million pounds, including both new Installations and makeup fluid (Versar, 1978, p. 75).
Mr. Oorey of Monsanto estimated that over 90% of the heat transfer systems using KBs were converted to alternative non-PCB fluids in 1970-72 and that current system PCS levels in the industry range from anxnd 100 ppm to three percent. Mr. Jack Pulley of Dow Coming, in his reply consent dated October 9, 1978, stated that Dow Coming replaced PCB fluids in their heat transfer systems about five years ago and that these system still contain PCBs in concentrations from 1/2% to about 2% in the new non-PCB heat transfer fluid. Data is also available for one other heat transfer system that contained 14,000 gallons of pcb based fluid. Craining and flushing prior to replacement of the liquid reportedly reduced the concentration of PCBs to two percent (Versar 1978, p. 76). Nansanto and Dow Coming agreed that it is technically infeasible to reduce the concentration of PCBs in oontmninated systems to below 50 ppn.
11.2 Requirements of the PCB 3an Regulation
All heat transfer systems that ever used PCB based fluids will be considered PCB articles because their surfaces are presently in contact
98 HONS 013310
with a liquid containing over 50 pps PCBa. These systens will be allowed to main in aervice wtil July 1, 1964, subject to the following conditions:
e Uae: After October 1, 1979, no heat transfer syetmn containing a liquid with a PCB concentration above 50 ppn may be uaed in the manufacture or processing of any food, drug, or cornutic.
e Testing; Required by July 1, 1979, for all heat trwsfer systems that ever contained a PCB baaed heat trsnafar fluid. aaa must be reteated within three months after each time
rfluid is replaced to reduce the concentration of PCBa to below 50 pps. Records of all testa must be kept for five years after the concentration of PCBa is reduced to 50 pps.
a Betroflll; Within six months following any teat that indicates the presence of more than 50 pps PCBa in heat transfer fluid, the fluid sust be drained and replaced with fluid that contains less than 50 pps PCBa. Topping off that results in reduction of PCB concentration to less than 50 ppm is also allowad.
e Marking; Required for all syatens found to have PCB concen trations in the fluid in excess of 50 ppn.
e Disposal of liquid containing over 50 n PCBa: for liquids with greater than 500 pps PCfes, incineration ia required in an approved PCB incinerator. Liquids between 50 and 500 pps PCBa can go to approved high efficiency boilers or chsmical waste landfills.
e Storage; Special storage facilities required for the storage of PCB contaminated heat transfer fluid.
e Disposal of contasinated machine after liquid is drained; High fperature incineration required In an approved to incinerator or disposal of machine in an appeewed thsmical wests landfill.
11.3 Poet Impacts of toe PCB Ban Regulation
Testing; The liquids used to replace the PCB baaed heat transfer liquids may be analysed for PCBs by a method similar to that used
99
HONS 013311
to analyze for FCBs in tranaformer oil. The cost of such an analysis should be about the same as the price of $60 per sample previously quoted by Versar for the transformer oil analysis (Versar 1978, p. 41). Sampling and order handling costa might increase this cost to $100 per sample, or a total of $45,000 to $60,000 for the analysis required by July 1, 1979, on the 450 to 600 contaminated systems presently in use. Additional testing required within three months of each system retrofill is included below as part of the retrofill costs.
Retrofill: The regulations require that the concentration of FCBs in heat transfer systems be reduced to less than 50 ppn by July 1, 1984. Most of the systems now contain about two percent FCBs. Monsanto tatad that draining most heat transfer systems will remove at least 904 of the fluid, and that new replacement heat transfer liquid will ooet about $8 per gallon.* Disposal of contaminated fluid containing over 500 ppm FCBs in an approved FCB incinerator would cost frtn $1.20 per gallon (in tank truck lots) to $2.10 per gallon (in 55 gallon drues) (Rollins, 1978). Transportation would add about $.02 per pound or $.16 per gallon to this cost (Vtrsar, 1978). Since one-half of the systems have capacities of over 2000 galIons, 804 of the liquid may be in these large systmae which would generate truckload lots of fluid when drained. The average disposal cost would therefore be $1.54 per gallon, including transportation. Incineration coats for liquids contaminated with less than 500 ppn FCBs were quoted at about one-half the rate for the more contaunated liquids (Rollins, 1978). This would be equal to a cost of $.81 per gallon, including $.02 per pound transportation. If each systme were drained every lx months of 904 of the fluid and then refilled with new fluid that did not contain FCBs, any FCBa that were adsorbed on the vessel walls or absorbed into porous gasket material would have a chance to diffuse into the liquid between retrofills. Eadi draining would therefore remove 904 of the FCBs frcn the systme, progressively reducing the concentration from the present 20,000 ppe (2%) to 2,000 ppm, then to 200 ppn, and finally to 20
Letter from w. R. Corey (Monsanto) to EPA dated August 4, 1978.
100
MONS 013312
ppi altar the third ratrofill. If tha average system capacity is 1,300 gallonl, tha 450 to 600 contaminated systems presently contain (1300 x 450 to COO gallons ) 505,000 to 780,000 gallons. The cost to reduce the concentration of FCBs from the present 2t to below 50 ppn will be $15 aillion to $20 nillion as calculated in Table 11.3-1.
Since each systma must be analysed within three months after each retrofilling, a total of (450 to 600 x 3 - ) 1350 to 1800 additional analyses will be required at a coat of $100 each, for a total additional analytical coat of $135,000 to $180,000.
Marking: Uie marking of heat transfer systems containing liquids contaainatad at levels above 500 pps FCBs is required fay the Disposal and Narking Regulations (EPh, 1978a). Since no systems are aspectad to be contaminated at levels between 50 pps to 500 ppm, the change in the definition of FCB mixture from 500 ppm to 50 ppn in the Ban Regulation is not expected to change the number of heat transfer eystmus requiring the application of a special label.
The druas and trucks used to transport the contaminated liquid to the Incinerator for disposal will also require special labeling, since this la already required for liquids containing over 500 ppm KBs, the effect of the Ban Regulation will be to add this requirement to the di^oeal of the liquid from the third ratrofill. if four labels are required per machine C $2, total additional labeling costs will be (450 to (00 machines x 4 labels x $2 per label installed - ) $3600 to $4800.
Storage for Dispoaal: since the required disposal areas will have to bo installed at each location that uses contaminated heat transfer yet-- to --t the requiraemnts of the Disposal and Narking Regulations, no additional coot will result frem the KB Ban Regulations.
Dlwxaesl of Beet Transfer Svstmsst There la no information in the record that will support any estimate of the number of heat transfer yet-- that will be scrapped before they are decontaminated to KB levels below 50 ppe.
101 HONS 013313
L
Table 11.3-1
Coat of Retrofilling Heat Transfer Byteem to Meet Sfl pot Limit on Kb concentration
Number of contaminated systems x Average System Capacity - Total quantity of fluid x Hei>t per gallon x Concentration of PCS Bands of KBs in fluid
450-600 1,300 gallons; 585,000 to 780,000 gallons 8 lbs per gallon 24 KBs____________________ 93,600 to 124,800 lbs KBS
First Retrofill Tbtal quantity of liquid x Drainage efficiency - Gallons to be disposed of and replaced
KB Content 24 Cost of replacneent fluid 8$8.00/gal + Cost of disposal 8 $1.54/gal + Labor 8 16 hours/aystoa 8 $15/hour Total cost of first retrofill Second Retrofill KB content 8 2000 ppn Tbtal cost of second retrofill
585,000 to 780,000 gallons .9 526,500 to 702,000 gallon 84,200 to 112,300 lbs KBs
,212,000 to il.tl6.6K '
$810,800 to $1,081,000 $108,000 to $144,000 $5,130,000 to $6,840,000
8,420 lbs to 11,230 lbs KBs $5,130,000 to $6,840,000
102 HONS 013314
Tahla 11.3-1 (Oontinuad)
Third Batroflll
KB content ( 200 p(Bi
842 lb to 1,123 lba FCBa
Ooat of raplacanant and labor
$4,320,000 to $5,760,000
+ Cost of diapoaal I $.81/gal
$426,000 to $569,000
Total coat of third ratrofill
$4,746,000 to $6,329,000
Total coat to raacb 50 pps Total lba FCBa rawed
$15,000,000 to $20,000,000 93,500 lb to 124,700 lba KBa
103 HONS 013315
However, since disposal of machines containing fluid with mote than 500 ppm PCBs was required ty the Disposal and Harking Regulations, the Ban Regulations only affect the disposal of those machines contaminated at levels between 50 ppm and 500 ppm.
The previously established requirement that all heat transfer systmms contaminated at levels above 500 ppn be disposed of in approved chmaical waste landfills would have resulted in significant costs.
As a very rough estimate, the volume of each system using heat transfer fluid might be ter times the volume of the fluid which it contains, the total volume of material requiring disposed in approved landfills might than be (450 to $00 systems x 1300 gallons/system x 10 gallons system volume/liquid volume 7.43 gallons/cubic Coot ) 800,000 to 1,000,000 cubic feet at a cost of $3 per cubic foot (Versar 1977, pp. 2-13). Because of the uncertainty in this estimate, actual disposal cost might be considerably higher than this figure. All of these costs would have been incurred, inter the requirements of the Disposal and terking Regulations which defined PCB mixtures as those containing over 500 ppm PCBs. the effect of the required decontamination will be to decrease the eventual disposal costa by $2.4 million to $3 million.
11.4 PCBs Controlled by the Regulation
tbnsanto claimed that leakage from heat transfer systems was infrequent and would seldom exceed 54 of the capacity of the aystam in any single Incident. If retroftiling contaminated heat transfer ayefts were not required, as much as 104 of the PCBs presently in the systems would be apUlad or leaked because of pump seal leaks and accidents. Hie remaining anounts of PCBs would be incinerated as required by the Disposal and Marking Regulations. If spill cleanup were 804 effective, the effect of the regulation would be bo reduce the amount of PCBm entering the environment to 24 of the 93,600 to 124,800 pounds presently in the machines, or by 1872 to 249$ powte.
104 HONS 01331$
11.5 Sunmary - Eeoooadc Impacts
Tfcatingi
Initial
S45,000 to $60,000
Following retrofilHnq $135,000 to $180,000
Retrofill: Dlapoaal:
$15,000,000 to $20,000,000
Coat savings becauaa system are decontam inated
$2,400,000 to $3,000,000
Ibtal
$12,780,000 to $17,240,000
11.8 Coat per Pound of PCBa Kept frail the &ivironnent
Coat per pound
to $17,240(000
$6827 to $6907 pur pound PCBa
(average $6870/lb)
105 HONS 013317
12.0 COrtPRESSCWS
Prior to 1972, Monsanto marketed a PC3 based lubricant under the trade name Turbinol* 1S3 for use in turbine type compressors. This liquid was apparently used in a number of natural gas pipeline compressors fVkrsar 1978, p. 78). Although the liquid was flushed out and replaced with non-PCB fluid in the early 1970s, residual levels of PCBs have been found in at least a few of the machines.*
12.1 Requirements of the FCB San Regulation
Compressors containing a liquid contaminated with more than 50 ppm FCBs may be used until May 1, 1980, provided a ECS label is applied to each contaminated machine. These compressors may not be used after Jmuary 1, 1980, unless they have been decontaminated to a level below SO ppm PCBs.
12.2 Impacts of the PCB Ban Regulation
versar previously estimated that there were perhaps ten ccspressora that would be affected by the preposed PCB Ban tagulations and stated that Goltsfcia Gas and Texas Eastern had been contacted for additional information on the nunfcer of contaminated ccmptesaors and the coat and feasibility of decontamination (Versar 1978, p. 78).
In his letter to the EPA of August 4, 1978, Mr. Willard Young of Texas .Eastern Transmission Corporation stated that Texas Eastern would be able bo reduce the level of PCBs in their compressors to below 50 ppe by the end of 1978 "by another cycle of draining, flushing, and installing new lubricants.' He did not include any information on the cost of this procedure or the number of compressors requiring decontamination.
In his letter to the EPA of August 4, 1978, Mr. Ebbert Welch, . Jr., of Columbia Gaa System Service Corporation stated that forced shutdown of ccspresaors on January 1, 1979, could have a significant effect on the
Letter fro* Willard T. Young (Texas Eastern Transmission Corporation) to EPA dated August 4, 1978.
106 MOWS 013318
itllvtry of natural gas, "depending on the nuaber of vmits affected." Mr. Milch also stated that the economic impact analysis of the proposed regulations (Versar, 1978) was deficient because the cost of service disruption wets not estimated. However, Mr. Welch did not furnish any data on the lumber of contaminated compressors operated by the industry or by tollable Gas, nor die he include any information on the difficulty, cost, ad tiaw required to decontaminate such compressors. Therefore, it is till not possible to eetimste the total economic costs of the regulatory raquirmaants which ban the continued use of contaminated ccmpreseors. Since Items Eastern apparently will be able to meet these requirements, total direct coat of the decor)tanination program should not exceed the $200,000 previously estimated (Versar 1978, p. 79). The requirement that the decontamination program be completed by the end of 1979 gives the industry time to complete the program during the slack sumner season, so there should not be any costs caused by service disruptions.
12.3 PCTs Oontrolled by the Begulation There is no information in the record that will support any
tstiaata of the amount of PCBs presently in use in compressors. Therefore, no eetimste can be made of the mount that will be controlled by the reflation.
12.4 Sumary - Economic impacts Decontamination costs -- $200,000
MONS 013319 107
13.0 REOAIMED OIL* , 13.1 Present Status of PCBs In Reclaimed Oil Approximately 1.3 billion gallons per year of used oil is
oollected for use as road oil. fuel oil. re-refined hydraulic oil, and re-refined lubricating oil. Much of the waste oil previously used in applications other than automotive lubrication has been contaminated with low levels of PCBs, and dissipative uses of this contaminated oil can introduce PCBs directly into the environment.
A total of 2,376 million gallons of new oil were sold during 1976, the major commercial uses being automotive lubrication (50.8 percent); industrial and aviation lubrication (30.5 percent); and other Industrial uses primarily in materials processing (17.4 percent). The mount available for collection and recycle was estimated to be 1,154 million gallons, or 48.6 percent of total sales. Data on U.S. use of new (virgin) refined oil and availability of used oil for recycling are preeentad for the year 1975 in Table 13.1-1.
Data generated by Bacon Systems*** for a 12-sonth period during 1970-71 indicate that, out of a total U.S. production of 2,480 Billion gallons per year, approximately 901 million gallons, or about 36.3 percent, ware actually collected for recycling or use as fuel. An additional 601 million gallons were estimated to be used on roads (application for dust
*Thia chapter is adapted from Chapter 13 of Versar, 1978. The EPA promulgated the rules affecting the use of reclaimed oil with eseentially no changes frcm the proposed regulations. **wtinetein, Norman J., (Bacon Systems, Inc.), Haste Oil Recycling and Disposal, EPA-670/2-74-052, Princeton, N.J.: August, i/i(as cited in Versar, 1978).
108 MOMS 013320
Table 13.1-1 Nm Oil Usage and Waste Oil Availability for Recycling In 1975*
Mantlva Lube Oil
industrial Aviation Lute Oils
Otter Industrial oils Lute Oils Purchased
fay o. s. own--tit
Outlet or Use
0. S. Sales Fraction
USad Oil
1975 i~ Available** Available
(gal x 10"6) for Recycle for Recycling
Service Stations Ccmnercial Bogina
Fleets New Car Dealers Auto Fleet and Other
Lube Oil Uses Detail Sales for
Oosnercial Engines Garages, Auto Simply
Stores Discount Stores
Factory Fills (Auto & Faun Bquifsent) Subtotals
239
225 103
151
95
90 250
54 1,207
.63
.50 .90
.50
.63
.63 .22
.90
150
112 93
75
60
57 55
49 J5T
Hydraulic t Circu lating Systan Oils
Metal Nocking Oils Aviation t Other Gas Bigine Oils Railroad Bigine Oils
Subtotals
314
145 147
60 58 73T
.42 .70 .50 .90 .53
132
101 73 54
31 m
Electrical Oils
Prooaaa Oils Refrigeration oils
Subtotals
62
340 11
"415
.90 .10 .50
56 34 6 ~5?
1 GDMO TOTALS
32 2,376
.50 16 1,154
teinetsin, 1974 (as cited in V^raar 1978, o. 81). fraction avallibla fee recycling after losses in use and to enviromant.
109 HONS 013321
control and possibly in asphalt) or as fuel oil; this used oil could conceivably have been collected for recycle so that the naxisui anount of oil available for collection, based on the Bacon System' estimates for 1970-71, nay be aa much as 60 percent of that produced.
A flow chart showing the distribution and utilization of waste oil in the United States, based on the 1970-71 data of Bacon System, la presented on Figure 13.1-1. Smeary data for disposition and uaage fron Figure 13.1-1 are as follows:*
Fate of Oil After Priaary Use
Percentage of New Oil Production
Used as fuel
41.5
Dissipated to environment and wmte disposal
42.3
Applied to roads
12.9
Re-refinad lube oil products
3.3
100.0
The general distribution shown in Figure 13.1-1 is believed to be valid at peasant, although the Magnitudes of the specific flow* have fluctuated as prices of virgin lube oil and fuel oil have varied. The value of fuel oil has increased since 1970-71, and virgin lube oil was scarce during the period of the Arab boycott and during a portion of the period of price controls. One result of these factors has been increased use of wests oil as fuel, either by the industrial concern generating the waste oil or by processors.
The priaary sources of wests oil available to collectors ere service stations and other autoaotive-related facilities. Industrial and
Varsar 1978, p. 83.
uo HONS 013322
w1
mnmmnrnmimo *Cifea<3 In Uarur 1978, p. 82.
HONS 013323
aviation facilities are also significant sources. A significantly lamer fraction of available oil is collected in urban areas than in suburb*! or rural areas. According to studies in the Pittsburgh area, spills and other wastes from product pipelines are a locally significant source of waste oil for collection.
The use pattern of processed or re-refined waste oil is extremely diffuse. Users include states and municipalities (road application), industrial and cornercial facilities (fuel, re-refined ltfee oils, road oil), utilities (fuel), and the consuming public (re-refined motor oil).
A small portion of the collection and processing of used hydraulic oils does not follow the general pattern of scattered sources, many reclaimers, and nunerous users indicated for the waste lube oils, declaration of used hydraulic oil, performed primarily by four ccmpenies, results In a product which is marketed as hydraulic oil.
13.2 Requirements of the Proposed Regulations Die disposal of oil contaminated with PCBa in excess of 500 pps
was regulated by the FCB Narking and Disposal Regulations (EPA 1978a). Vte PCB Ban Regulations change the definition of PCB used in the Harking and Disposal Regulations to include all mixtures containing more than 50 ppa PCBa. Uhder the provisions of the ban regulations, oil contaminated with PCBa in excess of 50 ppm must be identified, segregated for purposes of disposal, and disposed of in accordance with one of the approved methods. Oil containing measurable amounts of PCBs less than 50 ppa may be {vocaaeed for any use including fuel or reclaimed lubricating or hydraulic oil, but it may not be used as road oil or as a constituent of any sealant, coating, or dust control agent.
112 MONS 013324
13.3 Sources and Amounts of Contaminated Waste Oil
Hydraulic Fluids; Oil is used as a low viscosity fluid in hydraulic aystans, and PCB baaed hydraulic fluids were widely used prior to 1972. The most expensive (and polluting) use was in aie-casting nachinery. PCB based hydraulic fluids ***re also used in construction machinery, farm nadiinery (a source of feed contamination),* and in deep mining equipment tdiere the use of PCBs resulted in greater fire safety.
Although hydraulic systems are nominally air-tight, leaks may occur at dynamic seals, and major spills may occur due to hose rupture. Normal leakage is collected in drip pans. Ihe rupture of a hose can spray hydraulic fluid aver a large area due to high operating pressures. It has been estimated that 80% of phosphate ester hydraulic fluid losses occur from leaks in the hydraulic system.** In certain industries, operators state that it is more efficient to continually add hydraulic fluids to the system rather than shut the system down, repair any leaks, and refill the system. Leakage from these systems is often collected and reclaimed.
Monsanto manufactured almost all the PCB-based hydraulic fluids. When Monsanto discontinued manufacturing PCB-based hydraulic fluids In 1971, they did not recommend draining or flushing of hydraulic systems. They did recommend that replacement fluids be added to the rsmaining PCB fluids in the systen. As a result, hydraulic systems which used PCBs in 1972 and prior years now contain replacement fluids contaminated with 0.006 to 50% PCBs as discussed in Chapter 10. The total mount of contamination is s function of the syston leakage and dilution during the past five years.
H).S. Department of Agriculture Ml Hoc Group on PCBs. Agriculture's Responsibility Concerning tolychlorinsted Biphenyls (PCBs) Washington, D.C. Office of Science and Education, U.S. Department of Agricultrue, 1972 (as cited in Verier 1976, p. 84). **Lapp, T.W. (Midwest Resarch Institute), The Manufacture and Use of Selected Aryl and Alkyl Aryl Phosphate Esters, EPA 560/6-76-008, Feb. 1976, p. 77 (as cited in Versar 1978, p. 84).
113 HONS 013325
A portion of the available used industrial hydraulic oil is refined ana sold for reuse as hydraulic oil. 'this specialized reclaiming service is furnished by the following four companies which reclaim a total of about ISO,000 gallons of hydraulic fluid per year (Versar 1978, p. 85).
E. F. Houghton and Co., Philadelphia, Pennsylvania Radoo Corporation, Lafox, Illinois Findett, Inc., St. Charles, Missouri Wallover Corp., East Liverpool, Ohio Automobile and Industrial Lubricating Oil; The amount of used oil collected for reuse In 1970-71 was about 900 million gallons psr year, with an additional 600 million gallons used internally for fuel or dust control on roads (Weinstein, 1974). Thus, about 60 percent of the amount of new oil sold was reused. Major uses of this oil were as fuel (1028 million gallons), road oil (319 million gallons), and feedstock for re-refined lubricating oil (138 million gallons) (Versar 1978, p. 85). The extent of PCB contamination of this oil was studied on a limited basis by the EPA National foforcement Investigation Center (NBIC) in Denver.* Samples of oil were taken from selected tank truck lots of ussd oil that had been collected in Virginia, Maryland, and North Carolina. This oil had been delivered to Continental forest Industries In Hopewell, Virginia, for use as supplemental fuel in a steam boiler of a paper mill. The oil had been collected primarily from automobile service stations, although It is possible that some industrial oil, Including hydraulic oil, had been included in some of the lots. FCBs ware found in the samples of
Testimony of Robert Magruder, (Continental forest Industries) presented at the U.S. EPA informal hearings on the PCB ban regulations at Washington, D.C., July 15, 1977.
114 HONS 013326
oil at concentrations ranging from 3.2 ppm to 19.4 ppm. Although these oil (Mples were collected from a restricted area, the extent of PC3 contamination is probably representative of waste oil collected throughout the United States.
The FCB contamination of the waste oil could came from contaminated industrial hydraulic oil or transformer oil or from FCB additives used in lubricating oils prior to 1973. In applications such as railroad car journal box oils, PCBs may have been used as lubricant additives.* FCBs may also have been added to automobile transmission fluids to control the swelling of oil seals.
It would not be expected that PCBs would be destroyed during re-refining of waste oils. FCBs were reported to be present in concentrations of several parts per million in reclaimed oil used to lubricate whetstones.**
13.4 Coedlance Costs
Collection of any waste oil likely to be contaminated with FCBs for a controlled use would not be attractive financially mless the oil were known to contain FCBs at levels below the control amouit. Analytical costs for determining low levels of FCBs will be considerably higher than the costs quoted for transformer oil because naturally occurring sulfur and chlorine compounds in petroleum oils cause interferences in the use of electron capture gas chromatography at concentrations of 5 ppn FCBs or below.*** These interferences result in false positive indications of the
"Monsanto Chemical Company, Aroclors for --, St. Louis, Mo.: undated (as cited in Versar 1978). **Maems, George, (United States Department of Interior, Denver, Colorado), "Polychlorinated Biphenyls,* File HLS 3-3-1Oh, June 13, 1977 (as cited in Versar 1978). "Hofstadar, R. A. (Exxon Research and Engineering Co.); Lisk, D. J., Bachs, C. A. (Oomell University), 'Interference in the Electron-Capture Technique for Determination of tolychlorinated Biphenyls by Sulfur-Containing Compounds in Petroleun Products", Bulletin of Ehyironaantal Contamination end toxicology, \tol. 11, No. 2, 1974 (as citad in Versar 19/8).
115 M0N5 013327
presence of CBs. The PCS components can only be resolved through couples clean-up procedures or the use of gas chromatography/mass spectrometry, techniques that would cost up to several himdred dollars per sample.
Hoad Oiling: The most recent data indicates that road oiling consunes 319 million gallons of waste oil per year (Figure 13.1-1). At an application rate of 1/2 gallon per square yard, this is sufficient to oil 45,000 miles of roadway 24 feet wide (Versar, 1978, p. 87). The proposed ban regulations would forbid the use of oil containing detectable anowits of PCBs for dust control. Fluids frcm transformers are likely to have detectable mounts and other Industrial sources are at least somewhat suspect. Currently these Industrial oils are collected along with utsd motor oil. Although virgin motor oil has no PCBs, used motor oil may hams PCBs frcm previous recycling which included industrial oil sources among the feedstocks or fron old transmission oils which contained PCBs as an additive. Nevertheless, used motor oil unmixed with industrial sources is wlikely to contain as much as 10 ppm PCBs and may have FCB concentrations that are undetectable without tnusually elaborate and expensive analysis. None of the reported analyses of waste oil for PCBs was baaad on used motor oil without any possibility of industrial contamination. Presusably waste oil solely frcm automotive sources would contain fewer PCBs. It is doubtful that road oiling could stand the costs of even "simple* tests at $70 per sample. Prospective road oilers therefore would be safer using waste oil if they take precautions to ensure that it does not contain industrial oils (and certainly no electrical oils).
Ccmpliance with the requirements of the proposed regulations could be achieved by either of the following strategies:
(1) Avoid all waste oil, and substitute virgin oil at considerable monetary and energy coat where the customer is willing to pay the increased price. At an average price of $.375 per gallon for 12 fuel
116 HONS 0133*
oil vs $.08 per gallon collection coats for used crank case oil, the cost of road oiling would increase (.375 - .08) x 139 million gallons $94 aillion per year (Versar 1978, p. 87).
(2) Use synthetic road stabilisation chemicals which both reduce dust and provide surface stabilisation. The increased cost of this type of material is presently offset by lower road maintenance costs on heavily traveled dirt roads at mines and other industrial facilities. Swings in maintenance on lightly traveled roads would be less significant and would only partially offset the increased material costs. A typical synthetic material is Coheres*, manufactured by Vfitco Chemical Corporation. This material is an organic resin in a water emulsion which is sold in large quantities for $.40/gallon plus transportation, and is applied after a 5 to 1 water dilution at a rate of one gallon per square yard.* Increased costs incurred by the use of this material are summarized in Table 13.4-1.
The use of synthetic road oiling materials such as Coheres* aey be more or lees expensive than the use of ueed motor oil depending on the local supply and price of the used oil. The present choice between the use of used oil and synthetic materials apparently depends on local supply and coat conditions. The total cost resulting from an effective ban on the use of waste oil would certainly be no greater than $31.7 million per year, as calculated In Table 13.4-1, and might even result in an overall coat savings as claimed by Mitco Chemical.
^Letter froe victor Shepard (Witco Chemical Corp.) to EPA dated September 23, 1978.
6*
117 HONS 013329
Ooat of Subatltutlrw COHEBBt* for Uead Motor oil In Baad oiling for Dut Control
Coheres*i Bulk Purchaa* Price
Trn*portation #.02/lb. (Veraar 1977)
TOWL
$. 40/gal. 17/gal.
?.37/gal.
Matarlal Coat for Coherex*: 1/6 gal./yd2 Hlnuai Oaed Oil: 1/2 gal./yd.2 6.08 to .30/gal.* Bquala: Incraaaed Coat (Saving*) per aq. yd. % 14080 yd2 par ail# of toad, 24 ft. wide * 45,000 nilea
.09
.04 to .15
$.05 (.06)
$704 (84S)
$31,680,000/ymc ($38,025,000/year)
face rang* reported by Victor Shepard (Nitco Chanical Corp.) for euppUes of uaad oil. tetter to EFft dated Septatoer 23, 1978.
118 HONS 01333
llserz Other than Wood Olleri: About 27 million gallons per year of transformer oil will not be available to collectors. However, oil diverted from road oiling nay more than offset this loss of supply, other industrial oils nay or nay not be contaminated with PCBz; to be absolutely safe, the recycling industry would avoid them. Individual industrial fins can probably continue to use their own waste oil as fuel oil if they make initial and occasional later spot check laboratory analyses to make sure their oils continue to contain less than SO ppa FCBs.
The impact on re-refiners (who make re-refined lube oil) and external processors (who process waste oil Cor use as fuel oil) will depend on what happens to road oiling. A strict enforceaent policy with occasional all-out efforts bo find PCBa in waste oil could prevent its use as road oil. Diversion of waste oil from this use would create a large increase in supply for processors and re-refiners. Probably nost of this would originally go to fuel oil use since the capacity of re-refiners is United and the consular acceptance of used motor oil is limited. Later, a majority of the increase night go to re-refiners if the Frost and Sullivan market projections of 23 percent growth per year until 1985 proves to be even roughly accurate.* This would provide an extra use as lube oil while retaining nost of the heat value for later use.
Collectors! If collectors avoid transformer and industrial oils, their total business will decrease. However, hauling contaminated oils to diasical waste incinerators or high efficiency boilers will be required and could offer new narhet opportunities to the collectors.
Processors i Haste oil for fuel uee should beocoie more plentiful as use for road oiling is discouraged or made impossible by the regulation. Ihe effect of a larger supply of waste oil on the price to processors theoretically would be to lower the price, waste oil can be
a, f. M., "lte-refined Oil: An Option That Saves Oil, Minimizes Pollution," Science, p. 1106-1110, September 17, 1976 (as cited in versar 1976, p. 89)1
119
moms
used as a supplemental fuel with coal. This use recovers the fuel value of the oil and would destroy any PCBs that might be present in the oil. Since FCB contaminated oils may be incinerated in large boilers, and since the use of waste oil with coal In boilers is relatively trcafelefree. this uee is probably very elastic. If coal burning plants can absorb the increased supply, which seems likely, the price decrease should be negligible.
Hydraulic Oil Re-refiners; Information collectad through telephone interviews indicates that at least three of the coapsnies which re-refine hydraulic fluid receive hydraulic fluids which are contaminated with PCSs. these fluids are sometimes contaminated to the extant of <000 PP (Chapter 10). In most cases, the reclaiming process removes no more than 10 of these PCBa.* It Is also reported that the concentration of ICBs in some of the hydraulic fluid applications encountered by theae companies remains at approximately 2000 ppm despite repeated flushings and drainings, the present status of FCB reduction technology is discussed in Chapter 10.
Industrial Waste Oil Generators: Those Industries whose waste oil contains more than SO ppm PCBs will have to incur disposal costs of up to $.75 per gallon (see Chapter 6). Even industrial oil cantaninated with less than SO ppm KBs may be avoided by waste oil collectors. Thia may not be a major preblea for companies that have large high efficiency boilers. Oil burning boilers can uee a mixture of waste and virgin oil. Hr. Hagruder of Continental Forest Industries indicated that up to 14 percent waste oil mixed with 16 residual oil is feasible.** The result may be the development of a separate market for industrial oil with low levels of FCBe for use as fuel, tong term economic impacts should not ha significant.
13.5 PCBs Controlled by the Regulation
The provision of the regulation that prohibits the use of oil containing any measurable amounts of KBs as a coating or dust oontrol
*Wephona conversion, Owein Fowkes (RADCO Corp.) with L. Fourt (Versar), Saptaxber 19, 1977 (as cited in Verier 1978, p. 90). Testimony on Robert Hagruder (Continental Forest Industries). Prveentad at the U.S.E.P.A. Informal hearings on the FCB Ban Regulations at Washington, D. C., July 15, 1977.
120
HQHS 013332
gent will affect only those waste oils that contain less than 50 ppn ?CBe, since the disposal of the more highly contaminated oils is controlled by other provisions of the regulation. The only available data indicate that waste oils are presently contaminated with FCBs to levels of 3.2 to 19.4 ppn (section 13.3). No information is available as to the sources of the oils for which this data was obtained, and diversion of transformer oil and contaminated industrial oils to high efficiency boilers might significantly reduce the concentration of FCBs in the remaining waste oil. However, if it is assuned that all of the oil affected by this provision of the regulation is contaminated at levels of 11 ppm (average of 3 ppm and 19 ppm), then the PCB content of the used oil that is available for recycling will be (11 ppm x 8 poinds per gallon x (651 million gallons automotive oil + 54 million gallons gas engine oils + 31 million gallons railroad engine oils + 16 million gallons U. S. government lube oils*) ) 66,176 pounds.
Approximately 12.9% of new lubricating and industrial oil production has been applied to roads, 41.5% used as fuel, and 3.3% re-refined as lube oil. Diversion of the 12.9% that has been used on roads will control (.129 x 66,176 pounds FCBs - ) 8537 poinds of FCBs. If this oil is used as fuel and re-refined as lube oil products in the same ratio as above, <41.5/(41.5-w3.3) ) 93% will be used as fuel and 7% will be re-refined. About one half of the re-refined oil will be lost to the environment and the other half will be used as fuel, so the effect of the regulation will be to divert about 96.5% of the 8537 pounds per year of FCBs used on roads to fuel use. Since many of the boilers using this oil ay not meet the criteria established for high efficiency boilers, perhaps 2% of the FCBs in the waste oil will not be destroyed, therefore, the total mount of FCBs that will be destroyed in the boilers rather than applied to roads will be (8537 pounds PCB per year x .965 diverted to fuel use x .98 destruction efficiency ) 8073 pounds PCBs per year, the actual anowt diverted to the environment may be lomr if the controls on the disposal of transformer oils and oontaminated industrial oils decreases the mount of FCBs in the remaining waste oil.
'Sable 13.1-1.
121
HONS 013333
13.6 Suaaary - Sconcnlc ngacta
Oanpllance Costa
Ibad Oil - increased coats of virgin or synthetic material (first several yaars)
toad Oil - Increased coat of obtaining adequate supplies of aagragatad used aotor oil after level of KBs In used aotor oil dropa below detectable limits.
$0 to 31.7 mlllloiv'yaar $0 to $6.4 ailUcrv'year
13.7 Cost Per Pound of KBs Kept ftf the envlionaant Coat per pound *
0 to $3' ~
year.
0 to $3925 per poind FCBs
122 HONS 013336
14.0 PC8S AS UNXOTEWTIOfAL PRODUCT COMTAMIMWTS
14.1 Current Production
There are a number of commercial chemical processes which produce FCBs as an unintentional byproduct in concentrations over SO ppn. These include the production of two classes of pigments, a new aluminas meeltlng process, and several other proprietary chemical processes.
Phthalocyanine plnsentsi fhthalocyanine blue and green pigments are produced in two steps.* The first step is the production of crude pigment using, in most cases, trichlorobenzene as a solvent.* In this instance, a side reaction involving the trichlorobenzene is the source of the KBs. The crude is then further processed to produce a number of different blue and green pigments. In 1976, production and imports of phthalocyanine blue and green pigments were 13,200,000 lbs* with a value of roughly $87.6 million. Testing indicates that the majority of this type of plpmnt is contaminated with over SO ppm KBs, though there ia considerable doubt concerning the validity of the test method which was used.**
Currently, the only major dcmestic crude manufacturer which does not uae trichlorobenzene as a solvent is DuPont.*** They reportedly use kerosene and have developed pigments based on the properties of the crude they produce. In addition, Fhthalchem uses a mixed solvent system which has trichlorobenzene as one of the components. Testing indicates that this crude may be contaminated below SO ppm; again, however, the analytical method has not been validated.
*"Main comments of Dry Color Manufacturers Association ...." dated August 7, 1978, p. 16.
**Testiaony of the Dry Color Manufacturers Association at the PCB Manufacturing, Processing, Distribution in Causerce, and Use Bans Bearings, Washington, D.C. August 30, 1978.
***Oral testimony of Arthur Hspmeier, (Rithalchem Inc.), at the PCB Manufacturing, Processing, Distribution in Comnerce, and use Bans Hearings, Washington, D.C., August 30, 1978.
123 HONS 013335
Import! of bloc crude, primarily from Japan, supplied over 56% of the U.S. market in 1976.* In addition, low-PCB crudes are currently available in commercial quantities from at least one Japanese supplier. This is a recent development, and any increase in donand for this product could not be met for roughly a year.** Also, Mr. MacDonald 9mith of Sim Chemical testified that this low PCB crude was of inferior quality.***
Diarylide piqnenta; Diarylide yellow, orange, and rad pigamnts are made by reaction of precursors which include dichlocobenzidine as an essential component. A minor side reaction results in the decomposition of the dlchlorobenzidine to produce 3,3'- dtchloroblphenyl.****
Sales of diarylide pigments in 1976 were about 9,760,000 pounds with a value of $41 million.**** There are currently no substitutes for the diarylide pigments, which are used in printing ink, textile Ink, plastics, and paints. In 1969, diarylide yellow (the diarylide with by far the highest production) accounted for 84% of all yellow pigments produced in the Uhited Statee.****
Aluainua mselting: Alcoa has developed a new smelting process which inadvertently produces over 50 ppm of decachlorobiphenyl.***** The FCBs are produced in a preliminary step involving the production of aluoinum chloride through the reaction of alumina with chlorine in the presence of coke. The PCBs and other contaminants are rueived in the second step, which is the electrolysis of the aluninum chloride to produce metallic aluninum.
'oral tsetirony of Arthur Hopmsier, (Phthalchem Inc.) at the PCB Manufacturing, Processing, Distribution in Ccsmerce and Use Bans Bearings, Washington, D.C., August 30, 1978 Letter to CPA from W. C. Parle, (Harmon Colors) July 11, 1978. ***0ral ccmamnts of Hugh MacDonald Smith (Sun Chadcal Corporation) at the PCB Manufacturing, Processing, Distribution in Ccsmerce and Use Bans Hearings, Washington, D.C., August 30, 1978, p.107. ***"Main Cements of Dry Color Manufacturers Association ..." dated August 7, 1978, Table 3. `"`Information on this almdnun smelting process and the resulting PCBs wes taken from the letter frcm James S. Boyt (Alcoa) to BPA dated October 10, 1978.
124
MOhS 013336
This process has several advantages over conventional aluminum siting. These benefits Include elimination of fluoride emissions, reduced energy consumption, and improved product purity. The energy wrings possible with this process are considerable. Conventional suiting requires 8 KNH per poind of aluminum produced. This new process requires 4.5 KNH per pouid, a savings of nearly 44%. Using these figures, a 300,000 ton per year melter could save up to 1.95 million KWH per year.*
In addition, the production of the aluminum chloride in the above process has a nuaber of energy and process advantages compared to conventional aluminum chloride production methods.
Other chemical processes! Killlips Petroleum and Dow Coming, both have chemical proceases that produce over SO ppm FCBs. The Phillip# pcoceee la still experimental and apparently involves the use of PCBs as a rhemlrsl Intermediate.** Dow Goming states that during the production of a chesilcal intermediate, PCBs, apparently largely monochlorinated biphenyl, mre produced at levels between 50 and 500 ppm.*** Tennessee Eastman also had a chwmical process that produced over 50 ppm PCBs.**** However, Tmnaasam Eastman subsequently advised EPA that it had modified its process and "because of these modifications, the only time a concentration of PCB in excess of 50 ppm occurs is after processing to concentrate and dispose of the PCBs, as specifically contemplated at 43FK24805........ "****
Polychlorinated terphenyls (PCTs) formerly produced by Monsanto art known to have bean contaminated with over 50 ppm of PCBs. The only uses of PCTs discussed at the hearings were a number of applications in microscopy. This use has been authorised. Similar applications involve the use of certain Aroclors. These uses have also been authorized.* *****
"Latter to EPA from James S. Boyt (ALCOA) dated October 10, 1978. "Letter to EPA from Phillip* Petroleum Co. dated August 4, 1978. ""Letter to EPA from Jade Pulley (Dow Coming Corporation) dated October
10, 1978. ""Letter from J. C. Edwards (Tennessee Eastman Company) to EPA dated
August 7, 1978. *****Latter from Elliott Stem (Tennessee Eastman Company) to EPA dated
December 21, 1978. (Letter in record of TSCA Exemption Docket No. 1)
US HONS 013337
14.2 Rewireamnta of the PCB Ban Regulations
It is assumed here that none of the operation* described above qualify as being "in a totally enclosed manner." Therefore, the manufacture, processing, distribution in ccmerce, and use of any dt--leal containing over SO ppm PCB* (including phthalocyanin and diarylide pijaanta and the product* of the Alcoa smelting process) are banned 30 days after the date of promulgation of the PCB Ban Regulation except in those cases specifically exenptad by EPA.
14.3 Economic Impact
Pigment Manufacturers: The impact the ban regulations will have on those manufacturers who produce products contaminated with low levels of FCBs will depend on the actions taken by the EPA in response to petitions for assertion free the regulation. For the purposes of this analysis, an upper bound economic inpact will be estimated assisting that no exemptluis are granted before enforemnent of the regulations begins. A lower bound economic impact will be estimated assisting that all exemptions are granted by the EPA. This second aasuRption also presusea that, where necessary, exemptions for processing and distribution in cannerce will be granted. The Interim Procedural Rules for Polychlorinated Biphenyls (PCB* a) Ban Bcenption (EPA, 1978d)*, state that only petitions front those affected fey the manufacturing ban will be considered. Therefore, separate petitions will be required for processing, distribution in cammsrce, and use exenptions.
*BfA. ISTSd. "Part 750 - Procedures for Rulemaking under Section < of the
Tbxic Substances Control Act: Interim Procedural Atlas for
tolychlorinated Biphenyls (FCB's) Ban Bxenption." Federal Register,
tbveefcer 1, 1978, pp. 50905-50907.
---------------- ---------
126 HONS 013338
Hie processes in use by tow Coming, Alcoa, and Phillips Patrolsun oust csaaa 30 days aftar the rule la promulgated inless EPA has granted or is considering a petition for exemptions (EPA 1978d). The aaall aacxnt of economic data available are insufficient to support an estimate of the impact this will have.
Upper Boind Estimate; There are three companies that manu facture crude phthalocyanine blue using trichlorobenzene as a solvent; they are American Cyananid, Chemtron, and Ththalchem.* Phthalchem uses a mixed eolvent systea which has trichlorobensene as one of the components; the others use pure trichlorobensene. Dupont uses kerosene; Hercules Powder end Thamaaett use a dry process. The crude produced by each of these cospmies may contain over 50 ppm PCBa although Ehthalchem pigment has consistently shown less than SO ppm PCBa.** In the absence of a valid analytical method for determining PCB levels in this material, however, this study will assuss that all three companies must modify their processes to conply with the regulations. Kerosene appears to be the most feasible solvent to replace trichlorobensene. Hr. Arthur Hoemeier of ehthalchem testified that it would require 12 months and cost roughly $250,000 for him to modify his plant.** Mr. Paul Maichick testified that the two Chemtron plants could be converted to the use of kerosene solvent for a total cost of $1,500,000 but that considering the age and condition of Chentron's
`Letter from Arthur Hop--ier (Rithalchan Inc.) to EPA - August 4, 1978. **Testiaony of Arthur Hopmeier (Phthalch-- Inc.) at the PCB Manufacturing,
Processing, Distribution in Co--mice, and Use Bans Hearings, Washington, D.C., August 30, 1978.
127 MOMS 013339
squipMnt, it would be economically aounoer for them to spend $5,000,000 construct a new plant.* They would also attempt to purchase low-PCB crud eras Japan in order to meet their needs during the 24-30 months necessary to construct this plant.* Purchase of the required 3 million poinds of crude per year would cost roughly $4.5 million. No data were given by American Cyananid. Based on (1) a Chemtron estimate of $750,000 to oonvei each of their aged plants and (2) Nr. Hopmsier's estimate-that Phthalches plant would require less to convert than other plants,** the cost for American cyanamid is estimated at $500,000. The total cost for plant conversion is:
$250,000 + SI,500,000 + $500,000 $2,250,000
. In addition, Harmon Colors produces either a special crude or further processes purchased crude in trichlorobenzene to produce a phythalocyanine pigment which contains 575 ppm of tCBs. This pigment is used by the automotive iregistry and its manufacture has been authorized bj the State of Michigan. It would cost Harmon Colors roughly $2 million to construct a new plant capable of producing this pigment in an alternative solvent.***
Pour companies presented information which indicates that they may be producing diarylide pi^sent with PCB levels in excess of 50 ppm. They ere: (1) Chostron, (2) Pope, (3) Ridgeway Color and Chenical, and (4) Sun Chemical. It appears that the diarylide pigments could be produced with lees than 50 ppm PCBe if some process modifications were made. Therare some estimates on the cost of adjusting the manufacturing process to reduce the concentration of FCBs. nr. Paul Maichick of Chemtron estimated that it would cost $50,000 to modify their manufacturing and, because the process modifications will put them out of compliance with their NPCeS
"testimony of Paul Maichick (Chsmtron) at the PCB Manufacturing, Processing, Distribution in Ocsmsrcs, and Use Bans Hearings, Washington, D.C., August 30, 1978.
*"Testimony of Arthur Hopmeier (Rithalchsm Inc.) at the PCB ftanufacturino. Processing, Distribution in Oommerce, and Use Bans Hearings, NSahington, D.C., August 30, 1978.
**`letter to EPA from W. C. Parle (Harmon Colors) dated July 11, 1978.
128
MOMS 013340
permit, an additional $250,000 will be required.* Two other companies estimate their cost for complying with a 50 ppm limit as follows:**
Company
Initial Capital Oast Increased Annual Operating Expense
1 $750,000
$250,000
2 $200,000
$375,000-500,000
Three of the four coapanies listed would have an average conversion cost of $333,000. If this average is used as the cost for the fourth company, the total conversion cost could be $1.33 million. Increased operating costs may amount to $345,000 per company.** Although acme types of diarylide pigments already contain less than 50 ppm FCBs, one to two years will be required to reduce the level of FCBe to below 50 ppm in all of these pi^mnts.**
The manufacturing cost estimates for both types of pigments include only those costa directly attributable to plant conversion and to increases in operating costs. If the manufacturers are forced to cease production of all pignmnts that contain, over 50 ppm FCBs, there will be additional costs associated with lost production and future loss of customers who convert to substitutes or foreign suppliers. There may also be costs associated with the disposal of contaminated pigments presently in inventory. There is not enough data in the official record to support i estimate of these costs, but the data which are present deserve attention and seem to indicate that these additional costs could substantially exceed the conversion costs.
"testimony of Paul Malchick (Chmstron) at the FCB Manufacturing, Processing, Distribution in Coammrce, and Use Bans Hearings, Washington, D.C., August 30, 1978, p. 126. **letter to EPA frem Donald Morgan, (Dry Color Manufacturers Association)
datsd August 7, 1978.
129 HONS 013341
In 1976, production and imports of phthalocyanine blue totaled 13,200,000 pounds* with a value, after processing into pigments, of routly $87.6 million. Imports of blue crude (not pigment), primarily frcm Japm (85%), supplied over 56% of the U.S. market in 1976.** The majority of the imports are high-FCB crude. Low-PCB crude is being produced in Japm, but an increase in demand could not be met for a year.***
Sales of diarylide pigments in 1976 were 9,760,000 pounds with a value of $41 million. In addition, roughly 275,000 pounds were imported.****
Sales for phthalocyanine and diarylide pigments in 1976 totaled $131 million. Total sales of all organic piqments in 1976 were $261 million, compared with $200 million for inorganic pigments.**** Thus, the two classes of pigments in question account for over 25% of the domestic market.
The percentage of the industry that would be forced to cease production in response to a manufacturing ban is not known, but it is estimated to bo closer bo 50% than to 10%.***** This implies that up to one quarter of the domestic organic pigment producing industry would have to close down. In addition, a ocmpany that can no longer produce yellow and/or blue pigaents may lose other portions of its sales because "customers demand a full line of colors."**** The minimum conversion time given at the hearings was 12 months, so In the event an exception is not granted, dcewstic manufacturers would be affected for at least 6 months and would not be back to full capacity for 18 months. The potential for sub stitution of different pigments types and the ease with which production of low- or noo-PCB pigment could be expanded are not known, but it does appear
`Letter to EPA from Arthur Hopmeier (fhthalchem) August 4, 1978. *"Testimony of Arthur Hopmeier at the PCS Manufacturing, Processing,
Distribution, and Use Bans Hearings, August 30, 1978. Letter to BPA from W. C. Parle (Hannon Colors) July 11, 1978. ****"Main Consents of Dry Color Manufacturers..." dated August 7, 1978. Testimony of Donald Morgan (DCMA) at the PCS Manufacturing,
Processing, Distribution In Commerce, and Use Bans Hearings, August 30, 1978.
130
MONS 013342
that iaporta could not iaamdiately fill any tonrtagss. However, tha railable information Indicates that axtanalva inX, dye, and paint ufocmulatlon will ba required, equipment nay require modification or nplacaiant. and printing quality will suffer.
Thera oould be additional coats once domestic manufacturers tagln producing low- or non-PCB pigmante. In those cases where process dlficmtion rather than solvent substitution is used, it may be necessary to task each batch of pigment for FCBs as it is produced. Chentron states that they have made process modifications that reduce the PCB concentration to Urn apparent levels but that there may be occasional batches with higher concentrations due to mechanical failure or operator error.* In addition to tbs testing, production of s batch with over SO ppm would be illegal ^redaction which could be subject to a possible fins. The lowering of the paadasible limit from 500 tp 50 ppm PCBs would result in the disposal of additional batches of pigment.
tower bound estimate1 The lower bom) estimate essuwes that the feUowlng eight "pigment* companies will individually apply for (and will taealvs) exceptional
Mmrican Cyananid Apollo Colors Cheatton Harmon Colors Phthslehma Kps ttdgewsy Color and Chemical dun Owm!cal
'fear Seem Paul Halchicfc (Owmtron) to EPA dated August 3, 1978.
131
MONS 013343
It is also aaauMd that each company will apply for two exemptions: one for manufacturing and one for processing and distribution in commerce.
Preparation of the required petition and attendance at the hearing may require one man-week per company. Considering that, due to the importance of the issue and the legal aspects involved, such of this work is usually handled by lawyers and higher level company officials, a ldgor rate of $200/day will be asatiaed. In addition,-total travel expenses of $600 for two people per company will be assumed. The total expense for the eight companies listed using the above figures is $19,200.
If EPA grants the manufacturers an exemption frcm the 'manufacturing," 'processing," and 'distribution in oamnerce* bans, the pigment that is manufactured could only be used to formulate inks, etc., if the purchasers were in turn exenpted from the 'processing* and 'distribu tion in ccnmerce" bans. Further, since the inks will contain PCBa at levels below 50 ppa because of dilution of material containing aore than 50 ppn PCBa, all material containing the pigments will have to be labeled as 'PCBa," and the users will require exemptions from the 'use' ban.
There is no information in the record that suggests whether EPS will consider class action petitions for exemptions, or that would suggest how EPA may handle the labeling problem. Therefore, no estimate can be made of the resulting economic impacts of these provisions of the regulations.
Other chemicals: Mb information exists in the record to support any estimate of the impact of the ban regulation on canpanies such as Alcoa and Dow Coming that are inadvertently manufacturing PCBa in chemicals other than dry pigments. These chemical processes will be subject to the same ban provisions or, alternatively, the need to obtain exemptions from the manufacturing, processing, distribution in commerce, and use ban regulations as described above for dry pigments.
U2 HONS 0133AA
14.4 PCB Controlled by the Regulation
Plewnta: Data reported by Sun Chemical Oorp. suggests that the average PCS concentration in diaryllde pigments is 95 ppm aid in (hthalocyanine pigments is 170 ppm.*
total amuaX sales of the phthalocyanine pigments are 13.2 million pounds of which 561 is liqpotted (most from Japan).** The rest is mete in the U. S. by six manufacturers, three of which use trichlorobenzane and praauaably have problems with PCB contamination. If the six manufacturers have equal market shares, the total KBs in the production of the three that use trichlorobenzane would be (13.2 million pounds pigment per year x .44 D.S. market share x .5 share from companies with KBs in product x 170 ppm KBs ) 544 pounds KBe per year.
Total annual sales of dairylide pigments are 9,760,000 powis, all of tiiich is contaminated with 3,3' - dichloroblphenyl at an average concentration of 95 pp. Seduction of this concentration to 50 ppn by required process changes would reduce the aeount of KBe entering the environment by (9,760,000 pounds pigment x (95 ppm - 50 ppm) ) 441 pounds per year.
Other chemicals: ft) information is available to support any estimate of the total production of KBs In other chemical processes.
14.5 Susaery - Eooncedc Impacts
Upper Bound;
Increased Annual Additional
Conversion Post Operating Costs
Poets
(hthalocyanine pigimnts Diaryllde pigments
$4,250,000 1,330,000
No data 345,000
No data No data
Aluainua maeltlng Chemical mmifacturing
No data
no data
No data
^Appendix's to "Main Comments of Dry Cblor Manufacturers Association...." doted August 7, 1978.
*`Letter from Arthur Hopmeier (Rithalchem Inc.) to EPft dated August 4, 1978.
133 HONS 013345
lower Bound;
Exarption applications $ 25,600
Aluminum melting
Chmical manufacturing
ft> data
No data
lb data
14.6 Coat Per Pound of PCBe Kept from the Bwlmr--nl
Jhthalocyanine pigments
Diarylide pigments
~-3f
" *7*1 pec pound KM - nOM{.
*Vm dollar* as initial expense ie equivalent to continuing annual costs one dollar discounted at 1M.
134 HONS 013^46
I
1S.0 SPILL MATERIALS: 50 ppn TO 499 ppm PCM The change In the definition of "PCB" from 500 ppm to 50 ppm will
require that materials such as dirt that are contaminated with FCBs in this concentration range will have to be picked up and buried in an approved PCS landfill. There is no information in the record that can be used to estimate the total additional volute of material that will be transported to these landfills aa the result of this charge in the regulation.
Disposal of PCB contaminated material in approved landfills has bean reported to cost $3 per cubic foot (Versar 1977, p. 3-7) and transportation to these facilities will cost an additional $2 per cubic foot (Versar 1977, p. 3-19). If the spill material covered by this regulation is asauned to be contaminated with 275 ppn FCBs, the cost of disposal will be ($5 per cubic foot/(100 pounds per cubic foot of dirt x 275 ppn FCBs) - ) $182 per pound of PCB. This figure could be lower in some cases if EPS approves alternative disposal methods in response to specific petitions for eaaapticn from this portion of the disposal regulation.
135
HONS 013347
16.0 CAPACITOR MANOFACIURItC 16.1 Present Use of PCBa PCBs Mere used as the dielectric liquid in almost all
paper/foil and film/foil A.C. electric capacitors manufactured prior to 1976. The primary types and uses of PCB capacitors are listed in Table 16.1-1.
Substitutes for PCBs have been developed by the capacitor manufacturers in anticipation of the ban on the manufacture and processing of PCBs. No PCB power factor capacitors were manufactured after late 1977, and there are no PCB capacitors of this type known to remain in manufacturers' inventories (Versar 1978, p. 99). A survey of manufacturers of industrial capacitors indicated that five companies (representing a $4% share of the market in 1976) were planning in mid 1977 to continue using PCBs into 1978 but to discontinue manufacturing PCB capacitors during 1978 (Versar, 1978, p. 103). two of the manufacturers have provided additional data on their use of PCBs during 1978 and on expected inventories of PCB cvBcibors. Aerovox (24% market share) planned to stop using PCBs on September 9, 1978, and expected an inventory on October 1 of less than 100,000 PCB capacitors.* Universal Manufacturing Co. (13% market share) has estimated that its inventory of capacitors at the end of 1978 will be approalmately 800,000 iteas which cost about one million dollars to manufacture. In addition. Universal will have an inventory at the end of 1978 of at least 500,000 completed ballasts which cost (tout $2,500,000 to maka.**
`Latter from Clifford Tuttle (Aerovox Industries, Inc.) to EPA dated August 15, 1978. Oral counts of N. Ray Clark (Universal Manufacturing Corporation) at the August 29, 1978 hearing on the proposed PCB Ban Mgulaticn.
136 KQNS 013348
Table 16.1-1
Major Types and Oaea of PC3 Capacitors
202*
Estimate 1976 Sales*
Use
Power Factor Correction Industrial Capacitors
$54.5 million $94.5 million
Used by electrical
utilities in high voltage power distribution systems.
(totor Control Ballast
Electronic
Used as part of large single phase A.C. motors (air conditioners, etc.).
Used as a component of ballasts for fluorescent lights and high intensity discharge (i.e., mercury arc and sodiua arc) fixtures.
As part of the circuitry in some TV sets, microwave ovens, computers, etc.
Sourcei Versar, 1978, pp 97-98.
137 HONS 013349
16.2 Requirements of the PCB Ban Regulation
Manufacturing! The regulation bans the manufacture of PCB capacitors.
Distribution in Commerce! PCB capacitors and new equipatnt containing PCB capacitors may not be sold (i.e., distributed in coamerce) after July 1, 1979.
16.3 Cost Impacts of the PCB Ban Regulation
Manufacturing bans The economic impact analysis of the proposed PCB regulation estimated that non-PCB power factor capacitors would cost 10% to 20% more than PCB capacitors having the sane performance characteristics and that the cost of industrial capacitors would increase 15% to 20% because of the change from FCBs to other dielectric fluids, (Versar, 1978). The only additional information that has since become available is the testimony of Ray Clark who suggested that 'perhaps in the overall, simply based on the difference of dielectric constant (of the non-PCB dielectric fluid) the non-FCB industrial capacitors should cost more on the order of five to seven percent.** Based on 1976 industry sales (Table 16.1-1), annual cost increases due to the banning of the manufacture of PCB capacitors would be expected to be (10% to 20% of $54.5 million $5.5 million to $11 million for power factor correction capacitors and (7% to 20% of $94.5 million " ) $6.6 million to $13.9 million for industrial capacitors. These estimates should be increased by perhaps 15% to compensate for inflation during 1977 and 1978. Since the use of swell capacitors is expected to grow rapidly over the next few years because of federally mandated Improvements in the electrical efficiency of appliances, the total demand for capacitors and the total increased costs resulting from the ban on the use of FCBs may be greater than these estimates baaed on historical sales data.
^Oral conents of N. Ray dark (Universal Manufacturing Corporation) at the
August 29, 1978 hearings.
"
'
138 HONS 013350
Ban on Distribution in Cgiroerce: The demand for PCB capacitors remaining in manufactures's inventories at the end of 1978 is likely to be extremely limited because the regulation bans the sale of these capacitors or new equipment containing PCS capacitors after June 30, 1979. The inventory losses incurred by the companies that use small capacitors in the manufacture of appliances and equipment is discussed in detail in Chapter 3.
The maxim* inventory losses incurred by the manufacturers of PCB capacitors would occur if all capacitors remaining in inventory at the end of 1978 *re scrapped. If all of the manufacturers who used PCBs in 1978 had the sane expected inventory losses as that percentage of annual sales anticipated by Universal, total Inventory losses would be (.54 market share for all affected capacitor manufacturers/.13 universal market shnre) x $1,000,000 Universal inventory loss ) $4.15 million. However, the actual loss will probably be much less than this because Universal was the last company to phase out the use of PCBs and because some opportunities may exist during the first six months of 1979 to dispose of this inventory. Therefore a reasonable estimate of inventory losses may be in the range of $1 to $2 million, all occuring during 1979.
16.4 PCBs Controlled by the Regulation
Tbtal consumption of PCBs by the capacitor manufacturing industry was 21 million pounds in 1975 of which 459 was used in large high voltage power factor capacitors and 55t in industrial, lighting, and appliance capacitors (Versar 1976a, p. 6).
Most large high voltage power factor capacitors do not rupture upon failure, and only 20t to 25% of the PCBs escape to the environment from those that do rupture. If it is assumed that 10% of the capacitors rupture on failure, the total amount of PCBs entering the environment from each year's production of large high voltage power factor capacitors would be equal to (21 million pounds per year PCBs x 45% in power factor capacitors X 1% rupture on failure x 15% PCBs lost on rupture - ) 14,200 pounds PCB per year.
139
HONS 013351
Only 0.4% of the email capacitors are assumed to rupture in use (Chapter 3). If 15% of the PCBs leak out of these ruptured capacitors, the total amomt of PCBs entering the envirorment frcm each year's production of small capacitors would be equal to (21 million pounds PCBs x 55% in small capacitors x 0.4% ruptured in use x 15% leak out * ) 6930 pounds per year. The rest of the PCBs would be disposed of in municipal landfills. There is no information in the record to support an estimate of how Mich may leach out of the landfill, but it is expected to be low due to the absorptive capacity of the surrounding material.
16.5 Stannary - Eoonosiic Impacts
Increased cost of non-PCB power factor capacitors: $5.5 million to $11 million per year.
Increased cost of non-PCB industrial capacitors: $6.6 million to $18.9 million per year.
Inventory losses incurred by manufacturers of PCB industrial capacitors: $1 million to $2 million (1979 only).
16.6 Cost Per Found of PCBs Kept frcm the Environment
Power factor capacitors
$5.5 million to $11 million per year
14,200 lb/year
8387 to 8775 per poind PCBs
Industrial capacitors
6 million to $18.9 million per year
6930 pounds per year
* 5950 to $2750 per pound
140 HONS 013352
17.0 MN CN THE MANUFACTURE OF WW PCB TRMSFOROS* Liquid filled transformers containing a PCB baaad liquid known
gmarically aa "aakarel" hava been used for nary year* in these installa tions Where tha ride of ftra justified tha use of a fire resistant fluid. Askiral transformrs hava been allowed in hazardous locations such as in side buildings without the requlrcnent for a fireproof vault or fire sprinklers. *to substitute transformr liquids have yet been developed whldi have fire resistant properties equal to the PCB based aakarel.
17.1 Raoulrsamnts of the Rsaulations The regulations prohibit the manufacture of new PCB transformers
after December 31, 1978, but classify continued use of existing PCB trans formers, sxc^t those used in railroad locomotives, as use in a totally closed Banner. The regulations authorize certain minor maintenance of Misting transformers but prohibit major, rebuilding of failed units. The ispacts of the regulation on the servicing and rebuilding of aakarel trans formers is discussed In detail in Chapter 4. Disposal requirments for fsllad aakarel transformers are opacified by the PCB Marking and Disposal Mgulatlons, and thsss requirements are not being changed by the PCB Ban Begulations.
17.2 Industry Structure, Production, and Sales Monsanto's customer list for PCBs in the early 1970s included
thirteen ccmpsnles that used PCBs to ssnufactire aakarel transformers. These ooapsnies and the location of their transformer manufacturing plants
This diopter is repeated with minor changes from Versar, 1978. The EPA promulgated without change the proposed regulations that affect the mmifacture of new PCB transformers.
141 HONS 013353
i
are listed in Table 17.2-1. Production of askarel transformers avenged SOOC units per year in the early 1970s (Versar 1978, p.109). Mien these caqpanies were contacted ty Versar in September, 1977, only one marufecturer was still producing askarel transformers, and it planned to stop production of this type of unit before the end of 1977 (Versar 1978, p.109). All of these Manufacturers produced both oil-filled and askarel transformers in the sane plants. Oil-filled transformers are interdianoable with askarel transformers in new applications provided the installa tion is properly engineered. Other substitutes for askarel transformers are also available. The 140,000 askarel transformers presently in service are only two percent of the total number of power and distribution transfonaars in use (Versar 1978, p.lll).
17.3 Substitutes for PCB Transformers The askarel transformers presently in service were specified
because this type of liquid-filled transformer offered advantages in size, reliability, and fire safety that were not available with other types of transformers. Alternatives to PCB transformers have always been available, although all of the other types of transformers have different design characteristics and none are direct sdostitutes for the PCB units. There fore, eventual replacement of the existing PCB transformers will require that each of the present installations be re-evaluated and that the necessary engineering changes be made to allow use of the best available * nplacmsent unit. New transformer installations will be designed to nabs opt ina use of the available non-PCBe transformers. The choice among the available alternative transformer types and mterials depends on the re quirements of each specific applicaiton and the characteristics of the available non-PCB units.
142 HONS 013354
Table 17.2-1
U.S. Transformer Manufacturers That Used PCBs After 1970
Company Name Westinghouse Electric Corp.
General Electric Conpary
Research-Cottrel1 Niagara Transformer Co. Standard Transfotmer Co.
Helena Corp. Hevi-Duty Electric Kuhloan Electric Co. Electro Engineering Nodes Envirotech Huell R.E. Uptegraff Mfg., Co. H.K. Porter
Van Tran Electric Co.
Plant location
South Boston. Va. Sharon, Pa.
Borne, Ga. Pittsfield, Hass.
Findeme, N.J.
Buffalo, N.Y.
Warren, Ohio Medford, Oregon
Helena, Alabama
Goldsboro, N.C.
Crystal Springs, Mass.
San Leandro, Calif.
Lebanon, Pa.
Scottsdale, Pa.
Belmont, Calif. Lynchburg, Va.
Vandalia, 111. Waco, Texas
Source: Versar, 1976a.
143 MONS 013355
A number of alternatives to the use of FCBs in fire resistant liquid-filled transformers and to the use of transformers that contain any dielectric liquid tuwre been developed and are canraercially available. These substitutes for PCB transformers differ in their performance charac teristics, applicable fire code installation requirsaents, aid cost. The following sections discuss the major types of substitute units that are available.
Non-PCB askarel transformers: Askarels are defined in the National Electrical Code as non-flasnmble chlorinated hydrocarbon liquids. Although all askarel liquids used in the past have been based on FCBs, there is no requirement that FCBs be present. General Electric is pres ently tasting a non-FCB askarel that is a combination of tridilonbensene, tetrachlorobenzene, and a hydrocarbon (either isopropyl biphenyl or terpheryl). GE plans to market this material in 1979 under the trade name Iralec*, if present transformer service tests are successful, and estimates that the price will be about one-half that of silicone.*
If Iralec* does prove to be a direct substitute for PCB based askarel, there may be no additional costs incurred by the banning of the use of FCBs in new transformers.
High fire point liquid insulated transformers: The 1975 National Electric Code (NEC) and previous issues allowed only the use of askarel and dry type transformers in hazardous locations without vault protection. Askarel was essentially defined as a PCB baaed liquid. The 1978 NBC has added a specification (Article 450-23) for "high fire point liquid insulated transformers* which can be used under these same condi tions (Veesar 1978, p.111). The high fire point liquid must have a fire point of at laast 300*C, and must not propagate flames.
`Information presented by GE at a meeting with EFA Office of Toxic Substances, June 21, 1978.
144
HONS 013356
Underwriters Laboratory presently lists three liquids as ateting the high fire point property requironents for transformers op erating at voltages below 600v (Versar 1978, p.ll2)>
Dow Corning 561
General Electric SF-97 (50)
SHE Silicones Corp. F-190
Factory Mutual Research has not yet completed developing formal
approval requirmnsnts and procedures for high fire point transformer
liquids. However, based on preliminary tests. Factory Mutual has issued
interim guidelines to its field offices which allow six silicone liqui<b
and three hydrocarbon liquids at Factory Mutual insured locations without
special fire protection. The list of Factory Mutual accepted liquids
includes the following (Versar 1978, p.112):
Smaller
Designation
Type of Fluid
Dow Coming Dow Coming General Electric Union Carbide SMS Silicones SH6 Silicones RTE Corporation Gulf Oil Chemicals Co.
Uniroyal
DC 561 DC 200 SF-97 L-305 F-101 F-190
KXB*> RF Dielectric Fluid PAO-20E
Silicone Silicone Silicone Silicone Silicone Silicone Hydrocarbon Hydrocarbon
Hydrocarbon
145 MONS 013357
Mineral oil-filled transformers: if fire safety Mere not a consideration, there would be no reason why oil-filled transformers could not be used in all applications. In the past, PCB-f illed transformers have cost about 1.3 tines as much as oil-filled units of the sane cspacity, and thus most users preferred the oil type where possible (Versar 1978, p.112). The oil-filled transformers ace the same size as the askarel units and are considerably lighter in weight. Also, mineral oil has somewhat better heat transfer diaracteristics than askarel, and an electric arc in mineral oil results in breakdown products that are non-corrosive.
The major disadvantage of mineral oil is flaommbility; trans former mineral oil has a flash point of 14S*C. if an arc occurs in the transformer, the breakdown products will be hydrogen and methane, both of which are flammable. Detailed record of such failures are maintained by the electrical industry. Fire Underwriters does not approve cf the use of oils and other flammable liquitb for Indoor applications, tfiere oil-filled transfoosers are not specifically prohibited as on-site ^placements for FCB-filled units, the National Electrical Code inposes certain restrictions ipon their mode of installation.
Oil-filled transformers are used in almost all power transformer applications and for moat substation distribution ^plications where the transmission line high voltage is reduced to 12.8 kv for local distribu tion. Most rural pole 'mounted transformers that reduce the voltage to 220 volts trs also oil-fillsd. The issue of flammability only becomes iaportant where the distribution transformer aust be buried, as in aery urban applications, or locatad close to, within, or on the roof of the building it serves. FCB-fillcd transformers have, in the past, been used in most such applications. Oil-filled transformers can be used in these appli cations only if they are suitably Isolated from floanable structures or if these structures are suitably safeguarded against fires. Mien trans
it
MONS 013358
footer* are located outside the building they service, the low-voltage power tust be brought into the building via cables or insulated buses. Additional energy losses are then caused by heating in the low-voltage transmission lines from the transformer to the point of use.
Open air-cooled transformers; Transformers can be built without the use of a liquid cooling medium. One type of dry transformer that is quit* successful, under limited conditions, is the open air-cooled trans former. In this design, cooling air is driven through the transformer ty either natural convection or forced circulation. In those sizes where air-cooled transformer* are available, they are about equal in price to aakarel-filled transformers of the same KVA rating. However, open air cooled transformers are limited in both heat capacity (which limits their ability to operate under occasional overload conditions) and dielectric strength (wbidi limits the maximum voltage available).
The problem of electrical Insulation is even more severe if the open air-cooled transformer only operates intermittently. Mien the trans former is operating, the heat generated within the windings keeps the insu lation dry and maintains a hi^i dielectric strength in the solid insulating eattrial. However, when the transformer is not operating, the coils cool to mnbient teepsraturss and the insulation can absorb moisture from the air tftich reduces its dielectric strength. Open air-cooled transformers must be thoroughly dried before being put into service after each cool period.
One other problem with air-cooled transformers is the tendency of dust to be attracted frcm the air to the coils by electrostatic forces, fost can build up in the coils and block the flow of air, or it can form conductive paths and cause short circuits.
147 HONS 013359
Cpen air-cooled transformers are generally limited to dry, clean locations where the load requirement* are fairly even and constant and where the maxima* voltage does not exceed 30 kv. Such traimfocmers are being successfully used in large office buildings, particularly tall buildings where the transformers are located every few floors. Even in this application, though, conditions arise that exceed the capabilities of the transformer. For instance, in the Sears Tower in Chicago, Oiich is over 1400 feet tall, the electric power is brought into the building and to the distribution transformers at 128 kv, which is beyond the voltage 1imitations of open air-cooled transformers (Versar 1978, p.llS).
Closed gas-filled transformers*: Transformers can be built with dry inert gas (usually at an elevated pressure) as a heat transfer nediua. These transformers avoid the maintenance probl earn caused by moisture and dust in open air-cooled transformers, but they are similarly limited in overload capacity because of reduced thenml inertia cospared to liquidfilled transformers.
Closed gas-filled transformers must be installed in pressuretight containers because of changes in gas pressure caused by changes in tesperature. However, the maxims* voltage ratings of gas-filled trans formers can be equal to these of liquid-filled units.
A raeeber of different gases have been used as heat transfer media in cloaad gas-filled transformers. The most oaimon gas used in the U.S. is the fluorocarbon hexafluoroethane (CgFg). Nitrogen and sulfur hexafluoride have also been used successfully in certain applications, alius has not been found to be a satisfactory gas for this application because its law dielectric strength results in corona discharges within the transformer. Hydrogen is unsatisfactory because ary leak in the trans former would result in a severe fire hazard.
Inis section is repeated from Versar 1978, pp.115-116.
148
HONS 013360
necause of the necessity for a pressure vessel container, gascooled transformers are 30 to 40 percent heavier than FCB-filled trans formers and cost two-thirds more (and twice as much as oil-filled trans formers) . In addition, the gas-filled transformers eust be sissd larger than oil-filled units to allow for the expected heavy load peeks of power corsimption.
17.4 Belative Prices of Ncn-PCB Transformers
The relative prices of distribution transformers of the size and type cameonly installed in office buildings are suxnarized in Table 17.4-1. If the HTBipe high fire point liquid-filled transformer proves to be acc^table for installation without auxiliary fire protection, there should be no cost increases for new transformer installations resulting from the ban on the manufacture of PCB transformers. The open dry type transformers are also quite cost competitive with the PCB units for most applications.
TVoe of Unit
Oil-filled PCB Non-FCB askarel Kn*p* Silicone Cpen air cooled Sealed gas cooled
Table 17.4-1* Relative Transformer Prices
Price; 1000 WA Unit
$15,300 19,900 19,000 18,400 22,300 20,700 30,600
Price; 2000 EVA unit
$23,300 30,300 29,000
~ 28,000 34,500 35,000 46,600
Source; NSC Engineers, 'Distribution Transformer Status - HIT Project.* Maeorandua to U.S. General Services Adninistration, June 1, 1977, as cited
in Versar 1978, p.116.
149 HONS 0133*1
17.5 Oosnliance Pots
Clean-up coeti: Hie only costs incurred by transfooaar manu facturers resulting frosi the ban on the use of PCBs will be clean-up and disposal costs of flushing PCBs frcm storage and material handling equip ment before using this equipment to store high fire point liquids. This equipment consists primarily of storage tanks, filters, puqps, an] pipit?. Clean-up costs, including disposal of contaminated solvents, tfiould not esceed $10,000 per plant, or a total one time cost inpact of perhaps $100,000 in 1977 and 1978 (Verser 1978, p.117).
Post of substltutesi The high fire point liquid cooled trans formers and air-cooled transformers will cast dbout the smse to 10* more than aakarel units depending on the acceptability of non PCB asksreIs and hydrocarbon base high fire point transformer liquids. Based on past sales of 5000 askarel units par year at an average price of $20,000, a 10 cost increase would increase sales and costs to the users by (5000 x $20,000 x 108 " ) $10,000,000 per year. There should be no effect on the demand for transformers for new installations, and there may be an increase in the demand for replacement transformers of 1000 to 2000 units per year. This additional dmaand should be easily sipplisd since the transformer manufac turing industry has recently been operating at only about 608 of capacity (Veraar 1978, p.117).
Market structure should not be significantly affected because all of ths former mvxafacturers of aakarel tranafonaers will have equal access to ths high firs point transformer liquid materials and technology. Access to this amzkst segment will open to those transformer aanufcturers who did not offer aakarel as an alternative to oil. This will primarily afford a marketing opportunity to RTE Corporation which has never stpplied aakarel wits but which has a strong market position in the high fire point liquid transformer area. The increased sales by DTE will probably be less than the total Increase in transformer sales, so this small shift in
150 MONS 013362
market structure should not result In a net decrease in the sales by any of the other manufacturers.
Increased fire losses! Ihe presently installed FCB askarel transformers were installed at a prrnnium cost compared to oil-filled units in order to achieve Improved fire safety. Mot all of the substitutes for FCBs have as good fire resistance. In particular, the high fire point transformer liquids can bum under certain conditions, including exposure to an external fire, and can release flammable gases if an electrical arc occurs within the transformer.
Various non-flaanable substitutes for PCB askarel transformers are available. Including the various dry type units and non-PCB askarels. Although these alternatives may cost acre than the FCB units they replace, they can achieve equal fira safety. Therefore, the banning of the manufac ture of FCB-fllled transformers is not txptctcd to result in significant increased fire loesee.
17.6 PCBa Controlled by the Regulation There is no information in the record to support any estimate of
the probability that PCBa used in askarel transformers will enter the environment frem accidental spills and venting of transformers. Venting results in the loss of no more than 2* of the total fluid in the trineformer. However, good clean-up of spills should limit the total losses to perhaps 5% of the total liquid vented. Use of FCBs in transformer manufacturing was about 12 million pounds per year in 1975 (VSraar 1976a, p.6). The ban on use of FCBs in new transformers will prevent the loss of (2% x 5t x 12 million pounds -) 12,000 pounds of FCBs into the environment from each year's production of transformers.
151 HONS 013363
17.7 Sumarv - Economic Incacts Transitional Costai
Clean-up costs tor manufacturers Long Term Goats;
$100,000 1978 only.
Higher costs of non-PCB transformers
so to S10 million per year.
17.8 Cost Per Pound of PCBs Kept Frew the Environment
Cost per pound - SO to $10 million per year 12,000 pounds per year
$0 to $833 per pound PCSs
152 HONS 013364
f
13.0 SUrlMAKf 18.1 Transitional post Inpacts Costs of decontaminating or scrapping existing equipment and the
ban on rebuilding of PCB transformers are all transitional costs. These costs will end when the existing PCBs are finally removed frae service. The transitional cost inpacts identified in this analysis of the inpacts of the PCB Ban Regulation (as distinct frcm the previously pranulgated PCB Effluent Standard and the PCB Disposal and Marking Regulations) are susaarised in Table 18.1-1.
18.2 Long Term Cost Inpacts The costs resulting fra* the ban on the manufacture of PCBe will
be continuing costs and will result in along term economic ispact. These costs include the additional cost of non-FCB capacitors and transformers. The long term costs ioentified as resulting from the PCB Ban Regulation are suanrised in Table 18.2-1.
18.3 Cost Per Pound of PCBs Kent frcm the Environment The effectiveness of the regulation in preventing the entry of
PCBs into the environment was calculated for each industrial segment if sufficient data was available. These costs are simraarized in Table 18.3-1.
HONS 013365
..
4
Iton (Chapter)
PCB Transformers: Manufacturer Clean Op Costs (17) Ban on Rebuilding (4)
Table 18.1-1
Transitional Cost Iapacta
$ Million Per Sear
1979
Succeeding Tears
$ Million Total
Estimated
Reliability of Total
5 .1 9.6
0 **
$ .1 373 to 749
-50% + 500% -50%
Lost Service Time
2.4 **
75 50%
Locceotive Transformers (5)
Retrofill Program bo 6t Limit Ihn-
Retrofill Program to O.lt Limit
Couplets by Jan. 1, 1982
Ccnplete by Jan. 1, 1984
6.6 5.15
20% 20%
Analytical Casts
PCB Capacitors and Bqui(raent Equipment Redesign (16) Manufacturers' Inventory Obsolescence (16)
Ban on Sales of Equipment after July 1, 1979 (3)
Coat of Petitioning for CjianyiLiens
Ocnplete by Jan. 1, 1985
*
.444
50%
1
1 to 2
0
1 to 2
50%
1,000
0 1,000 -100% + 50%
These costs will be significantly reduced or eliminated if EPA grants exeapticns from the distribution in cameras' ban.
10***
0
10
Data not available to sipport estimate; probably aaall cost iapact. Costs will be incurred over 30 to 40 years, probably increasing slowly for 10 years arei then
decreasing slowly. May be significantly reduced if EPA accepts class action petitions.
MONS 013366
1,
it-- IQmpt--L
Tabla IS. 1-1 ICunUmmd?
f1Ja79d8llilo--nttMinnr
Mr Tx
* --Ulan total
M--
--Liability of Total
Oil rilled It--**** (*
Ban an neclslwing Oil tor Nasal*
3.2 tx> 3.2 to 5.6 5.6
7 No data on duration of iapact
Cbot of Equipping Hicfi Efficiency Boiler Ooot of Appro--d PCB Incineration
Traneformer Service (7) Special Storage Areas
NO data
7 No data on duration of Japact
-90% to 0*
7 No data on duration of iapact
Hilling Machine* (8)
Rebuild Loaders uKi Scrap continuous Miners
Storage Costa Exenption of Application Elactroragneta (9) Dan on Rebuilding Hydraulic Systems (10) Testing
Rstrofill nispnsal of Fluid 50-500 ppm PCSs Mzfcing Ban on RKycling Fluid
Couplets by Dec 31. * 1981
Ocaplete by Dec 31, 1981
.01 0
.001
0
1.6 1 to 2.6
.01 .001
20% 50%
50% 50%
.1 .1
1 .96
20%
.5 to 10980-84 1.4 total)
1.5 to 2.4
9.8-16.1 1-1.5(1480 only) 10.8 to 17.6 by 1984
1.4 .20*80 an?]r> i.6
.05 0
.05
.3 to 1.7 0 to 1.7
.7 to 3.4
-20%
50% -80% + 20% 50% -80% t 20%
Infor--tion Not Nvailtoia in Naoord to N--e tsti--tas
HONS 0 1 3 3 6 ?
Tfcble 18.1-1 (OontiniMO
Itsn (Owttrl HMt Transfer Systems (11)
lasting Itetxofill
Cost Savings - Disposal of Systems Cospressocs (12) Reclaimed oil (13)
Increased Cost of Synthetic Road Oil Material Increased Cost of Road Oil
Unintentional Contaminants (14) Process Changes - Phthalocyanine Pigrents
? ilUrJn Par YSar
ssnw
19/9
SnonHiw Yrs totJii
Estimated
Reliability of Votal
.045 to -06 .135 to .18 .18 to .24
5.1 to 6.8 9.9 to 13.2 15 to 20 (I960 only) (by 1980)
-50% "501
.2 0
(2.4 to 3.0) *50% .2 -50% + 100%
0 to 31.7
0 bo 31.7 (thru 1984)
0 to 6.4 (years 6-15)
4.25
0
0 to 100 0 to 64*
4.25
-80% + SOt
Process Changes - Diarylide Yellow Pigrents 1.3 0***
Process Changes - Other Processes
** 0
1.3*** **
-80% + 50%
Exemption Applications o T
.02 o
.32 -0'. + 50%
wwe ***Alao long term ooit ixt$*cta; See ltfcle 18.2-1.
Table 18.2-1 Long Term Coat Impacts
Transformers: (Chapter 17)
Increased Cost of Non-FCB Transformers Increased Fire Losses
$0 to 10 million/year $0
Capacitors: .(Chapter 16)
Increased Cost of Non-FCB Power Factor Capacitors .
$5.5 to 11 millior/year
Increased Cost of Non-FCB Industrial Capacitors
I j Diarylide Yellow Pigment (Chapter 14) !
Increased Manufacturing Cost
$6.6 to 16.9 million/year $345,000/year
Spill Materials (SO to 500 ppa PCBe) (Chapter IS)
No data
157 MONS 013369
Wl 18-3-1 Bccnaaic Oof of the KB Ban peculation
aCvhaarttaer Htafcar It--
3 Scrap Spara KB Capacitoce
3 nauw KB Capacitors froa Bnlit--it In Invantory
4 Ban Babuildlng Aakarel Tranafouaarg
Total Cbat $ Killian
1
Bounds KBe Diverted fre* the Envircnaent
500
Ooet per Kind of KBe
$ 2,000
1,000
5,160
$187,000
Theee caeta will be significantly reduced or eliadnated if EPA
grants naqiLiua froa the "dietribution in aoanxoe* ban.
397 bo 771 (30 yra) 47,000 to 925,000
$429 to $16,400
5 Batrofill milraad Tranafomara to 6t
5 Batrofill Railroad Tranaforaers froa 6% to .It
6.7 5.15
*(3.76 adllicn lb) total
**(80,240 lb. total)
**(>$1.75) **(>$68)
6 Raquira Incineration of 96 to 510 (30 yra) Tranaforaar Oil
200,000
$480 to $2,550
7 Spacial Storage Arena at Tfcanafonaar Service Stopm
*
**
8 Retrofill/Ban PCB Miner 2.6 to 4.3 Itotoct
7 (27,500 lb total)
? (>$94 to $155)
9
Ban Rebuilding Electro*
.96
agnate
200 to 2,000
$480 to $4,800
*Informtion not available in record to arte aatlaeta.
rapceeanta total aaouit of KBe in thla im. Informtion not avaibfcle in recxxd to mfca an aatimta of aaouit divert*] tram thm anvinmant.
HONS 013370
HONS 0 1 3 3 7 1
nbk H.3-1 (Oontinued)
Oaaptar Mater Tta.
Mel Cbet $ MUlion
tolrii RSi Plwi'fl fm thi Envlxcnant
10 Daoontaadnate Hydraulic 21.4 to 25 Hyetaae
470 to 2,3*0
11 Daoontaainate Heat Tranafar Systran
12.8 to 17.2
12 Deocnteadnate Ooaptaasors
.2
1,872 to 2,496
13 Ban Oea of tMsta Oil on 0 to 31.7/year Roads
8,073/year
14 Rithalocyanina Blue TispantM .425/year
544/year
14 Diarylide Tallow Pigaanta .478/year
441/year
15 Spill Mtarials (50-500ppa)~
to Chemical Mate landfill
*
*
16 Ban New Large PCB Capacitors 5.5 to 11/year
14,200
16 Ban Maw Snell PCB Capacitors 6.6 to 18.9/year
6,930/ynar
17 Ban New PCB Tranafanaera 0 to 10/year
12,000/year
Inforaation not available in the record to make estinate.
Ooet par taad of ICBB $6,000 to $53,000
$6,870
* $0 to $3,925
$781 $1,084
$182 $387 to $775 $950 to $2,730 $0 to $833
References
Dow Coming Corporation. Removal of PCB from Dow Coming 561* Transfonaer Liquid by Charcoal Filtration. Midland. Michigan: undated.
EPA. 1976. "Water Program - Proposed toxic Pollutant Effluent Standards
for Polychlorinated Biphenyls," Federal Reqister. Julv 23. 1976. m.
30468-30477.
---------------- 3--------
7
EM. 1977a. "Polychlorinated Biphenyls (FCBs), toxic Substance Control," Federal Register, May 24, 1977, pp. 26564-26577.
Ern. 1977b. "Polychlorinated Bipheryls (FCBs), toxic Substance Control," Federal Register, Decesfcer 30, 1977, p. 65264.
Em. 1977c. PCB Markina and Disposal Regulations - Sirnort Dnment.
(OTS-068005) Washington,'b.i.: tfficeOf foxic Sdostihces, &.S.----Environmental Protection Agency, undated.
Em. 1977d. "Proposed toxic tollutant Effluent Standards for
Polychlorinated Bipheiyls (PCBs): Final Decision," Federal Reqister,
February 2, 1977, pp. 6531-6555.
---------------- ---------
Em. 1978a. "Polychlorinated Biphenyls (FCBs), Oisposal and Marking,"
Federal Reqister, February 17, 1978, pp. 7150-7164.
Em. 1978b. "Polychlorinated Bipheryls (PCBs), Addendus to Preaable and
Corrections to Final Rule," Federal Reqister, August 2, 1978. do. 33918-33920.
Em. 1978c. Support Dncuaent/Draft Voluntary Bavironaental Insect Statement for Polychlorinated Biphenyls (PCBs) Manufacturing. Processing, bistributlon in Ccamerce and bee Ban Regulation (Section 6(e) of TSn). Washington, D.C.: Office of toxic Substances, U.S. Environmental Protection Agency, May, 1978.
Em. 1978d. "Part 750 - Procedures for Rulonaking Under Section 6 of the
toxic Substance Control Act: Interin Procedural Rules for Polychlorinated Biphenyls (PCBs) Ban Exaction," Federal Reqister. Novasfcer 1, 1978, pp. 50905-50907
Em. 1978a. "Polychlorinated Biphenyls (PCBs), Manufacturing,
Processing, Distribution in Caaaerce, and Use Bans," Federal Reaister.
June 7, 1978, pp. 24802-24817.
-------------- =a-------- L
MOMS
Jade Faucett Asaociatee, Inc. 1976. Economic Analysis of Ptcooesd Bale Pollutant Effluent Standards tor Polvdaoclnstsd Biphenyls: Ttsntda-- Capacitor. ana kb Manufacturers iep i3b/i-76-6o8). Washington. p.c.i office ot Mater Hanning and StSndwde, U.S. Environ--ntal Protection Agency, October 1976.
FDA. 1973. 'Polychlorinated Btpheryls - Cont--ination of An1--1 reach, Foods, and Food Packaging Materials," Federal Register, July 6, 1973, pp. 18096-18103.
Foss, St^hen o. t Higgins, John B.r Johnston, Donald L. i McQuade, J--es M. (General Electric Co.). 1977. Betroflllino of Railroad Transfer--re. Canbridge, mai Transportation Systaas Center, U.S. bor, July, 1978.
Hesse, John L. 1975. "Polychlorinated Bipheiyl Usage and Sources of Loss to the Environ--nt in Michigan," Conference Proceedings. National Conference on Polychlorinated Bicnanvla (Noveaber 19-U, 1975, Oucaoo, Illinois 1. ijsshlngton,~5.'5.!'8tti oTrotic'SJmt--ces, tf.l.-----Environwntal Protection Agency (Report No. E>A 560/6-75-004).
Hofstader, R.A. (Exxon Research and Engineering Co.); Like, D.J.; Badie, C.A. (Cornell University). 1974, "Interference in the Electron-Capture Technique for Determination of Polychlorinated Blpheryls by Sulfur-Containing Coapomdi in Petroleua Products," Bulletin of Envlronawntal Cont--lnstlon and Tbslcoloqy, Vol. 11, No. 2, 1974.
Lapp, T.W. (Midwest Rtsearch Institute), 1976. The Manufacture and Use of Selected Aryl and Alkyl Phoerhste Esters, EPA 56d/i>-76-008, February,
Msugh, T.W., 1976. "Rereflned Oil: An Option That Savea Oil, MiniaUxes Pollution," Science, p. 1108-1110, Spt4nber 17, 1976.
Monsanto industrial Chemicals Co. Arociors for --. St. Louis, Mo.: undatad.
NIGSB. 1977. Crltsria for a to Polychlorinated Bichanyla
(kite I
iftoiS.l ta(i-xnjt*doaehlr-d-)..tP.hOUfcclolcpaattiioonnanloB. roaure
77-225), MBShingtan, D.C.: U.S. Govemeent Printirg Office, Septeeher
1977.
Ql--teed, J. 1977. On--ants end Ihcr--inlatlone on Maktw Fluid for AHaral Transfoc--ra. Mmikeeha, HI.: ME Corporation. Nov--bar I?.
HONS 013373
Page, Killian C.: Michaud, Terry (Dow Coming Corporation). 1977. "Development of Methods to Retrofill Tranefonwre with Silicons Transformer Liquid*, SEE Paper 22*477, Preaentad at the electrical Insulation Conference, Chicago, Illinois, September, 1977. (Subnittad as attadnnt from Tarry Michaud (Dow Coming Corp.) to PCS Rnoord, August, 1978).
Rolliru Envlronamtal Service, Inc. 1978. Indaanified Disposal Service focPolYchlorlnated Biphenyls IPCBa - hstaSHs)'. May 1. with TAR Electric S^ply Co. written reply conaant on the PCB Ban Regulation.
Stsndell, Ray C. 1975. *Sunacy of Recent Information Regarding Effects of PCBe on Birds and Mmaeals.* in Conference Proceedings. National 1. 19/5. ChicaqoT 111. Protaction Agency (Report No. EPA 560/6-75-004).
Versar, Inc. 1976a. PCBa in the United States: industrial use ad Environmental Dietrlbulion. Springfield. Virginia: National Technical Infoneat ion Service (OTTSPB 252-012/3HP), February, 1976.
National Technical Information Service (NTIS PB 267 833/2NP), April, 1977.
Varaar, Inc. 1978. Microeconomic Impacts of the Proposed *pcb Ban Regulations* (B'A 5<o/s-7>-35), Springfield, Va.: National Technical Information Service (OTIS PB 281-881/3W), May, 1978.
U.S. Department of Agriculture Ad Hoc Croup on PCBe. 1972. Agriculture's Pssponslbility Concerning Polychlorinated Biphenyls (PCBs). Hesiiingtcn" ri.C.i fafficeof Science ano Eoucation, u.s. Department of Agriculture, 1972.
Mslah, E.J.j VOytiX, D.E.: Pearce, h.A. (Weatinghouae Electric Corp.), 1977. Evaluation of Silicone Fluid for Raplacament of pcb Coolants In Railway industry, final Report. (Report 5oP6<^tM-i2j4). Cambridge,
Mi.i Transportation Systems Center, U.S. DOT. December, 1977.
Neeme, George. 1977. "Rilychlorinated Bipheryls.* Denver, Colorado: O.S. Department of Interior, File HL5 3-3-10h, June 13, 1977.
HONS 013374
w
Weinstein, [toman J. (Recon Syitena, Inc.) 1974. Waste Oil Recycling and Dleppael. EPA-670/2-74-052. Princeton, tJ.J.r August, 1974.
Mood, David (Msiaanto). 1975. "Chlorinated Biphenyl Dielectrics, Their Utility and Potential Substitute*" in Conference Proceedings. National Conference on Polychlorinated Biphenyls.Novawber 19-21. 1975. Chicago. Tlllonia. weanmgton, 5.(!.t 6fflee of tokic substances?* o: hrvlromental Protection Agency (Report No. BPA 560/6-75-004), pp. 317-322.
MONS 013375
HONS 013376
I
p.e. Ciyard, Managar non*anto Agricultural Products Co. 800 If. Llndbargh Boulavard St. Loula, MO 63166
1
X
r.
HONS 011377
**. >*--
PCB m--mlmitmtnm 5--------^
PA2M41/7M01
PCB MANUFACTURING, PROCESSING, DISTRIBUTION IN COMMERCE, AND USE BAN REGULATION:
ECONOMIC MPACT ANALYSIS
(MUCH 1171 IL1BMIOMOTM. PHOTECTIOIIA88CY omci OF PUUMM MD MMM6anT
wob--tow, ox. mm MONS 013200
This document is available In limited quantities through the O.S. Bwironmntal Protection Agency, Industry Assistance Office, Office of "toxic Substances (IS-793), 401 Street, S.W., 'Washington, D.C. 20460.
Ibis docvjaent will subsequently be available through the National Technical Information Service, Springfield, Virginia, 22151.
SONS 013201
B* 230-03/79-001
PCB WMBHCWRinC, PROCESSING, D&mnUIXON IN ca--o, MBBIW RBGOIATICNi economic rawer mkbis final Report Subeitted tot
0.8. ll>ai Imamu el Protection Apeney Office of Planning and Mnageaiant ' Nbahington, D.C. Attention: Mr. Stephen R. Nell Project Officer Contract lt>. 68-01-4771
March 30, 1979
HONS 013202
Thin rnport has bMn mviaaod toy tha Offica of Flaming and Hanag--ant, U.S. ttwiiranantal Protection tgmcy aid anaoiad foe pdolication. Approval doas not naoaaaartly signify that tba oontmta taflact tha visas and polidaa of tha Bwlromantal Frotaction hganny, nor doaa nantlon of trada nasa or bo--atulal products oonatituta andocaaaant or lanr--anVit' I nn for usa.
HONS 013203
PREFACE
This report mis prepared by Verier, Inc., for the Office of Pluming and Msnspunt of the U.S. Bnvlromentel Protection Agency. The report summarises Verier'i estimate* of the probable costs and impacts of complying with the PCB Manufacturing, Processing, Distribution In Ooswrce, and Oss Ban Regulation - 40 CFR Fart 761. This regulation iapl--wts the regulrunts of Section! 6(e)(2) and 6(e)(3) of the Ttoxic Substances Control Act.
Versar's Mialysis of the econcadc impacts of the proposed PCB Ban Mgulation was suemurired In the report "Microeconcmic Impacts of the Proposed 'PCB Ban Regulations" dated (by 16, 1978. The promulgated regulations Incorporate a significant umber of changes that were made to the proposed regulations. In addition, considerable additional Information on the economic impacts of the regulation has bean added to the rulemaking record as the result of written oammants on the proposed'regulation and two weeks of ptfclic hearings. This report is a revision of the report on the proposed regulations and is based on the promulgated regulations Mid the Information available from the rulmaking record.
This revised report was prepared by nr. Robert A. Westin. Principal Investigator, and Mr. Bruce MOedeock. Aaaistance in the handling of data and the preparation of final copy was provided by Ms. Juliet Ballance and Mrs. IMbecca Brown of the Vhraar staff. Special acknowledgment is given to the doss support received from Mr. Stephan R. Hail, EPA Project Officer, and Mr. Steven B. Malhenaon who wns the EPA Project Officer diving the preparation of early drafts of this report.
i HONS 013204
TftBLE or ccwrans
ss
x.o pmccocTiow.................................................................................
x
l.X History of PCS Dw..........................................................
X
1.2 Regulatory Action on PCBa..............................................
3
2.0 lermxxoGy tor bocnckec nencr analysis cf the kb ban HsanxrxcNS..................................................................................
8
2.1 General Approach..............................................................
8
2.2 Data Base for Economic mpoct Analysis.................... 10
3.0 XM*ACT OF BAH CN THE DISTRIBUTION CF FOB CAPACITORS AK> B3UIPMBW......................................................................................
11
3.1 Present status.................................................................. 11
3.1.1 FOB Capacitors....................................................... u
3.1.2 PCS Equipment....................................................... 12
3.2 Requirmnts of the Regulation................................... 14
3.3 Bocnoedc tapact of the Regulation............................... 14
3.4 PCBa Controlled by the Regulation............................... 20
3.5 Sunnary - Economic Inpacts........................................... 22
3.6 Cost Per Pound of PCBa Kept From the environment . 22
4.0 mraers on users cf askarel transpcrcrs...........................
23
4.1 Present Status.................................................................. 23
4.2 Requirmnts of the Regulation................................... 24
4.3 Eccncmic Bnpoct of the Regulation............................... 25
4.4 PCBa Controlled by the Regulation............................... 30
4.5 Sutmary - Economic Bqpects........................................... 31
4.6 Cost Per Rand of PCBa Kept from the Biviranmnt . 31
a HONS 013205
TftBlE CF ccwrons (Continued?
Ehs 5.0 RAIUOAD LOCCMOTIVE TRANSFORMERS........................................... 32
5.1 Present Ownership and Use Plans ................................... 32
5.2 Requirements of the PCB BanRegulations..................... 33
5.3 Cost impacts of the PCB BanRegulations..................... 35
5.4 PCBa controlled by the Regulations............................ 42
5.5 Stannary - Economic impacts............................................ 42
5.6 Cost Per Pound of PCBs Kept from the Qwironnent. . 43
6.0 OIL-FILLED POWER MO DISTRIBUTION TRANSFORMERS................ 44
6.1 Present Contamination of Oil-Filled Transformers . 44
6.2 Requiranents of the PCB BanMgulation..................... 56
6.3 COet Impacts of the PCB BanRegulation..................... 59
6.4 PCBs Controlled by the Regulation................................ 70
6.5 Stannary - Bocnonic Impacts............................................ 71
6.6 Ooet Per Pound of PCBs Kept fran the Ehvircment . 71
7.0 oners cn transfciwr service companies.............................
72
7.1 Present Status................................................................... 72
7.2 Requirements of the Regulation................................... 72
7.3 impact of the Regulation............................................... 72
7.4 PCBs Controlled by the Regulation............................... 73
7.5 Summary - Bccncmic impacts........................................... 73
8.0 M2KDS MKKQERY ...................................................................... 74
8.1 Currant Use of PCB-Cooled Mining Machinery Motors . 74
8.2 Raquiranants of the Regulations................................... 76
8.3 Compliance costs ............................................................... 76
8.4 PCBs Controlled by the Regulation............................... 80
ill HONS 013206
TXBLE OF OQWIBtrs (Continued)
8.5 Sumrnry - Bocncnic Aspects................................
EHS 80
8.6 Oust Mr Found of PCBe Kept from the Environment . 81
9.0 BBCHCHKWEIS.................................................................................. 82
9.1 Current Osage...................................................................... 82
9.2 Requiranta of the KB Ban Regulations.......... 83
9.3 Cost lapacta of the FCB Ban Regulations.......... 83
9.4 KBs Controlled by the Regulation.......................
84
9.5 Sunaery - Boonoetlc Aspects........................................... 85
9.6 Cost Per Found of PCBs Keptfron the JOivlrcnnaRt . 85
10.0 H2DRNULZC SVSIB45...................................................................... 86
10.1 rreeent Use of PCBs in Hydraulic Systems .... 86
10.2 Requirements of the PCS Ban Regulation.................... 91
10.3 Dost Aspects of the KB Ban Regulation................. 91
10.4 PCBs Controlled by the Regulation........................... 96
10.5 Susaary - Economic impacts....................................... 98
10.6 Coot Far Found of PCBe Kept from the Envizonsant. 97
11.0 HEKT TMNSnSt SXSIB6............................................................... 98
11.1 Prseant Use of PCBe in Heat Transfer Systems . . 98
11.2 Requirmnsnts of the PCS Ban Regulation................. 98
11.3 Cost Bracts of the PCS Ban Regulation................. 99
11.4 PCBa Controlled by the Regulation........................... 104
11.5 a.emery - Baoncnic Aspects.......................................... 205
11.6 Coat Par Pouid of PCBs Xapt fron the Bnrlronaant. 105
iv hONS 01320*
tame cv mrmns
UBS. 12.0 CCWRESSORS.................................................................................. 106
12.1 Requirements............................................................ 106
12.2 Impacts of the PCS Ban Regulation..................... 106
12.3 KBs Controlled by the Regulation..................... 107
13.0 RECLAOd OIL .......................................................................... 108
13.1 Present Status of PCBs in Reclaimed Oil......... 108
13.2 Requirement* of the Proposed Regulations ....
112
13.3 Sources and Anoints of Contaminated waste Oil . . 113
13.4 Conpliance Costs.................................................... 115
13.5 PCBs Controlled by the Regulation..................... 120
13.6 Sinnary - Economic Impacts................................. 122
13.7 Cost Per Pound of PCBs Kept from the Environment. 122
14.0 fcbs as unurbotcnal product cGNiwmnNrs.................... 123
14.1 Current Production ................................. . . 123
14.2 Requirements of the PCB Ban Regulations.......... 126
14.3 Economic impact........................................................ 126
14.4 PCBs Controlled by the Regulation..................... 133
14.5 Summary - Economic impacts................................. 133
14.6 Coet Per Pound of PCBe Kept from the Environment. 134
15.0 SPILL MMXKDUS: 50 ppm TO 499 ppmPCBs.......................... 135
16.0 CAPSCHOR MMWECTORDC........................................................... 136
16.1 Present Use of PCBe...................................................... 136
16.2 Requirements of the PCB Ban Regulation.......... 138
16.3 Coet impacts of the PCB Ban Regulation.......... 138
16.4 PCBs Controlled by the Regulation..................... 139
v HONS 013208
ffflntimirfl) *sae.
16.5 Sunuary - Economic Bqpacts........................................... 140 16.6 Coat Per Pound of PCBs Kept from the Qwirorment. 140 17.0 8NI CN THE MKNUnCTOTE CP ICH KB TRANSFCMERS .... 141 17.1 Requirements of the Regulations....................................141 17.2 Industry Structure, Production, and Sales .... 141 17.3 Substitutes for PCB Transformers................................ 142 17.4 Relative Prices of Non-KB Transformers.................... 149 17.5 Compliance coets............................................................... ISO 17.6 KBs Controlled by the Regulation................................151 17.7 Sumnary - Eccnanic Bipacts............................................1S2 17.B Cost Per Pound of PCBs Kept Fran the Qwirorrant. 152 18.0 SUMKBf.......................................................................................... 153 18.1 Transitional Cost Bipacts................................................153 18.2 Long 'Dam Oast Bipects....................................................153 18.3 Cost Per Pound of PCBs Kept from the Bivircnnent. 153 MfBBCfS
HONS 013209 vi
LIST CP TOMBS
4.1- 1 Eatimatad Nlaber of PCB Transformers in Service................
fas
24
5.1- 1 Swmery of KB Cooled Railroad Transformers in Service. ... 34
5.3- 1 Retrafill of PCB Railroad Transformer with Silicone........ 37
5.3- 2 coat of Retrofilling Railroad Tranafomara to Meet January 1, 1982 Limit of 6t PCBa: $21.99/gal................................................... 38
5.3- 3 Retxofill of Contaminated Silicone Filled Transformer.... 40
5.3- 4 Coat of Analysing Silicone Oil for the Presence of PCBa in Retzofilled Railroad Transformers................................................... 42
6.1- 1 Utility Reports of PCB Contamination of Oil Filled Trans formers with Ccncantrationa above 50 ppn....................................... 45
S.l-2 Transformer Manufacturer and Service Oonpaiy Reports of PCB Contamination of Oil Filled Transformers above 50 ppm .... 49
6.1- 3 Edison Elactric Institute Smeary of Contaminated Trans former Data Submitted by Electric Utilities............................... S2
6.1- 4 Edison Elactric Institute Suumry of Contaminated Traneformer Data Submitted by Transformer Ccnpaniae........................... 54
6.1- 5 Estimated Amounts of PCBa in Oil-Filled Transformers............ 57
6.3- 1 Used Transformer oil Available for Declaration....................... 62
6.3- 2 Eetineted apply of Transformer Oil Available for Recycling for Sale......................................................
63
6.3- 3 Coet of Disposal of Transformer Oil from small Utilities, Ttaaefoomr Repair Shops, and Other Sources.............................. 69
8.1- 1 Use of PCB-Coolad Electric Motors in Mining Machinery .... 75
1.3- 1 Ooet Inpect of Forced Retirement of PCB Continuous Miners . . 78
11.3*1 Cost of Retrofilling Beat Transfer Systems to Meet 50 ppm Limit on PCB Concentration.................................................................... 102
vii HONS 013210
13.1-
LIST CF TBEUB (Continued)
1 New Oil Usage and Mats Oil Availability for Recycling in 1975 .....................................................................................................
591
109
13.4- 1 Coat of Substituting COHEREX for Used Motor Oil in Rosl Oiling for Dust Control...................................................................... 11(
16.1- 1 Major Types and Uses of PCB Capacitors...................................... 137
17.2- 1 U.S. Transformer Manufacturers that Used PCBe After 1970. . . 143
17.4- 1Relative Transformer Prices ................................................................ 149
18.1-1 Transitional Cost Inpacts................................................................... 154
IB.2-1 long Term Cost Inpacts........................................................................... 157
18.3- 1 Economic Costs of the PCB Ban Regulation................................... 158
viii
HONS 013211
LIST CF FIGURES
Page
1.2-1
Section 6(e), Tootle Stfcetances control Act............................... 5
10.1- 1 Calculation of Nunter of Die-Casting Machines that Used PCB Based Hydraulic Fluids .............................................................. 89
13.1- 1 Distribution and Utilization of Haste Oil in the United States During 1970-71..........................................................................Ill
ix HONS 013212
1.0 INIKXUCriON
1.1 History of PCS Use
Commercial PCBs are manufactured by the direct chlorination of the chnical "biphenyl." The result of this reaction is a mixture of chlorinated biphenyl molecules that differ in the number and arrangement of chlorine atoms attached to the biphenyl rings. Die final product may contain between 211 and 681 chlorine by weight, depending on the mxnt of chlorine introduced to the reaction vessel. PCBs, therefore, are mixtures of various kinds of polychlorinated biphenyls.
Die first commercial production of PCBs in the United States was in 1929. Almost all of the PCBs that have been produced in the U.S. were manufactured by Monsanto Industrial Chemicals Company which marketed various mixtures under the trade runes Arcelor* 1016 and Arcelor* 12xx, with the last two digits denoting the average percent chlorine in the mixture. Die commercial PCBs varied from Aroclor* 1221 (similar in physical properties to a light oil) to Aroclor* 1268 (a waxy solid). Monsanto also usad PCBs in acme cosnercial products formulated for specific purposes, including certain types of Pydraul* hydraulic fluids, Dierminol* heat transfer fluids, Turbinol* compressor fluids, and Santovac* vacuum pimp fluids. In addition, Monsanto produced various mixtures of polychlorinated terphenyls (PCTs), all of which contained up to It PCBs as unintentional byproducts. Die PCTs were marketed under the trade name Aroclor* 54xx, with the final digits again denoting the average chlorine content. Die PCTs were also marketed as constituents of some pydraul* hydraulic fluids (Veraar, 1976a).*
PCBs in general were noted for their excellent chemical stobility, low solubility in water, and low price. Die various ccnmarcial
Veraar, Tnc., 1976a. PCBs in the United States; Industrial Use and &rvlrormental Distribution, Springfield, Va.: National Technical ' . Information service (OTIS PB 252-012/3HP), February, 1976.
1 HONS 013213
mixtures covered a wide range of viscosities, melting points, and boiling points and were used in a nurber of applications including as a plasticiser for plastics, paints, and caulking compounds; as a dielectric liquid in electrical transformers, motors, electromagnets, and capacitors; as a dye carrier in certain carbonless copy papers and printing inks; and as an additive to certain greases, lubricating oils, casting waxes, hydraulic fluids, heat transfer liquids, compressor liquids, and vacuum pump liquids. The various uses of PCBs were described in a report published in early 1976 (Versar, 1976a); estimated use of PCBs in each application and the present environmental distribution of the PCBs are summarized in Table 1.1-1.
PCTs were not generally recognized as being toxic until after the occurrence in 1968 of widespread poisoning in Japan caused by the accidental introduction of PCBs into cooking oil. The resulting acute syiptcns became known as "Yusho" disease, and it affected 1291 people*. In 1969, analytical procedures were developed that enabled PCBs to be Identified In concentrations of parts per million in environmental samples. In 1970, PCBs were identified as the contaminant in coho salmon frem Lake Michigan that had affected the reproduction rate of ccnmerdal mink fed contaminated fish. The mink reproductive problems had first been reported in 196S; identification of PCBs as the cause awaited developnent of satisfactory analytical procedures (Stendell, 1975).**
*R>r a comprehensive review and discussion of the literature describing the toxicity of PCBs and the details of the VUSHO incident, see: NI06H, Criteria for a Raccm--ndgrt Standard----- Occupational Exposure to Rjlvchlorinated Biphenyls (PCBs), vmshinqton, D.C.: U.S. cJoverrmant Printing Office, 77, pp.W9.
**Stendell, Bay C. 1975. 'Summary of Recent Information Regarding Effects of PCB's on Birds and Mnasals" in Conference Proceedings. national Conference on Polychlorinated Biphenyls, November 19-21,' 1975, Chicago. Illinois" Washington, D.C.: Officeof TOxic Substances, U.S. Environmental Protection Agency (Report No. EPR-560/6-75-004).
2 MONS 013214
In 1972, tensanto voluntarily restricted the sale of FCBe to the manufacture and maintenance of electrical transformers and capacitors and introduced the product Aroclor* 1016 as a more biodegradable dielectric liquid for use in capacitors (food, 1975).* Monsanto than contacted their customers to reccnmnd that heat transfer systmas containing VCB based Therminol* fluids be drained, flushed, and refilled with non-KB liquids and that hydraulic systems containing FCB based Pydraul* fluids be topped off as required with compatible non-PCB liquids (Versar, 1978, p. 75).**
following Monsanto's action in 1972, the only U.S. production of PCBs for "open* system use sms by Geneva Industries which manufactured about one million pounds of KB based heat transfer liquid between 1972 aid 1974 (VSrsar, 1978, p. 4). KBs were also imported after 1972 for use in maintaining electric motors in certain coal mining machines, and for use in some types of investment casting waxes.
1.2 Regulatory Action on KBs
In 1973, the U.S. food and Drug Administration (FDA) established temporary tolerances for KBs in food, and FDA surveillance resulted in the rejection of nuaerous lots of fish and occasional lots of chickens and eggs (FDA, 1973).*** By 1975, there was significant evidence of KBs in industrial effluents and in the environment, and reports of KB contaalnation were being featured in the non-tedmical press. On March 26,
*food, David (Monsanto). 1975. "Chlorinated Biphenyl Dielectrics, Iheir Utility and Potential Substitutes" in Oonfscsnce Proceedings, national
Conference on folychlorlnatsd Biphenyls, Ifcyafisr 19-zi. irn.
amaiffiiii !^B**-*-c- office of lbxlc Substances, Protection Agency (Report No. EPA-560/6-75-004)
pp. 317-322. Verier, Inc. 1978. Microeconomic Iaeacta of the Proposed *KB Ban
Regulations' (BA 5i0/,6-177-035). Springfield. Va.s National Hactsiical THtoSSnSTBervlce (WIIS PB 281-881/3NP). Mey, 1978. ***!GA. 1973. "Polychlorinated Biphenyls - Contamination of Animal reads, foods, and food Fadcaglng Materials," Federal Register, July 6, 1973. pp. 18096-18103.
3
HONS 013215
1976, Senator Gaylord Nelson of Wisconsin Introduced into the Senate wt amendment to the Tbxic Substances Control Act (TSCA) that required the eventual elimination of the use of ?CBs in the United States. This amendment was the basis of Section 6(e) of TSCA (Figure 1.2-1), and the eventual ban on the manufacture of PCBs became a legislated rsquirmaent on October 11, 1976, when TSCA was signed into law.
Concurrent with the consideration of the PCS amendment to TSCA, the EPA proposed toxic pollutant effluent standards for PCBs aider Section 307(a) of the Federal Hater Pollution Control Act (EPA, 1976).* ibis proposed regulation would have imposed severe limitations on PCB discharges by capacitor and transformer manufacturers who used PCBs. Following extensive hearings, the PCB effluent standard was promulgated on February 2, 1977 (EPA, 1977d).** The regulation required that all PCB manufacturers and those transformer manufacturers and capacitor manufacturers using PCBs eliminate PCBs fraa their effluent water by February 2, 1978. The one-year ccapliance deadline for manufacturers of electrical equipment was tstablishad to enable plants to phase out the use of PCBs, convert to substitutes, make appropriate technological or process changes, or take such other steps as necessary to achieve compliance.
Section 6(e) of the Tbxic Substances Oontrol Act (TSCA) required the n*A to regulate the narking and disposal of existing PCBs. The manufacture of PCBs and their handling and use in other than a totally enclosed manner was banned effective January 1, 1978. The act also completely banned the manufacture of PCBs after January 1, 1979, and their distribution in ccamerce effective July 1, 1979. Finally, the act authorised the EPA to grant exemptions and authorizations under certain conditions.
"iJPA. 1376. "Water Prograa - Proposed Tbxic Pollutant Effluent Standards for Polychlorinated Biphenyls," Federal Register, July 23, 1976, pp. 30468-30477.
**EPA. 1977d. "Proposed Tbxic Pollutant Effluent Standards for Polychlorinated Biphenyls (PCBs): Final Decision," Federal Raqister. February 2, 1977, pp. 6531-6555.
4 HONS 013216
Figure 1.2-1 Section 6(e), tteocic Substances Control Act
PUBLIC LAW 94-469--OCT. 11. 1976
90 STAT. 2025
() Polvchumikatck Uiriuxru.--(]J Within tix months after Rain.
Um pffitlirt data off l)ii* Ad (he Administrator shall pimnuli'alt
nilrt to--
(
(A) nraarribe methods for tha dif|**al off |*olycMoiijmted
bi}ilMv|i, and
'
( M) inquire polychlorinated biphenyl* to U marked with clear
and adequate warnings, and inutiaiiioni with rcsjwrt to tWir
processing, distrilmtion in ttmmwnt, wt, or diyjeMil or with
m|*eet Ivinyiimilitnaiiniutf suchactivities.
Krquimmnts pirwrilwd by rule# under Oils |njnph sliall lc t on-
riHieht wiili the m|inneHtt off |wnifra|>lw (2) and ft),
IdjM) Kurjit t jnnvkW under subparagraph (B), effective one
year after the effecti\e date off tbia Art no (N-raon may manufacture,
prwr**, or dim rilmt* in ronimemt or oae any i*>JytMonnatrd biphenyl
many manlier otIter (ban in a totally enclaved manner.
(B| Tlie Administrator may by ruk authorise tha manufacture.
lirMtoiiif, distribution in commerce or uaa (or any combination off
rOch activities) off any jiolythlorirmird biplwnyl in a manner other than
in a lotallv enrlqeed manner iff fle Administrator find? that such manu
facture. jutMYiistng, distribution in commerce. or use (or combination
off Such activities) will not prexenl an unreasonable risk off injury to
hcaHhorlhr environment.
*
t(') For llie jKirj>oae off this (Miiafrajdi. the lerui "totally enclosed manner** means any manner which will inmre that any esjawnre off
I*M*TkKMatSt.>**twl---*4
human (ring* or the environment to a polychlorinated biphenyl will
la- itvigniln-ani aa determined W the Administrator by rule.
|ft)(A) Knelt as provided in sub|iantgra)df (B) and ((.*)--
(ij no Ja-mm may ineouferturr any |>o)yc)ilorinsted biphenyl
after too years after the effertive date of this Art, and
*
(ii) no jarsun may pinrwws or distribute in commerce any |oly*
rhhirmafid ldplienyl after two and one-half years after such date
(H) Any jarson may lari it ion tlie Administrator for an exemption rrtifkHl hf from tlie reouiitments of *ub|tat-Mgmph (A), and the Administrator oeaiptMia.
may grant l*v rule such an exemption iff the Administrator find#
that--
(i) an unreasonable risk off injury to health or environment
wouldsk* result,and
(ii) pud faith efforts have l*e made to de\rtop a chemical
subatam-e which does not prr*e*m an uumtsonnhle nsk of injury
to healih or the environment and which may W suMituied for
such pqlyrhlorhMled biphenyl.
An exemption tranted under flits subparagraph shall W subject to T*nw tad such terms and ronditiona at the Administrator may pn*<-ril# and D-btHMM.
shall be in effect for such period (bat not more than one year from
the date U is printed! as tlie Administrator may prescribe.
((*) Suh|nraprai4i (A) shall not apply to the distribution in mm-
merre off any polychlorinated biphenyl iff such polychlorinated
biphenyl was sold for purposes other than male lie.fore two and one
half years after (lie dale off mart men* off this Act.
tt) Any rule under paragraph (1), (91(B). or (9)(B) shall lie
promulgated in arrordanr* with paragraphs (9), (9), and (4) of sub
station (cl. (A) This sultfrction doer not limit tie authority of the Attaints-
iraitir. umler any other provision of this Act or env oilier Feleral law.
to take action respecting any polychlorinated lupnenyl.
HONS 013217 5
Regulatory Implementation of the various requirement* of Section 6(e) of TSCA has occurred in several steps. EPA proposed regulations on the marking and disposal of PCBs on Hay 24, 1977 (EPA, 1977a),* and made available a support document (EPA, 1977c)** and a contractor's report on the estimated economic impacts of the proposed regulations (Versar, 1977).*** Written comments on the proposed rule were accepted by the EM and informal hearings were held during the period June 24-29, 1977. 4m final regulations were promulgated on February 17, 1978 (EPA, 1978a),**** and corrections were published on August 2, 1978 (EPA, 1978b).*****
The EPA held pdolic meetings on the retaining use ban provisions of Section 6(e) on July 15, 1977, in Washington, D.C., and on July 19, 1977, in Chicago, Illinois. Oi December 30, 1977, the EPA announced that it would not implement the ban on activities conducted in other ttwn a totally enclosed manner (Section 6(e)(2)) wtil after formal regulations were praeulgated (EPA, 1977b).****** These use ban regulations were proposed on June 7, 1978 (EPA, 1978e)******** At the sate time, the EPA
Is (PCBs), Toxic Substance nay 24, 1977, pp. 26564-26577, Disposal Regulations - Support lington, D.t": Office of lbxic Substances, U.S. Environmental Protection Agency, indated. ***Versar, Inc. 1977. Mictosconaeic Impacts of the Proposed Harking and Disposal BmqulaHons far PCBs Tm'SSfl/W-W-OlSl. Springfield, Virginia: National Technical Information Service (WflS PB 267-833/2MP), April, 1977. ****ffiA. 1978a. "Rolychlorinatad Biphenyls (PCBs), Disposal aid Marking.* Federal Register. February 17, 1978, pp. 7150-7164. *****BRA. 1978b. "Klychlorinatsd Biphenyls (PCB's), Addendum to Freaable end Corrections to Final Rile.* Federal Register. August 2, 1978, pp. 33918-33920. *****BPA. 1977b. *folyehlorinated Biphenyls (PCBs), Tbxic Substance control.* Federal Register. Dtcwber 30, 1977, p. 65264. *******EPA. 1978e. hfolychlorinated Biphenyls (PCB's), Manufacturing, Procesainq, Distribution in Commerce, and (Me Bans,* Federal Register, Jum 7, 1978, pp. 24802-24817.
6 MOMS 013218
made available a support document (CPA, 1978c)* and a contractor's report on the estimated economic impacts (Versar, 1978). In the preamble to the proposed regulation, the CPA asked for written ocmnents on specific technical aspects of the regulation, written consents were accepted imtil the start of the hearings which were held in Washington, O.C., fraa August 21 through September 1, 1978. Opportuiity for cross examination of the CPA econaaics contractor was granted to the Edison Electric Institute md the Electronic Industries Association on September 26, 1978, and reply consents on the proposed regulation were accepted for one week after that date.
Versar's previous report on the economic impact of the PCS Ban Regulations (Versar, 1978) was based on the proposed regulations and the data available in May 1978. EPA has since considered several hundred written main comments and reply comments and the information presented at ten days of informal hearings and has revised many of the details of the proposed regulations. Hie information presented to the EPA since the regulations were proposed has also significantly augmented the data available to Versar. The purpose of this report is to revise the economic analysis performed in May, 1978, to reflect the changes in the regulation mm3 to incorporate additional information (1) that has been made available to the EPA ae a result of the rulmnaking, and (2) that has been included in the rulmnaking record.
*EPA. 1978c. Office of Tbxic Substances. Support Docunei voluntary Environmental npact Statmnmtfoc Polychlorinated Biphenyls (PCBs) Manufacturing, Processing. Distribution in ; i&Tm Bain fcqulgaon (Section lie) of/KW: Washington, B.C.' U.S. fovlronmental Protection Agency. May 1978.
7 HONS 013219
2.0 METODC01XCY FOR BOMOUC IMPACT ANALYSIS CP THE PCB BAN REGULATIONS 2.1 General Approach Section 6(e) of the Ibxic Substances Control Act (TSCA)
established specific dates for the banning of activities involving the manufacture, processing, distribution in commerce, and use of PCBs. TSCA alao authorized the EPA to grant exemptions from the rule or to author ize specific activities that would otherwise be banned. These exemptions and authorizations may be granted only if the SPA makes a formal finding that the activities "do not present an unreasonable risk of injury to health or the environment."
If the EPA bad not promulgated the PCB ban regulations, the requirsmnts of TSCA could have taken full effect on the dates specified in the act. The effect of the discretionary actions that the BRA has tatan by promulgating the regulations is to reduce the economic impact of the legislated requirements in certain cases.
Since the EPA defined in the regulation those materials and aenufectured products that are subject to the legislated requirements, it is difficult to separate the economic consequences of the act from the economic impact of the regulation. Calculation of total eooncaic impacts is further complicated by the compliance actions taken by industry in anticipation of the regulations.
This analysis is limited to impacts expected to result from the PCB ban regulations. These impacts are the incremental changes from a base condition essuaed to be the industry practices in 1975 as modified by the PCB effluent standards and by the PCB Disposal and Harking Regulations. Increased industry costa caused by the use of substitutes for PCBs and the resulting product development oosts or the costs of discontinuing certain products are the basis of the calculation of cost impacts. Each affected
8
HONS 013220
industry is considered separately, and long-term economic impacts are calculated by predicting long-term practices and comparing the resulting costs to those that would have been Incurred under the base period conditions. Transitional costs are also calculated where there will be a significant capital investment required to comply with the ban regulations or where there will be a prolonged period of adjustment of industrial practices. The economic impact analysis is limited to directly affected industries and to their suppliers and customers. The analysis does not evaluate (1) minor secondary impacts and ripple effects of the regulations, (2) benefits to health or the environment from the ban, or (3) the extent to thich exemptions that may be granted by the EPA will reduce these costs.
In general, the methodology used to estimate the economic impacts of the PCB Ban Regulations is the same as that used in previously published studies of the economic impacts of the Proposed PCB Ban Regulations (Versar, 1978), of the Proposed PCB Marking and Disposal Regulations (Verier, 1977), and of the Proposed PCB Effluent Standards (Jack Faucett Associates, 1976).* All of the cited economic impact studies, including this one, have been limited to an evaluation of the costs of the regulations.
*Jack Faucett Associates, Inc. 1976. Economic Analysis of Proposed Toxic Pollutant Effluent Standards for Polychlorinated Biphenyls: Tnnsfoaner, Capacitor, and W Manufacturers (EPA 230/1-76-008), Washington, D.C.: office of Hater Planning and Standards, U.S. Biviromental Protection Agency. October 1976.
9 HONS 013221
2.2 Data Base for Economic Impact Analysis Oils report's analysis of the economic impacts of the final KB
Ban Regulations is based on the following data: Published reports as referenced in the Official lacori of rulemaking including the previous Versar report "Microeconomic Impacts of the Proposed 'PCB Ban Regulations'* (Vtersar, 197S). e Written comments on the Proposed PCB Ban Regulations received by EPA and made part of the official record of rulemaking. e Oral comments presented at the public hearings on the pi npimail rule (August 21 through September 1, 1979). Verbatim transcripts of these hearings are part of the official rtcord of rulemaking. e Reply comments on the proposed rule received by EPA subsequent to August 21, 1978, and made pert of the official record. e Information on the sampling protocols used by utilities in selecting oil filled transformers to be tested for the p'lmnce of PCBs. This information was obtained by Versar through phone conversations with representatives of companies that [casantsfl data on the extant of PCB contamination of transformer oil in their written or oral comments on the proposed regulation.
10 MOMS 0i32*2
3.0 DWCT OF BAN ON THE DISTRIBUTION OF PCB CAPACITORS AND EQUIPMENT
3.1 Prsssnt Status
3.1.1 PCB Capacitors
The itN of PCBs in aoall capacitors has been gradually phased out over tha past two years. Although several manufacturers ware using PCBs in at laaat a portion of their 1978 production of small capacitors, moat capacitors manufactured during 1978 do not use PCBs. Most snail capacitors are used in tha manufacture of new appliances and lighting fixtures; the use of capacitors as repair parts accounts for a comparatively aaall parcantaga of the total demand for these items.
Baerson (kiiet tool Company estimated that it would have an inventory of approximately 30,000 PCB capacitors as of January 1, 1979, and that this inventory would represent an Investment of $120,000.* Mvance Transformer estimated that they might have 100,000 PCB capacitors in inventory on January 1, 1979, that were not built into ballasts or other equipment.** It is not possible to extrapolate this data to an estimate of tha total inventories of capacitors that may remain unused on July 1, 1979. If each company normally carries a two-month inventory of capacitors and if only tan percent of these contained PCBs on January 1, the value of snail PCB capacitors In the Inventory of equipment manufacturers would have bean ana sixtieth of annual capacitor sales of $95 million, or approximately $1.5 million on January 1, 1979. The nuiber of PCB capacitors remaining in inventory on July 1, 1979, will probably depenl on tha policies of various coapaniaa regarding tha maintenance of spare parts for obsolete equipaent. There will apparently be sufficient time available for manufacturers to use their inventories of PCB capacitors that are components of presently manufactured products.
Letter from George Hakin (Bnerson Quiet Kool Company) to EPA, dated August 2, 1978. **Oral comamnts of Ernest Freegard (Advance Transformer Company) at the Bearings on tha PCB Ban Regulation, August 23, 1978.
U mows 013ii3
3.1.2 PCB Equipment
>t>st capacitors used in appliances and lighting fixtures manufactured during 1978 do not contain PCB6. There is no easy way to distinguish which appliances do contain PCB capacitors. The provisions of the PCB Disposal and Markina Regulations that require that non-PCB capacitors and non-PCB fluorescent light ballasts be distinguishable from PCB units did not beccme effective until July 1, 1978 (EPA, 1978a). The regulations that require equipnent containing PCB capacitors be so Mikwl apply only to equipnent manufactured after December 31, 1978 (EPA, 1978b).
There are also considerable rambers of PCB capacitors presently in inventory in electrical subassemblies such as fluorescent light ballasts. According to Mr. Ray Clark, the manufacturers of fluorescent light fixtures normally carry a 60-day supply of ballasts in inventory, and he estimated that about one million of the seven million ballasts in their inventories on January 1, 1979, would contain PCB capacitors.* Not ail of these ballasts are used within sixty days. Manufacturers of lighting fixtures also maintain inventories of the less camon and obsolete ballasts for use as replacement parts in misting fixtures. Seme of these ballasts may remain in inventory for as long as thirty years.** According to Mr. Freegard, the percentage of production of ballasts by Advance Transformer Oompany that involves the slow moving types is less than ten percent of the fluorescent light ballasts and perhaps slightly more than ten percent of the ballasts for high intensity discharge (mercury arc and sodium arc) lighting ballasts.***
*Oral comments of N. Ray Clark (universal Manufacturing Corporation) at the bearings on the PCB Ban Regulation, August 28, 1978.
**Oral consents of Herbert Etowe (Electronic Industries Association) at the hearings on the PCB Ban Regulation, August 23, 1978.
***Oral cements of Ernest Freegard (Advance Transformer Company) at the . hearings on the PCB Ban Regulation, August 23, 1978.
12 MOhS 013224
Electrical equipment containing PCB capacitors may pass through several hands prior to its sale to the final consumer. For instance, air conditioning units are distributed by the manufacturer to retailers under a conditional sales agreement which allows the units to be returned to the Manufacturer if they are not sold during the suimer season. The unsold units are then stored during the winter and sent to retailers the following spring. Anana Refrigeration stated that "There is customarily a large Mount of carry-over merchandise left over In the distribution channel after the primacy selling season has ended. It is not unccmmon for a dealer or distributor to have an inventory containing air conditioning aquipssnt which is three to four years old."*
Microwave ovens do not have the seasonal sales pattern of air conditioning units, but inventory carry-over is still significant. Mr. Nelnoricfc of the Association of Home Appliance Manufacturers calculated the rate of tales of each year's production to be 54% per year based on a total durable goods inventory equal to 72% of annual shifronts. Carry-over frcm the production years 1975 through 1977 would therefore be expected to be 239,000 wits on December 31, 1979, and 120,000 units on June 1, 1979.** Inventories of lighting ballasts and fixtures might be expected to turn over more rapidly. However, many of these items are manufactured as ccaponents of equipment such as subway cars and highway luminaries which will be classified as PCB equipment and which have longer lead times prior to final sale to the user.
*"Oomnents of Mans Refrigeration, Inc.......... ' submitted to EPA as an attactmmnt to a letter dated August 4, 1978, from Arthur Berold of Nsfaetar and Chamberlain.
*"better frcm J.T. Meiseorlck (Association of Home Appliance Manufacturers) to Steven Rosenthal (Covington and Burling) dated Septosber 7, 1978 (Appendix III). This letter was submitted to the EPA as an attachment to a letter from Mr. Rosenthal dated September 12, 1978.
13 MONS 013225
The manufacture of appliances using PCB capacitors is not bmnmd until July 1, 1979, but any such appliances manufactured during 1979 must have the PCB equipnent label applied. Therefore, it will be easier to Identify equipment containing PCB capacitors that was Manufactured during 1979 than that manufactured in 1977 and 1978.
3.2 Requirements of the Regulation
Sale of new PCB capacitors: The sale of new PCB capacitors is banned after June 30, 19^9, unless epa grants a specific exemption fraa this "distribution in oamnerce" ben requirement.
Manufacture of PCB equipment: The use of PCB capacitors in the manufacture of new equipment such as television sets, microwave ovens, and fluorescent light ballasts and fixtures is considered a totally enclosed processing of PCBs. since all processing is banned after June 30, 1979, PCB capacitors and aubassasblies containing PCB capacitors will have to be used by June 30 unless a petition for an exemption from this processing ban requirement ia granted by the EPA.
Sale of new PCB equipment! The sale of new PCB equipment is bemad after dune 3b, 1979, unless EPA grants a specific exemption from this "distribution in ccmmeree" ban requirmaent.
fxssgitlon requirements! EPA has not yet stated the conditions under which petitions for exemptions from these ban provisions will be accepted or the conditions under which exceptions will be grafted except to state that any exemptions granted will be for a period of only one year. EPA has suggested that exemptions may be granted only under those conditions (1) that will result in no significant threat to health or the environment and (2) where a good faith effort to develop substitutes for the PCB capacitors has been demonstrated.
3.3 Economic Impact of the Regulation
3.3.1 PCB Capacitors
The regulation bans the distribution in ccmmerce after July 1, 1979, of PCB capacitors unless the EPA grants exemptions from this
14 HONS 0131*6
rsquirmnent. If the EPA grants a complete exemption frai this requlrmmnt, there could be sero economic impact. If the EPA does not grant any exemptions, the effect of the regulation would be to require that all mwll PCB capacitors be sold to the ultimate users by July 1, 1979, and that any FCB capacitors remaining in the distribution channels at that time be disposed of in accordance with the disposal requirements.
The ecoraaic Impacts resulting from the ban on 'distribution in
comerce' will depend on the extent to which EPA grants exceptions. The
nuaber of individual maall capacitors maintained in inventory as spare
parts is not known but is probably no more than a few percent of one year's
production of PCBs. Many of these capacitors might be relatively old,
having bean left over from production nna of unusual types and than kept
aa spares to replace wits that fail in service. A rough estimate of the
value of maall capacitors remaining in inventory on July 1, 1979, would be
that the parts inventory would equal two percent of annual production of
mil capacitors and that one half of these ai^it still be PCBs. The value
of maall Industrial capacitors was previously reported to be $94.5 million
in 1976 (Versar, 1978, pp. 97-98). The manufactured cost of remaining
inventories of PCB capacitors would therefore be (2% x 1/2 PCBs x $94.5
million*) $1 million. The economic loss resulting frcn a ban on the sale
of these capacitors might be larger then this amount if equipaent that is
otherwise usable must be scrapped because no replacement capacitors are
available. However, no information is available to support an estimate of
the resulting coats.
.
It is anticipated that additional information will be made available to EPA in petitions for exemptions from the ban on side of capacitors. This information will enable EPA to more accurately estimate economic impacts of their decisions on the exemption petitions.
15 HONS 013227
3.3.2 PCB Equipment
Compliance with this regulation would require that all inventories of subassemblies, appliances, and lighting fixtures containing capacitors on July 1, 1979, be examined to determine whether any of the capacitors contain FCBs. Any PCB capacitors that are found will have to be replaced with non-PCB capacitors before the subassmsbly, appliance, or lighting fixture can be sold.
A ban on the distribution in ccenerce of equipment containing PCB capacitors will have a greater impact than a ban on the.sale of capacitors because the equipment ban will involve more items and because it will be' sere difficult to identify the banned items. The major cost of the regulation would result from the efforts to identify which equipment contains the PCB capacitors so that they could be replaced with non-PCB units.
A rough estimate of the total rxnber of items in inventory that
will.have to be checked to determine whether they contain PCB capacitors
can be calculated from information presented by the industry. Aerovox
reportedly has about 24% of the market for small industrial capacitors
(Versar, 1978, p. 103) and has stated that their production rate is 80,000
wits per day.* if the average wit cost of Aerovox production is
.
representative of the Industry, this would imply an annual production of
(80,000 units per day x 250 days/0.24 market share-) 83.3 million
capeciton per year. The average cost would therefore be ($94.5
aillion/B3.3 million wits) - $1.13 per capacitor. If dealer inventories
equal 704 of annual shipments, this implies that there will be (83.3
million wits per year x .7 ) 58.3 million separate pieces of equipaant
containing small capacitors in inventory at any given time.
The inventory model suggested by Hr. weiseorick can be modified to calculate the fraction of wits in inventory on July 1, 1979, that will
*Latter from Clifford H. Tuttle (Aerovox Industries, Inc.) to EPA dated August 15, 1978.
16 HONS 0132*8
contain PCB capacitors. This modal assusss that production of capacitors is constant at P0 units per year, that the ratio of inventory to sales is equal to 0.71, and that the probability of sale of any given item is not proportional to the time it has been in inventory. Mr. Weizeoridc stated the relationship between inventory, production, and sales by the differential equation
where i - inventory at time t P production rate, units per year S sales rate, units per year
and solved this equation for the condition t < 0, P " 0 t > 1, P - 0 0<t < 1, P-P However, starting at about the beginning of 1977, some of the
production of capacitors was of non-PCB units, and by the end of 1978, all
of the capacitors being produced were non-PCB types, if it is emiuaed 'that
the proportion of PCB capacitors used by equipnent manufacturers decreased linearly from 100% PCB on January 1, 1977, to 0% on December 31, 1978, the
production rate of equipment containing PCB capacitors during these two
years could be expressed by the equation:
P - PQ <1 - , t - 0 to 2
.
where P0 constant production rate using all capacitors P production rate using PCB capacitors t * years after January 1, 1977.
17 HONS 013229
The differential equation for the inventory of PCB items during these two years would then be expressed as
&-P-S and since: s * 771
(1) (3)
and P - PQ (1 - |),
thm at " fo i1 ~ I
77T from t 0 to t * 2
In linear form, this equation can be written:
(2) (4)
di + 77T - P
dt
(5)
which has the solution
i - .71 Pc [l - | + ill (x . . -t/.7l)J
(6)
where i .71 P at t 0
Evaluating for the inventory at the end of 1978 (i.e., t 2), i .334, or 33.41 of equipment in inventory on January 1, 1979, contained PCB capacitors.
Aeauning that no PCB equipment was made after January 1, 1979, the differential aquation for the inventory would be written
di , ,, at ' " S
(7)
Since S
this can le written as
di +
dt 0
which has the solution t
^o8 771 for i * iQ at t
(8) (9)
18 HONS 013230
On July 1, 1979, (t 1/2), the inventory of PCB items, will therefore be equal to .49 of the Initial inventory at the beginning of the year, or equal to (.49 x .334 x P ) IS.4% of the total inventory.
Based on these calculations, the inventory of equipment containing capacitors on July 1, 1979, will consist of 56.3 million items, of which 9.56 million will contain PCB capacitors. These capacitors will have an estimated manufacturers' sales price of (9.56 million capacitors at $1.13 " ) $10.85 millon. These estimates will be higher than the actual inventory of PCB capacitors to the extent that dealers succeed in selling their oldest stock first.
If the EPA does not grant exemptions from the ban on the sale of equipment containing PCB capacitors, the dealers may have to open many of the 58.3 million items to determine which items contain PCB capacitors, and then replace the capacitors in 9.56 million items with non-FCB capacitors. Major cost items for the inspection program will be labor, customer discounts required to offset the damage to the packing cartons, and supervision, in most instances, the equipment will have to be partially disassembled in order to expose the capacitor. Hr. Welzeorick suggested a coat of $40 per unit based on $20 labor, $10 adninistrative cost, and $10 reduced value caused by damage. This implies a total pragran cost of $2.33 billion to Inspect all 58.3 million items. It is possible that at least some of the units could be identified as not containing PCB cspacitors by chscklng sach wit serial rubbering and information supplied by the manufacturer. However, even if the labor and administrative expenses could be cut by a factor of three to an average of $10 per unit by identifying serial nwbers and therefore not having to disassemble the units, the inspection pcograi would still cost in excess of $1 billion.
The eecond portion of this program will consist of replacing the capacitors in the 9.56 million pieces of equipment that are found to contain PCB capacitors. Mr. Heixeorick suggested a rework cost of $75 per wit implying a total coat of $717 million. This is undoubtedly high, since many of the suspect ltmes are fluorescent light fixtures that retail for about $10 par wit. There is not sufficient information to estimate
19 MOMS 013231
the proportion of the 58.3 million units in inventory that would be sold a distress prices before July 1, 1979, or scrapped rather than being inspected. However, it must be concluded that the total inspection ooats, rework costs, and losses due to forced sales could easily exceed $1 billion.
The calculated costs resulting from the ban on distribution in commerce of equipment containing PCB capacitors is adnittedly based on a rumber of assvnptiona. However, it is anticipated that additional information on the economic impacts will be presented to the EFA by the manufacturers and distributors of this equipment together with their petitions for exemptions from these requirements.
The final cost impact of these regulations will result from the requirement that impacted manufacturers and distributors of PCB equipment apply for exemptions. These petitions will require that detailed coat estimates be prepared which in turn will require the participation of corporate marketing, accounting, and legal staff. Each petition would likely require anywhere from 3 to 30 man days of effort to prepare, and coat a total of $1,000 to $10,000 based on toted burdened labor at $42 per hour. EPA has not yet announced its policy on accepting class action petitions. If each manufacturer and retailer is required to apply separately, perhaps 1,000 to 10,000 petitions will be filed, at a total cost of about $10 million.
3.4 PCBs Controlled by the Regulation "total oonsueption of PCBs by the capacitor manufacturing industry
during 1975 was about 21 million pounds, of which 55% was used in maall industrial and appliance capacitors (Versar 1976a, p. 6). If total production of these smell capacitors was 83.3 million units, the average capacitor contained (21 million x .55/83.3 million ) 0.14 pounds of PCBs.
20 HOBS 0132
Th ban on the (ales of spare capacitors would affect $1 Million worth of capacitors containing a total of ($1 million x 0.14 lb FCB per wlt/$1.13 per unit ) 124,000 lb PCBs. The capacitors removed froa equipaent in Inventory would contain (9.56 million wits x 0.14 lb FCB per wit - ) 1,340,000 lb PCBs.
It is assqaad that the spare capacitors are still owned by manufacturers of FCB equipment and will.have to be disposed of in approved cheatcal waste landfills. The capacitors in ecpiipmant are assumed to be in dtalers inventories, and these may be disposed of in mwicipal trash.
The failure rate of mall capacitors is about 0.2t par year, of which 10% leak on failure.* If the average appliance lasts twenty yean, each cqpacitor would have a (20 years x 0.2% probability of failure per year - ) 4% probability of failure.
Die effect of the regulation will be to prevent the loea of FCBs to the nvironaent by capacitors that fail and leak in service. If it is assumed that all the FCBs in leaking capacitors enter the environment, the affect of the regulation would ha to reduce the loss of PCBs from equipaent by (1,340,000 pounds FCBs x 4% fail x 10% leak " ) 5,360 pounds of FCBs. The rest of the FCBs in capacitors installed in equipment will and up in municipal landfills Whether they are removed in 1979 or when the equipaent fails.
All of the spare capacitors will have to be disposed of in chsaical waste landfills, thereby preventing the entry into the envlranaent of (124,000 pounds x 4% fail x 10% leak - ) 496 pouids FCBs that would have occurred had these capacitors been used.
Latter frae George Hakin (Bnerson Quiet tool Co.) to EPA dated September 6, 1978.
21 HONS 013233
Municipal landfills are not as safe a repository for PCBe as are approved chemical waste landfills. However, PCBs are rather iaanbile in material with high organic content and would not be expected to leach out of wnicipal waste if present in low concentrations. No information is available on which any estimate can be made as to the fraction of the PCBa frcm intact capacitors that are expected to leach frcm nnicipal landfills
3.S Saaaary - Economic Impacts
Inventory losses: Spare capacitors
$1 million
This coat will be reduced significantly or eliminatead if EPA grants exemptions frcm the 'distribution in commerce* ban.
Inspection and rework: PCS Equipment $1 billion
This coat will be reduced significantly or eliminated if EPA grants exceptions from the 'distribution in ccanerce* ban.
Petition costs:
$10 million*
3.6 Post Par Pound of PCBs Kept Prom the Bmrorwcnt
Spere capacitors:
- $2,000 per pound PCS
This coat will be reduced significantly or eliminated if EPA grants exemptions frcm the "distribution in ocasatcce* ban.
Cspadtcrs in equipment:
" S187'000 p pound PCS
This coat will be reduced significantly or eliminated if EPA grants exemptions frcm the `distribution in commerce" ban.
*"ay be significantly reduced if EPA accepts class action petitions for exemptions to the ban on 'distribution in commerce.*
22 HONS 013234
4.0 IMPACTS OK USERS OP ASKAREL TRANSFORMERS
4.1 Present Status
In calculating the economic lngact of the PCB Disposal and forking Regulations, versar estimated that there are about 140.000 treefotaers presently in service that were manufactured as PCB (askarel) transformers (Versar, 1977). These transformers were originally filled with a coolant liquid that contained froa 60t to 100% PCBs. Although over 100 of these transferrers have been retrofilled with silicone or hydrocarbon coolant liquids, none of thea have been sufficiently daeontaadnatad so that the concentration of residual FCBa is below TOO *
ApproxilMtely 1000 of the askarel transformers are installed on railway locomotives and ccsmuter cars (Versar 1978, p. 19). These units are addressed specifically by tha PCB ban regulations, and the impact of tha ragulationa on theae wits is dlscusaad in Chapter 5. Of the roiaining wits, moat are pad mowtsd distribution and power transformers located in buildings and in electric generating stations, with a substantial nwber of amkarel precipitator transformers being momted on stacks. It is eatiamted that askarel transfonsera each contain an average of 2,500 pounds of PCB. The distribution of ownarahip of these askarel transformers was previously estimated to be as described in Table 4.1-1. No additional information on tha ownarahip of askarel transformers was presented in the written or oral ccmnanta subeitted to ERA aftsr tha PCB Ban Regulations were proposed.
%cloaure with letter from Terry Michaud (Dow Corning Corp.) to EPA dated August 1, 1978.
I
23
HONS 013235
I
L
Table 4.1-1*
Estimated Umber of PCB Transformers in Service
Category of User
Number of units
PCB Content-Pounds
Utilities
42,000
105,000,000
Industrial and Commercial
97,000
191,000,000
Pailroad
1,000
4,000,000
Source: Versar, 1978, p. 19.
The PCB Ban Regulations define askarel transformers as being any
transformers that are filled with a liquid containing PCBs in
concentrations exceeding 500 ppm. This chapter discusses the iapect of the
regulation on transformers that were originally filled with a PCB based
dielectric fluid. Chapter 6 discusses the inpact of the regulation on
those transformers that were originally filled with mineral oil but which
have since become contaminated with PCBs in concentrations above 500 ppa.
4.2 Requirements of the Regulation
Rebuilding and major maintenance: The regulations forbid the removal or the core and coils from the transformer. As a result, any significant electrical problem involving the windings of an askanel transformer will result in the'vnit being ecrepped. However, retrofilling a PCB transformer aeveral times with a nen-PCB liquid may reduce the residual concentration of PCBs to below 500 ppm. The ban on rebuilding does not apply to such decontaminated transformers.
Minor maintenance: There are no restrictions on the performance oi maintenance ttiat do not require removal of the coils. After July 1, 1979, transformer service companies cannot sell used or reclaimed askarel unless they have petitioned for an exampticn from the provisions of the regulation which ban the processing of PCBs prior to their distribution in commerce.
24 HONS 01323*
Reclaiming PCB askareli After June 30, 1979, PCBs may be reclained for reuse only by those who hove petitioned the EM and been granted tun exemption from the "processing1' bans.
Storage of PCB askarel Storage prior to use or resale must be in a specially marked area which meets the requirements established by the disposal regulations.
Disposal of failed transformers and PCB based askarel; No change from the previously promulgated Disposal and Harking Regulations.
Retroflll with non-PCB fluid; Authorized without restriction. Tbe retrofilled transformer-oust continue to be considered a PCB transformer, until the liquid has been tested at least three
months after the transformer was returned to service and found to contain less than 500 ppm PCBs. The transformer is then classified as a PCB contaminated transformer.
4.3 Economic Impact of the Regulation
Foregone savings from rebuilding
Askarel transformers have a normal service life of 30 to 40 years or more (Versar 1978, p. 7). Premature failure can occur as the result of electrical breakdown of the insulation or distortion of the coils caused by severe overload conditions. Normal industrial practice has been to rebuild failed askarel transformers by removing the core and coils, burning off the coils, and rewinding the coils using new wire on the original core. This repair normally costs about 604 of the price of a new transformer, and the repairs take about 254 as long as normal delivery of a new mlt.* This rebuilding service is offered by both the original manufacturers of the transformers and by approximately 300 small transformer service companies.**
Based on an average price of $20,000 per new transformer (Versar 1978, p. 20), the ban on rebuilding askarel transformers will result in foregone savings of ($20,000 x (1-604) - ) $8,000 per transformer, in addition, the ban will increase the time required to restore service from
Oral comments of Hr. Lynwood Holley (American Electric Apparatus Repair Corporation) at the hearings on the PCB Ban Regulations, Au^ist 28, 1978. **0ral comments of Robert Santamn (Sancban Electric Company) at the hearings on the PCB Ban Regulations, August 28, 1978.
25
HONS 013237
the present one to two month* to six months or more, depending on the availabilty of a satisfactory new transformer*. The out-of-service time might even be longer than would be expected based on past practices because the ban on the manufacture of new askarel transformers will require that each installation of existing askarel transformer* be redesigned when the transformer fails and must be replaced. Adequate replacement transformers ere usually available in s rxnfoer of designs including oil-filled transformers with protective vaults and sprinklers, high firs point liquid-filled transformers, and various types of dry transformers. However, none of these designs are direct replacements for existing askarel transformers, so a certain mount of engineering time must be ***** to the normal delivery time for a new ixiit.
An active market in used askarel transformers axistsd in the past, but that market has declined over the past year due to uncertainties shout the restrictions that SPA wes expected to impose on the use of these ixtits. The PCB ben regulations do not affect the recale and reuse of eskarel transformers by users, and units removed fran service because of changes in service damsnrts might be made available as replacement units for acme of the failed askarel transformers. However, the risk of a spill occuring during transport of an askarel transformer and the high potential liability incurred by any spill of PCBa will probably limit any market in used askarel transformers.
Hot enough information is available to estimate the proportion of aakarel transformers that would have been scrapped due to obsolescence rather than due to electrical failure! most existing askarel trmfonaers have not been in service long enough for either aging or changing service dwmnds to be significant. Assuming as an example that frcm one third to two thirds of the existing askarel transformers would have been rebuilt if it were not for the ben on rebuilding, the total foregone savings would be $8,000 par ixiit x 1/3 to 2/3 of the 140,000 units in service (Versar, 1978, pg. 21), or a total of $373 million to $747 million over the next 40 years.
Letter frcm Robert L. Sendaen (Electrical Apparatus Service Association, Inc.) to EM (KB Ban Regulation Hearing Record), Undated.
26 HONS 013238
These foregone swings will not be distributed evenly over the next 40 years because present failure rates of asKarel transformers are relatively low. the failure rate is likely to Increase as the average age of the transformers increases. It was previously estimated that approximately 80,000 gallons of PCBe were used in the repair of askarel transformers in 1974 (Versar, 1976a). this is enough PCS to fill 335 transformers with an average capacity of 240 gallons of liquid (Versar 1978, p. 21). Many transformer service companies have also used reclaimed askarel in rebuilt transformers, so the actual number of transformers rebuilt nay be three to four times the number calculated frcm data on the use of new askarel (approximately 1200 per year). The mount of business lost to the transformer rebuilding industry due to the ban on the rebuilding of askarel transformers might be as much as (1200 transformers par year x $12,000 per unit ) $14.4 million per year. The transformer manufacturers would supply new taiits to replace those not rebuilt at an avaraga coat of $20,000, so Increased costa due to the regulation may be about (1200 units x $8,000 -) $9.6 million per year. Increased labor requirasmnts by tha manufacturers are expected to offset any job losses by the repair shops, and in fact little unemployment is expected in the transformer service industry because nearly all of the 300 companies that aervice askarel transformers also service oil-filled transformers. Since about 97% of large, ped mountedi liquid-filled transformers contain mineral oil, tha ban on the rebuilding of askarel transformers should have a relatively moall impact on tha level of transformer repair business.
Lost service time
The delay in replacing failed askarel transformers nitwit increase in seme cases frcm the present four weeks required to rebuild a wit to aa much as six months (Versar 1978, p. 21). This delay could have eerious econcmic impacts on any industrial plant that was dependent on a ingle trwiaformer for Its power. Rental wits might be available, but at a higher cost to the plant. The previous estimate of increased rental
27
MQNS 013239
costs for temporary replacement transformers mas $2,380,000 per year starting In 1979 (Versar, 1978). tfo additional data were submitted to the EPA in written or oral comments on the proposed regulation that would support any revision of this estimate.
Limitations on sale of reclaimed aakarel
The regulations do not impose any restrictions on the processing of PCB baaed aslcarel by the owner of a transformer or by a service cospwiy that returns the askarel to transformers having the sene ouster. Therefore, there will be no restrictions on the present maintenance practice of periodically filtering the aslcarel in operating transformers to reduce the moisture content and improve its electrical properties. However, after June 30, 1979, sale of PCBs will be allowed only if the owner has petitioned the EPA for and been granted an exemption frcm the ban on the distribution in ccaraerce of PCBs. If the EPA does not grant exceptions, there will be a lade of available PCBs to top off aslcarel transformers that may develop small leaks and to replace the PCBs absorbed by the filtering material tfcen aakarel is routinely filtered. However, since it is technically feasible to dilute aslcarel with various solvents. Including trichlotobenxene, KTBopm, and Iralec*, without damaging its electrical properties, there may be little economic impact caused by the ban on sale of new and reclaimed PCBs. It should be noted that PCBs frcm PCS tranformers that have been disposed of or are designated for disposal must be incinerated and therefore are not available for recycle or reuse.
Disposal of failed transformers and aslcarel liquids
The PCB Ban Regulations do not change the requiranents previously Imposed by the PCB Disposal and Marking Regulations in this area (EPA, 1978a), and therefore there are no additional economic impacts.
Retroflll with non-PCB fluid
The PCB Ban Regulations clarify the conditions older which a retrofllled transformer may be considered to be in the sane class as oil-
28 MOWS 0132*0
filled trmbtMn Cor purposes of servicing and disposal. However, the regulations do not establish any limitations on retrofilling. Therefore, the effect of the regulations may be to reduce servicing problems when make-up askarel is no longer available and to reduce eventual disposal costs in seme cases.
Ban on sale of PCBs
Effective July 1, 1979, neither unused PCBs nor- reclaimed PCB based aekarel will be allowed to be sold unless the seller has petitioned for and been granted an exemption by the EPA from the "distribution in coanerce* ban. If the EPA does not grant exemptions, there will be a lack of available PCBs to replace askarels lost through small leaks or to replace the PCBs absorbed by the filtering material when askarel is routinely filtered. However, since it is technically feasible to dilute askarel with various solvents, including trichlorobenzene, RTEhpS, and Iralec*, without damaging its electrical properties*, there may be little economic inpact caused by the ban on the sale of new and reclaimed PCBs.
Ban on processing PCBs for sale
The Tbxic Substances Control Act defines the processing of a chmaical as "the preparation of a chemical substance or mixture, after its manufacture, for distribution in canmerce..." (Section 3(10)). Therefore, activities with PCBs that do not involve its sale are not considered to be "processing" as defined by the Act, and such activities performed for the purposes of maintaining transformers in other than a "totally enclosed manner" are specifically authorized by the regulation until July 1, 1984. This means that there are no restrictions on the filtering or other handling of askarel unless there is a change in the ownership of PCBs. Transformer askarel can continue to be tested and maintained by either the owner of the transformer or by a service company, but no PCBs can be added to the transformer except those that were owed by the owner of the
*01mstad,~J. (1977) "Ccnments and Recoanendations on Makeup Fluid for Askarel Transformers", Waukesha, WI.: RTE Corporation, November 15, 1977. (Submitted to the PCB Regulation Hearing Record as an attachment to RTE Corporation "Main Canments").
29
MONS 013241
transformer no later than 30 days after the effective date of the regulation. In addition, "processing" and "distribution in cornerce" for purposes of disposal are specifically authorized by the regulation.
Hie only significant inpact of this provision will be to ban the salvaging of used PCBs by transformer service companies for use in maintenance of other transformers. However, the major use of such reclaimed askarels has been in rebuilt transformers, and the rebuilding of askarel transformers is being specifically banned. The economic impacts of the ban on "processing* PCB based askareis have been included in the estimated cost of the ban on rebuilding askarel transformers.
Disposal of failed transformers and askarel liquids
Hie PCB Ban Regulations do not change the requirements previously imposed by the PCB Disposal and Harking Regulations in this area (EPA, 1978a), and therefore there are no additional economic impacts.
Betroflll with non-PCB fluid
Hie PCB Ban Regulations clarify the conditions under which a retrofilled transformer may be considered to be in the same class as oil-filled transformers for purposes of servicing and disposal. Hie regulations do not establish any limitations on retrofilling. Hie effect of retrofilling may be to reduce servicing problems when make-up askarel is no longer available and to reduce eventual disposal costs in some cases. Hie ban regulations impose no economic costs relative to retrofilling of askarel transformers.
4.4 PCBs Controlled by the Regulation
Hie ban on rebuilding askarel transformers will eliminate the loss of PCBs to the atmosphere that occurs when a transformer is baked-out prior to removal of the coils. There is no information available on the PCB loeses that occur during this process. However, if total loeses of PCBs during rebuilding of an askarel transformer were controlled to one to ten pounds per unit, the regulation would reduce the entry of PCBs into the environment by (1 to 10 lbs per unit x 1/3 to 2/3 of 139,000 units * ) 47,000 to 925,000 lbs.
30 HONS 013242
The ban on the sale of PCBs should accelerate the retirement of aakarel transformers, but there is not sufficient information available to estimate the effect this will have on the amount of PCBs entering the environment.
4.5 Stmmary - Economic Impacts
foregone savings from rebuilding:
$9.6 million (1979); $373
million to $747 million total
lost service time (increased rental of replacement transformers): $2.38 million per year
4.6 Poet Per Pound of PCBs Kept from the Environment
Ban on rebuilding
$373 million to $747 million * 23.8 million* -------------rrw to saTooSHb------------------------
$429 to $16,400 per pound FCB.
^Present value of one dollar per year indefinitely discounted at 105 eouals $10. '
31 HONS 013263
5.0 RAILROAD LOCOMOTIVE TRANSFORMERS
5.1 Present Ownership and Use Plans
Many of the major railroads in the northeastern united States are electrified. High voltage alternating current is supplied at 25 hz, 11,000 volts, by overhead catenaries to electric locomotives and multiple wit electric comuter cars (MUEC). Transformers on board the locomotives and MUEC cars reduce the voltage to the level required by the traction motors. These transformers are specially designed to fit into the limited space available on the car or locomotive and are built to withstand severe shock and vibration. The transformers incorporate a pimp to force the coolant liquid through cooling fins and thereby improve the thermal efficiency of the wits. It has been standard practice to use PCB based askarel coolant liquids in these transformers because of the possibility of a severe fire should a derailment occur in one of the runnels leading into New York City.
The federally fwded Northeast Corridor Improvement Project is upgrading much of the power distribution system between Washington, D.C. and New York City. According to Hr. Clifford Gannett of the Federal Railroad fckiinistration, the scheduled completion date for conversion of the power on this portion of the railroad system is now September, 1983*. The conversion of the catenary power to 60 hz, 25,000 volts, will have a major effect on the continued use of many of the present askarel transformers on locomotives and MUEC cars operating in this area. Although seme of the newer equipnent can be converted to operate at the higher voltages by changing internal taps in the transformers, many of the
Original-information indicated 3rd quarter of 1982. Letter from Clifford Gannett (Federal Railroad Administration) to EPA dated "sptmdm 18, 1978. Subsequent press reports indicated completion in Cepftoet of 1983. This was confirmed by a telephone call to Mr. Gannett in February 1979 (See telephone mmoo dated February, 1979 from Harold Snyder, thS/EPA to record.)
32 HONS 013294
transformers will have to be replaced, and the railroads Intend to scrap any of the oldest cars and locomotive* rather than to invest in the new trsnsfotmars that would be required to keep them operating. Table 5.1-1 lists the ownership of the MUBC cars and locomotives using PC8 cooled transformers that are presently in service and sunurizes the effect of the voltage conversion on the continued use of these transformers.
5.2 Hsquirnente of the PCB Ban Regulations
Use of PCB railroad transformers: Authorised until July 1, 1964 subject to the following limits on the concentration of PCBs in the dielectric liquid:
After January 1, 1982: St PCBs maximum After January 1, 1964: 0.1% PCBs maximum
Servicing and retrofilling of PCB railroad transformers mtd treatment of PCBs in other than a totally enclosed manner: Authorized until July 1, 1984, provided that there is no change in the ownership of any PCBs.
Processing of PCB contaminated liquid prior to sale for aervicing transformers: Banned after July 1, 1979, mless SPA grants an exemption free: the 'processing* ban regulation.
Sale of PCBs for servicing railroad transformers: Banned after July 1, 1979, unless EPA grants mi exemption from the 'distribution in ccnasrce" ban regulation.
Testing of liquid in PCB railroad transformers to determine concentration of PCBs: Required immediately after any servicing that ia performed to reduce the concentration of PCBs and again 12 to 24 months later. Records of these analyses must be Maintained until January 1, 1991.
Rebuilding PCB railroad transformers in other than a totally enclosed manner: authorised until July 1, 1984. However, any transformer rebuilt after January 1, 1982, must be refilled with liquid containing less than 50 ppm PCBs.
33 HONS 013245
Table 5.1-1
a--ary of PCB Ctalad Railroad Itansfoners in Service (one Transformer per Car)
Owner SEPm NJD0T Conn DOT/MDV DOT Conrail Oonrail
Amtrak Aatrak Aatrak
Effect of Late 1982
Change
Maber of Matter
IVpe of
pcb Cars
Brpd patent Transfonaara Scramed
MUBC 344 38
Nudxor Tranefouaers
Haolaoad
Kota PCB Transformers to Besain In Service Gal/frana.
74 232
KJBC 122 18
0
104
MJBC
244
0
0
244
MJBC
77
0
0
OS 1 loco.
E33, E44 Loco.
51 76
51 0
0 76
0 710 0 500
Hetroliner 61
OG 1 Loco. 33
G60 Zooo.
26 964
0 33 0 147
2 0 0 152
59 0 26 665
255 710 380
HONS 013246
*11
data
tram
letter
to B*
fna *r.
Clifford
Gannett,
ftdaral
Railroed Malniatnfeicn,
9/15/71
Maximal concentration of PCBs in liquid used to service or bop off railroad transformer*:
No restriction intil January 1, 1982. 6% PCBs fra* January 1, 1982, isitil January 1, 1984. O.lt FCBa after January 1, 1984.
5.3 Coat Impacts of the PCB Ban Regulations
July 1, 1984 deadline on continued use of PCB railroad transformers!
It has not been demonstrated that it is technically possible to reduce the concentration of PCBs in PCB railroad transformers to belcw the 500 ppa level that is used to distinguish "PCB transformers" from "PCB contaainated transformers." It is anticipated that EPA will review the technology of retrofilling and processing of transformer liquids before the July 1, 1984, ban on the use of railroad transformers containing more than 500 ppe PCBs to assure that this requirement does not cause substantial sconcmic impacts. Compliance with these regulations will therefore require that the affected railroads maintain close ccmnunication with CPA to resolve any unanticipated problems. There is not sufficient information in the record bo support any estimate of the costs that will be incurred fay the railroads in participating in the eventual review of these regulations.
Required reduction of PCB levels to below 6t by January 1, 1982;
It has been daaonatrated that a single retrofilling procedure consisting of draining, flushing, and refilling with non-PCB coolant liquid can result in PCB concentrations substantially below 6% (Walsh, 1977;* Ross, 1977**). The analysis of the inpacts of the proposed PCB regulation issiamd a total materials and labor cost of $20 per gallon for retrofilling
*Walsh, .J., D.E. Vfeytik end B.A. Pearce, (Westingbouse Electric Oorp.) 1977. Evaluation of Silicone fluid for Replacement of PCB Coolants in Railway industry, final import, import Mb. oot-Kc-1294. i~W* liiije~ Ha. i Transportation Systems Canter, U.S. DOT. December 1977 (attachment bo reply caaments from Clifford Gannett (Federal Mllroad Administration)).
**R9aa, Stephan D., John B. Biggins, Donald L. Johnaton, and James M. WcQuade (General Electric Co.). 1977. Retrofilling of Railroad
Transformer*. Cambridge, Ha.< Transportation systems Center."oTs.
DOT, July 1978 (attachment to reply cements from Clifford Gannett (Federal Railroad Administration)).
35
HONS 013247
a transformer a single time with silicone liquid (Veraar, 1978). A revised estimate for the cost of retroftiling a transformer based on the procedure developed by Cow coming Corporation (Page, 1977)* is summarized in Table 5.3-1. The use of silicone at $12 per gallon (Versar, 1978, p. 30) in estimating retrofill costs should give an upperbound but reasonable figure because, although the alternative liquids may be cheaper, only silicone can be treated to ranove dissolved PCBs by filtration.
The total cost of retrofilling the 964 existing PCB railroad transformers is calculated in Table 5.3-2 to be $6.6 million. Nwry of these transformers will be scrapped in late 1982 when the scheduled voltage change on the Northeast Corridor is made. It is therefore possible that at least some of the transformers will be replaced prior to January 1, 1982, with units which can operate at both the present voltage and the higher voltage that is planned. If this replacement is made prior to the date specified for the 6t PCB limit, the present transformers will not have to be retrofilled. The cost of this retrofill requirement can be calculated by assuming that all of the transformer replacements are made by January 1, 1982, and that retrofilling is only performed on the 665 transformers that will remain in service tnder higher voltage conditions. The coet of this limited retrofill pcogran is calculated to be $3.7 million. If the changeover does not occur until September, 1983, all of the cars will have to be converted to non-PCB transformers in order to take advantage of the retaining useful life of the exisitng equipment.
*Page, William C. and Terry Michaud (Dow Coming Corporation). 1977. 'Development of Methods to Retrofill Transformers with Silicone Transformer Liquid,* IEEE Paper 22-477 presented at the Electrical Insulation Conference, Chicago, Illinois, Septonber, 1977 (attachment to letter from Terry Michaud to EPA dated August 1, 1978).
36
HONS 013248
Table 5.3-1
Betroflll of PCB Railroad Traneformer with Silicone - 300 Gallon Capacity AssuneiT
Cost
Step Procedure
Materials
1 Bot drain askarel from 5 druas $ $25.00* transformer (85 raaoval - $125.00 - Kies, 1977)
Estimated Labor-man hours
2 hours
2 Pill with 255 gallons 255 gal TCB 8 $5.21 4 hours trichlorobensene, circu- a $1329.00...
late and drain
3 Fill with silicone
300 gal silicone
2 hours
8 $12.00 $3600.00
4 Dispose of liquid (tollina, 1978)***
10 drues 8 ($115/drum disposal + $27.28
transportation
Sub*total
ff"Hours i 515.06**
* Labor Cost: 8 $15. per hour
$120.00
Tbtal cost per transformer:
$6477.00
Cost per gallon:
$21.99
Versar 1977, pp. 3-8. "Versar 1978, p. 33.
****>11ins fovironaantal Service, Inc. 1978. Indemnified Diapoaal Service tec Polychlorinated Blchenvls (PCBs - Astaurels), May 1. 1978. SUBeattad ee an attachamnt to letter from Jasm's Thompson (T&R Electric Supply Co.) to EPA, dated August 28, 1978.
37 HONS 013249
Tabla 5.3-2
Oast af Retrofilling Railroad Tnmfooen to Meet January 1, 1982 limit of 6 PCBa: $21.99/gal.
ana HUT ODM DOT/tCA moor OMIL Q3AML
mama
MW Maw
00
All Tl'MWfcOW WltlDfilUd
allow/
Nater of Twftmu
NIK MK
mac mac
un (ooo
K33, |M UXJD Mtiolimr OBI *****
HO U
399 390 390 2S9 710 900
395 710 300
344
123 344
7
91 79 41 33 34
Malt
CD*t
41,0*1,009 471,000
1,341,000 30.099
7*4,099 034,009 342,009 919,009 317,009
04,447,009
<302,000
Mmam TTaafmT Mpiaownt ftuai MnMrt by jiwity l. 1*03
mater of Tfffnnw Opt
233 41,379,000 194 972,000 244 1,341,000 49 90 90
S* 331,000 9 34 217,000
43,734,900
(179,000 ^Ulom)
*V$rv, 1V7S, p. 29.
HONS 01.3*50
Reduction of the concentration of PCBs in each of 665 retrofilled tranaformer* from an assvmad average concentration of 5% to 1,000 pp will require two separate retrofilling procedures, assining that each retrofill reduces the amount of PCBs in the transformer by at least 86%. It ms suggested that silicone liquid could be processed essentially in place to reduce the concentration of PCBs and that this processing would cost $4,600 psr transformer + $25 per gallon of liquid in the transformer, or an average of $40.33 per gallon for a 300 gallon capacity transformer.* This estimate was based on an aseuesd loss of ten pounds of silicone per gallon of liquid treated by activated carbon, or a recovery efficiency of -25% (l.e., 10 pounds of new silicone would be lost in processing and recovering 8 pounds of contaminated ailioone). Oils analysis indicates that it would ba cheaper to use new silicone at $12 per gallon, even though activated carbon has been shown to remove PCBe from silicone.** The coat of each retrofill would be $15.14 per gallon as calculated in Table 5.3-3. Total cost to the railroads for the two retrofill procedures required to reduce the PCS concentration in each transformer to below 1000 ppm would then be (170,000 gallons x 2 rstrofllls x $15.14 per gallon - ) about $5.15 million. This cost could be reduced if a less expensive disposal method became available or if acam way were developed to reclaim the silicone.
^Attachment 2 to "Comments on Proposed Regulations to Ban PCBs." Submitted by General Electric Co. as a written oomment to the EPA Hearing Mooed on the FCB Ban Regulations. Uhdated.
**0ow Corning Corporation, imnoval of PCB from Dow Coming 561* Tt--tecner Liquid by Charcoal filtration, Midland. Michigan: Uhdated IAS dtea in Verier, i97b, p. ).
39 HONS 013251
Table 5.3-3
Batroflll at Contaminated Silicone Filled Transformer 300 Gallon Capacity Aasaasd
Stan Procadura
X Hot drain tUieem (851 rsaoval of liquid)
2 Flush with 45 gallons silicon#, (additional 3* mbomI of FCBa)
3 Rami with 255 gal. MM Silicons (fU/gaUon)
Cost
Materials
$540. $3060.
Labor-nan hour* 2 hours 2 hours 2 hours
4 Disposal of 6 druse
ooMsadnatsd silicone ($142)
Sub-total* $4452.
Plus Labor Cost $15/hour:
$90.
Total coat par transfcraer: $4542. Awaraga cost par gallon: $15.14
6 hours
40 HONS 013252
It should be noted that the highest calculated total cost of the retrofill program of $21.82/gallon (Table 5.3-1) + 2 x $15.14/gallon (Table 5.3-3) " $52.10/gal is somewhat less than the estimated co6t of $78 per gallon assumed by Charles Bigelhardt of Amtrak and by Dean Aboudera of the American Public Transit Association in their oral constants at the August 31, 1978, hearings on the proposed PCB Ban Regulation. However, it is felt that the estimate of $52.10 per gallon is in fact an upper bound estimate of the cost impact of the PCB Ban Regulation because of the opportunities available for cost reduction by use of other materials being evaluated by the Federal Railroad Administration such as RTBnp* and Iralec T-l*.*
Testing to determine concentration of PCBs in liquid. Testing of the liquid in each railroad transformer that remains in service will apparently be required four times: upon completion of each of the three retrofill procedures and again 12 to 24 months after the completion of the final retrofill. Only the initial testing will be required for those transformers that are replaced in late 1982. There has been no information submitted to the EPA on the recamended methodology or estimated cost of analyzing samples of silicone oil for the presence of PCBs. The methodology for this analysis should be about the sane as for PCBs in mineral oil, although the silicones would require additional maintenance of the colum in the gas chromatograph. Cost of each analysis therefore might be $125 to $150, including order processing costs. Tbtal cost of the required analyses would be expected to be $440,000 as calculated in Table 5.3-4.
*0ral ooamnts by Clifford Gannett (Federal Railroad Administration) at August 31, 1978 hearing.
41 MOWS 013253
Table 5.3-4
Coat of Analyzing Silicone Oil for the Presence of PCS in Rstrotilled Railroad Transformers
Initial retrofills 964 Samples 0 $150
3 x 665 transformers 8 $150
Tbtal analytical coat -
$144,600 $299,250 2443,850.
5.4 PCBs Controlled by the Regulation
There are presently about 4,000,000 pounds of PCBe in use in railroad transformers. The final disposal of this material was regulated by the PC3 Harking and Disposal Regulations. The effect of the present regulations is to reduce the mount of PCBs lost by leakage of transformers by requiring that the PCBs be removed from the transformers and be replaced with other liquids. Although it was noted that railroad transformers often lose liquid by leaks and venting, no information was presented bo the record that would support a quantitative estimate of the PCBs required to top off these transformers to replace lost liquid. Therefore, no estimate can be made of the effect of the required retrofill program on the entry of PCBs into the environment.
5.5 Svnaary - Economic Impacts
Cost of reducing PCBs to 6%
$6.6 million
(silicone in 964 transfor mers) .
Cbat of reducing PCBs to 1000 ppm $5.15 million (silicone in 665 transformers).
taalytical Costs:
$444,000
42 HONS 01325*
S-6 Cpet Per Pound of PCBs Kept frcm the Environment At best, each retrofill prevents the entry into the environaent
of the amouit of PCBs removed from the transformers. Deduce PCBs to 6%: x 4 nu uion pounds $1.75* per pound PCB Deduce PCBs to .11; $5.15 million $300,000 17(5,000 gallons x i lb/gal x 5.t PCBs " *8* f*r po>d PCB
i I
u--s all PCBs would be lost bo the environment if not rmoved by retrofilling.
43 HONS 0X3255
6.0 OIL-FILLED POWER AND DISTRIBUTION TRANSFORMERS 6.1 Present Contamination of Oil Filled Transformers The PCB ban regulations lower the level at which PCB contaainated
mineral oil Is regulated from 500 ppm to 50 ppm. A mineral oil transformer may fall into one of three categories. A mineral oil transformer that has been tested and found to contain over 500 ppm PCBs is classified as a "PCB Transformer.* A transformer that has not been tested or that has been tested and found to contain between 50 ppm and 500 ppn PCBs is a "PCB-Gontaminated Transformer.* Transformers that have been tested and found to contain less than 50 ppe PCBs are not subject to regulation.
Most liquid-filled transformers have been filled with transformer oil. a non-chlorinated petroleum product similar to SAE 10 motor oil (Versar, 1976a. p. 255). These transformers are similar in design to PCB askarel transformers, and many of the oil-filled tranaformers were built in the sane plants that manufactured askarel transformers (Versar, 1976a, p. 84). The total muter of oil-filled transformers presently in service was previously estimated to be about 30,000,000 overhead and distribution transformers (each containing an average of 16 gallons of oil) and 5,000,000 other distribution and power transformers (each containing an average of 250 gallons of oil) (Versar, 1978, pp.36-39). It was also estimated that nearly all of the pole mounted transformers and perhaps 804 of the other oil-filled transformers art owned by electric utilities (Versar, 1978, pp. 39-40).
During the hearings on the proposed regulation, a mnber of utilities and transformer repair companies presented information on the results of sampling programs that they conducted to evaluate the extent of PCB contmnination of oil-filled transformers. This information is sumaarized in Tables 6.1-1 and 6.1-2. The reply comment from the Edison
44
HONS 013256
Tnhle 6.1-1
PtUlQT "sports of PCB Contamination of Oil Mils* Tnfai, with Ccnosntraticns Above 50 bob
Cfcppany
Pole Moulted Beference Distribution
Nota IMm Transformers
Allegheny Power Service Oorp.
1
0 of 2
Boston Edison
CcnaorMealth Edison
2 3
0 of 9
Consuners Power
4
Other Transformers
Other Samles Saspling Procedure
9 of 33* 0 of 2
4 of 12
4 of 29
oil storage tanks: 0 of 2
1 oil storage tank: PCBs <5 ppn
* 33 randomly sel ected substation transformers. Other 6 samples
were not put of
the randan smiple,
35 gallon drums of oil: 0 of 4
100 selected to be representative of age of operating transformers; no data an how these 21 samples were chosen to be analyzed first, (210 ppm max).
Many sanplas were submitted fran a
repair shop. Others are sanples taken from trans formers in various parts of tbs state.
HONS 0 1 3 *5 7
MONS 013258
Dayton tauer and Light
labia 6.1-1 (Ooritinued)
tale tainted Reference Distribution tate Nufcer Transformers
Other Transformers
Other Samples
5 -- 5 of 17 (in nervine)
0 of 9 (new)
Detroit Edison
Duke tauer Oo.
6 7
--
2 of 4 *
Reclaimed oil
storage tanks:
0 of 3
-- 51 of 161 *
SaK>linq Procedure
Sene of the 17 used transformers were selected because it ues knoun that PCBs were used in the plants where they were nenufactured.
* nexissm - 80 ppm.
Only transformers rated at less than 44 kv; hitler voltage imits thought to be less aentaadnatad. * of 161 sanplad, 3 were above 500 ppn, 7 hetnesn 100 ed 500 ppe, 41 present below 100 ppe but not quanti fied. "....it ues asauaed that all 1'ilee with de-
muti of FCRi am ocn-
MONS 013259
Table 6.1-1 Notes 1/ Letters from Nancy H. Gormley (Alleghany Rawer Service Ccrp.) Cc CPA
dated August 4, 1978 and September 7, 1978. . 2/ tetter from Charles Dolloff (Boston Edison Co.) to EPA dated July S,
1978. 3/ letter from John Hughes (Camacnwaalth Edison) to EPA dated August 4,
1978. 4/ letter from Nathan Haskell (Consumers Power Co.) to EPA dated August 7,
1978. 5/ "Supplemental Consents" subnitted to EPA by Harold F. Fax (Qeyton
Rower and Light Ccepany), August 18, 1978. 6/ Letter Iron Skiles Boyd (Detroit Edison) to EPA dated August 3, 1978. 7/ Written Cements - "Response Concerning EPA's Proposed PCB... Bane..." -
subalttsd fay nike Rower Co., August 4, 1978 and oral ocmaants fay Hr. N. J. Melton (Duke Power Co.) at the PCB Hearings, August 21, 1978. 8/ letter fran J.R. Thorpe (CPU Service Carp., a subsidiary of General public Utilities) to EPA dated August 4, 1978. 9/ letter fran Stand Newton, Jr. (<38 Service Corporation) to EPA dated October 6, 1978. }/ Oral Ccanants of Lyle Salmela (Northern States Power Conpany/MidOontinent Area Pow Pool) at PCB Hearings, August 22, 1978, (pp. 78-79 of transcript). 11/ "Consents of Ottertail Power Co. on the Proposed Amendnerrts to 40 OR 761." Undated. 12/ letter from Widen Gerstner and Paul Greiner (Edison Electric Institute) to EPA dated August 7, 1978; Exhibit III.
49 HONS 013260
Mila 6.1-2
Transformer Manufacturer and Service Ctaeanv Recocts of PCB contaainatinn of <M1 Filled heefcoen ttcw SOmal
Ccwpanv
tola Mointed Reference Distribution
Mote Mater Transfanners
General Electric
1
4 of 75
Other Transformers
8 of 164
General Electric
2 ( 25 of 55
Other Samples
Saeplinq Procedure
Samples analyzed at Customer request. Mote: these two groins of data from <Z nay overlap.
HXE 3 ( 0 of 19 )
TfcR Electric
Supply
Transformer Consultants
5
6 of 14
< 185
of 434 '
. .
2 oil storage tanks: Randcm saiple of
72ppa and 82ppn
used pole nouited
transfanner in
inventory. Average
103ppn FCBs.
) .
Ch custoier request -
primarily industrial clients; 72 of the transformers had more than SOOppai PCBe, although several of these may have been retrofilled aakarel transformers.
Table 6.1-2 Notes
1. Letter from William Gerstner and Paul Greiner (Bdiaon Electric iMtitute) to BA dated August 7, 1978. Exhibit III.
2. Utrsar. 1979, p. 40. Confirmed in letter Cron Janee young (General Electric) to BA dated October 6. 1978.
3. "Main Ooemnta..." aubaitted in writing to BA by John Qbeetad (JOT Corporation) vitiated.
4. Letter fran Janee Thcnpecn (TSR Electric Supply Cospany, Inc.) to BA dated August 28, 1978.
5. "Response to Jvne 7, 1978 Federal Register Regarding Proposed Oenge In PC8 Regulation*" aubaitted to BA by Stanley Meyers (Transform: Consultants) as an attadnant to letter dated September 13, 1978.
50 MOWS 013262
Electric Institute (EES) also sumarized this information. The EEI namely Is includsd as Tables 6.1-3 and 6.1-4. Since the EEI tables use a different definition of distribution transformers (including more than just the pole motnted wits) and Include the results of sanpling of oil storage tanks in the totals, the resulting tables are not directly comparable to 6.1-1 and 6.1-2. However, the EEI apparently had access to same data on oil-filled transformers that was not otherwise presented to the EPA.
The only data on contamination of oil-filled transformers that were baaed on a reasonably random sample of transformers presently in service were the data reported by Allegheny Power, Ooemonwealth Edison, and TVA. The samples taken by Duke Power were from a population that excluded the large transformers which Duke Power believed were not contaminated. The other utilities sampled on the basis of convenience, usually sifting transformers that were in the shop for repairs or that were being serviced in the field. RTE Corporation reported data based on a planned random sample of transformers which they had built. Although RTE reportedly has never used PCBs in their manufacturing plant, they reported that the level of PCBs seen in transformers was higher in the older units than in newer ones (none of the transformers was found to be contaminated in concentrations above 50 ppm). TWR reported a random sample of used transformers and stated that they felt that the average concentration of PCBs in oil was above 50 ppm because their holding tanks for reclaimed oil contained more than 50 ppa PCBs. GE and Transformer Consultants reported the results of analyses done on their own samples and for other companies) these data may have also been reported by the owners of the transformers and may therefore be duplicate information.
It is not possible to calculate statistics that describe all tranaformers from the data that has been reported because of problems in sampling protocols, possible double reporting of data, and uncertainties
1
51 HONS 013263
Table <.1-3 Edison Electric Institute Sa--nr of Oontaarinatad Transfonser Data Submitted by Electric DH1|Hti`
Distribution^
Power
Total^
Ccnm. Ed. TVA
No. >50 pr- No. > 50 ppn No.
26 -
17 5 43
34 2 38
>MH >S00H52
Gonsuners Duke Allecbeny av Georgia Detroit
2-
ia&
51
33 161
20 2 i 39
- - 76^
24 - 24
4 2 14
4 51 9 17 2
3/ 2
Dayton
9-
17 5 ; 26
5
Boston Ed
1-
Ottertail
1
TOTAL
37 0
0
277 67 24%
456 21%
95
5 1%
* Source: letter from Willim Gerstner and John Kearney (Edison Electric Institute) to EPA dated October 10, 1978. Appendix B. Appended notes also fro* Edison
HONS 013264
MDf to 1>M S.l-3
\/ See msi/nze C-57.80 (1978). Thia definition Includes but is not llidtwl to pole-type and reeidoitial pad-type transformers.
2/ includes oil storage facilities estd other PCB articles. 3/ As indicated by Duke Power Oo. in its hsarinq testimony (August 21. 1978, at Tr. 113) its
saepling program was not representative of its system. Rather, it was designed to ample those transformers "most likely to be PCB-oontmninated.' M. 4/ As indicated in the Duke Power Oo. Hearing Tastlaciy (Aug. 21, 1978, Tr. at 134) the 3 oanples indicating concentration greater than 500 ppe were from transfonears manufactured by the seme company at least one of which wee incorrectly filled with askarel by the manufacturer. Id. at 129. He strongly believe that any contamination greater than 500 ppm is meet inueual and inique and la not at all representative of the 35 million mineral oil transformers. 5/ Includes 58 transformers not identified as to power or distribution of which 15 (26%) contained mineral oil dielectric oontaadnated tilth PCBa at levels greater than 50 ppm.
o
KaJ
MS
Table 6.1-4 mitb BitThrlf! Institute 9u--rv of Contaminated Transformer Data
Sutadtfced by Transformer Ccwcaniea * (1)
General Electric^' RIB Til Electric^ Transformer Consultants^ TOTAL
Distribution^
Power
Total
NO. >50 m No.
261^ 20
13
>50 DOB No. 6 294
>50 non >500 m 37
19 -
19 -
6 14 6
434/
185
434^ 205
65
294 26 9t
447 191 43%
761 248 33%
65 15%
HONS 01326*
* Source; Letter fscm William Gerstner and John Kearney (Edison Electric Institute) to HA dated October 10, 1978. Appendix C. Appended notes also from Edison Electric Institute.
Hot-- tP Table 6.1-4
y Mestlnghou-- h-- not provided any independent evidence In its 11--its of the contamination of sinscal-oil transformers with PCBs. Its evslimticns are solely based on assumptions
it --toe using the cements and testieeny of others for the purpose of d--enstrating the economic iapect of the paripueed regulations.
2/ See Nd/USE C-57.12.80 (1978). This definition includes but is not limited bo pole-type and residential pad-type transformers.
3/ (Z adaits that it has "no idea how bo tackle the probl--i of what percentage of the oil is oontasinabad* and that "no statistical basis for any conclusion exists in General Electric.* R.C. Oethoff, letter to Dr. E.L. Simone (July 3, 1978). In particular, the assertion on page 5 of its Main Consents that 3-10 Billion pole-type distribution transformers may contain in excess of SO ppm PCBs is without foundation.
y Includes 75 pole-type transformers of which 4 (St) were above SO ppm.
5/ TtR Electric buys and sells used transformers. Its sanple survey is not statistically
"representative" of its inventory, the electric utility industry, or the class of 35
million mineral-oil transformers.
'
6/ Dole-type transformers. See August 28, 1978 Dr. at 126.
TJ Transformer Consultants is a transformer servicing company. Transformer Consultants has
orally informed us that it has now analyzed roughly 2,000 oil samples of which approxi
mately 33% contained greater than 50 ppm PCBs and 10% contained greater than 500 ppm
PCBs. Ina--uch as roughly two-thirds of its customers are industrial and the remainder
are small utilities, none of the sanp>les conducted by Transformer Consultants is repre
sentative of the electric utility industry.
1
HONS 0 1 3 2 6 7
8/ Generally transformers of 200 kva or greater.
9/ See, Reply Carments of Transformer Consultants (September 13, 1978). Note: These rxmbers differ from those submitted by Mr. Nestin on September 26, 1978.
about the analytical methodology that ties used in each case. However, from inspection of the data, it night be reasonable to conclude that from 5% to 40% of pole mounted transformers and from 20% to 30% of other oil-filled transformers are contaminated with FCBs in concentrations exceeding 50 pfm. Contamination to levels above 500 ppm appears to he rare. Table 6.1-5 sunsarises calculations of the anoint of FCBs in all transformers and the amount present in transformers contaminated above SO opt. Because of the uncertainties in the data, the range of confidence in these estimates must be at least a factor of four, i.e., each estimate should be bounded by e rings of -80% to +4004.
- Approximately 80% of the oil-filled transformers are owned by electric utilities, including the 149 class A and B operating companies and approximately 1000 Rural Electric Cooperatives,* About eight million of the pole mounted transformers are owned by the 1000 rural systems, of which 950 are distribution cooperatives that do not generate any power* and that therefore do not have high efficiency boilers.
6.2 Requirements of the FOB Ban Regulation
The regulation defines a class of FCB equipnent called "PCB Contmainated Transformers" and specifies certain exemptions from the marking, disposal, and ban requirements that apply to other FCB equipeent. "PCB Contaminated Transformeri" include (1) transformers which were not originally filled with a FCB aoolant liquid but that now are known to contain a liquid contmainated with FCBs in concentrations frcai 50 ppa to 500 ppe, (2) oil-filled tranformers that have not been tested for FCBs, and (3) transformers that were originally filled with FCB based askarel but that have been decontaminated to the extent that the concentration of FCBs is found to be below 500 ppe when tested after at least three months of service following the last decontamination proceAire.
*Ives, Joseph S. (National ftaral Electric Cooperative Association). Written statmaent dated August 7, 1978, and oral testimony at August 21, 1978 hearing.
56 HONS 013268
p
Table 6.1-5 Estimated Anoints of FCB in Oil-Pilled Transformers
Pole Mounted
Other
A**rage oil capacity, gallons per transformer*
16 gal.
250 gal.
x 7.6 * lb oil per transformer
121.6 Id
1900 lb
Mistier of transformers In service* 30,000,000
5,000,000
t above 50 ppm
10% 25%
Himber of transformers above 50 ppm 3,000,000
1,250,000
Pounds of oil in contaminated transformers
364.8 million lb 2,375 million lb
Aaausad average PCBs concentration 80 ppm
80 ppm
founds of PCBs in contaminated trans formers
IP*
190.000 lb**
Nimber of transformers below 50 ppm 27,000,000
3,750,000
Pounds of oil in non-oontaminated transformers
3,283 million lb 7,125 million lb
Assiamd average PCB concentration 10 ppm
20 ppm
founds of PCBs in non-contaminated transformers
Total pounds of PCBs 62>000 lb**
332,500 lb**
Versar, 1978, pp. 36-40 Confidence limits: - 80% + 400%
total 400,000 lb PCBs**
57 HONS 013269
Th following provisions apply to "PCS Contaminated Transformers" i
Continued use: defined as use in a totally enclosed wanner, and therefore not regulated.
e Marking: exempted from the requirement that a PCB label be applied.
e Servicing and rebuilding in other than a totally enclosed manner: authorised rntil July 1, 1984, provided there is no change of ownership of liquid containing over SO ppa KBs. (Note: reclaimed transformer oil may be presuMd to contain between 50 and 500 ppm PCBs unless it has been tested.)
s Reclaiming used transformer oil: authorized without restriction for use by the owner of the oil in his own transformers.
s Sale of reclaimed transformer oil: tested and found to contain less than 50 ppm PCB: not regulated.
Jtot tested for PCBs or tested and found to contain 50 to 500 ppa PCB: banned after June 30, 1979, unless SR grants an exemption from the 'distribution in coaeerce* bans. BPS has not yet announced the conditions under which individual and consolidated petitions for exemption will be accepted.
a Resale of used transformers: excluded by TSCA from the "distribution in cn--arce* ban.
e Disposal of drained transformers: not restricted.
e Disposal of used transformer oil: tested and found to contain no detectable PCBs: not regulated, (testing may be performed on batches of oil fren different transformers, i.e., testing of storage tanks is permitted.)
Tasted and found to contain detectable PC8s in concentrations below 50 ppa - not regulated, except the oil nay not be uead
58
HONS 013270
as a sealant, coating, or dust control agent (i.e., not allowed as road oil or pesticide carrier).
Not tested or tested and found to contain 50 to 500 ppa FCBs: storage and shipping containers must have PC3 label. Storage must be in special FCB storage areas and shipping vehicles must be marked. Disposal must be in one of the following:
(1) In an approved PCS incinerator.
(2) In an approved chemical waste landfill.
(3) In a large (50 million BfTU per hour or larger) high efficiency boiler that meets certain specified operating criteria. The EPA Regional Administrator must be notified 30 days before the first time PCB contaminated oil is burned.
(4) By any other method that has been denonstrated to have as high a destruction efficiency for FCBs as does a high efficiency boiler and that has been approved for disposal of PCB-oontaninatad oil by the BPA Regional AAninistrator.
6.3 Cost Impacts of the PCB Ban Regulation
The regulation does not affect the continued use or resale of PCB contaainated transformers, nor does it affect the maintenance of these transformers except to ban the sale of reclaimed contaminated fluid. The only impacts will be on the reclamation and disposal of contaminated used transformer oil and other contaminated transformer liquids.
July 1, 1984 deadline on rebuilding oil-filled transformers:
After July 1, 1984, rebuilding of oil-filled transformers will only be allowed for those inits that have been tested and found to contain lass than 50 ppa FCBs. It is anticipated that EPA will review the status of the rebuilding of transformers and the occurrence of PCBs in the oil of oil-filled transformers prior to the 1984 deadline. Those companies that rebuild transformers will therefore have to stay in close contact with EPA and participate in the regulatory review process in order to ensure that this deadline does not result in major unforeseen econcmic impacts. There is not sufficient information to support any estimate of the costs to be
59
HONS 0132*1
Incurred by Che transformer service industry and by the users of oil-filled transformers by participating in the eventual review of these regulations.
Reclamation of used fluid frcm PCB contaminated transformersi
According to Duke Power Company, reclaiming and reprocessing transformer oil saves at least $.40 per gallon on the 170,000 gallons of oil vhich they reprocess in-house each year.* The Cincinnati Gas and Electric Company reported that they salvage 60,000 gallons of used transformer oil each year from their transformer repair operations and that this is reprocessed into 58,000 gallons of useable oil at a total cost of $18,000 or $.31 per gallon.** New transformer oil presently costs about $1.19 per gallon** and the price is expected to increase over the nest few years as supplies of naphthenic crude oil are depleted and transformer oil must be made by the more expensive process of deeply dewaxing paraffinic crude oil fractions.
Not all used transformer oil is reclaimed because mailer transformer ccmpanles and utilities do not generate enough used oil to justify the purchase of the necessary equipment. However, reclamation appears to be the standard practice for most transformer repair shops and major utilities. The regulations authorize the reclamation of used tranaformer oil by utilities for use in their own transformers. The regulation requires that all transformer oil be presumed to contain mors than 50 ppn FCBs unless it has been tested and found to contain less than 50 ppm FCBs. The sale of reclaimed transformer oil is banned after June 30, 1979, unless each batch has been shown to have less than 50 ppm FCBs or EPA exempts the seller from this ban requirement, the EPA has not yet
'touke Power Company's Response..dated August 4, 1978. Submitted to EPA as a written main camnant on the proposed PCB ban regulation. **Imtter frcm E. E. Galloway (the Cincinnati Gas and Electric Company) to EPA dated August 4, 1978.
60 MONS 013272
estsbliahed the basis on which it will accept individual or consolidated petitions for exarption, nor has it announced the basis for granting such exemptions- The filtering of oil by transformer service companies as a part of routine field maintenance is allowed because the oil is returned to the transformer frcm which it is taken and ownership of the oil does not change, ao there is no "distribution in- ccamerce" taking place.
As calculated in Table 6.3-1, approximately 73% of the transformer oil is in transformers owned by large utilities, most of which do their own routine maintenance.
Maintenance of most of the transformers not owned by the major utilities is performed by transformer manufacturers and by independent npair shops. About 8 million of the 30 million pole mounted distribution transformers are owned by small distribution utilities most of which do not rspsir their own transformers. As calculated in Table 6.3-1, the effect of the ban on the sale of reclaimed oil is to eliminate the opportunity to recycle 22% of the available oil unless earn batch is tested and shown to contain less than 50 ppm PCBs. If it is assumed that 4t of all oil becowes available for recycling each year (equivalent to assuming an average of 25 years between major servicing operations on each transformer) and that 75% of the oil was actually recycled, savings in 1978 would have been (1.73 billion gallons x 4% available x 75% reclaimed x $.40 to $.80 per gallon savings per gallon reclaimed -) $20.8 million to $41.5 million. The cost of the foregone savings from recycling in 1979 could be as much as 22% of the 1978 savings, or $4.6 million to $9.2 million.
The actual reduction in the amount of oil reclaimed by transformer shops will depend on the economics involved in testing the oil to dmsonstrate that each batch contains less than 50 ppm PCBs. The total fount of oil that could be reclaimed for purposes of resale by transformer eintensnce shops might be 11.4 million gallons per year as calculated in fthlt 6.3-2. If this oil were accumulated in 1000 gallon batches prior to
61 MONS 013*73
Table 6.3-1 Used Transformer Oil Available for Reclamation
Pole Mounted Transformers
Other
Average capacity-gallons
Total number in service Owed by Industry Owned by anall utilities Owned by major utilities
Amount of oil in use
Ibtal
Mount of oil used by major utilities
Ibtal
16 250
30.000.000
8,000,000 22.000.000
5.000.000 900.000
100.000 4.000.000
480 million gal
1,250 million gal
1,730 million gal
352 million gal
1,000 million gal
1,352 million gal
Percent of transformer oil used by major utilities:
1,352 million gal. 1,730 million gal. 78%
Percent of transformer oil not available for recycling: 1-78% - 22%
62 MONS 013224
Table 6.3-2
utiaatad Supply of Transformer on Available for Recycling for Sale
total mount of oil i fraction available each year x fraction to transformer repair companies x fraction assumed recoverable (not
too degraded by prolonged use) total annual supply of oil available
tor recycling for sale
1.73 billion gallons 44
22%
75%
11.4 million gallons
63 HONS 013275
testing, all of the oil could be tested for PCBs by performing 11,400 analyses. Costs of such a routine sampling and analysis program were previously estimated to b? from $67 to $80 per sample (Versar 1970, p. 41). The cost of performing such an analysis on a 1000-gallon tank full of oil would be only $.08 per gallon. Testing to prove that the oil could be reclaimed would be justified as long as the expected cost per gallon reclaimed is less than the cost sawings of $.40 per gallon achievable by reclaiming the oil. Therefore, the analysis of 1000-gallon batches would be justified if as few as one of every five batches were actually fond bo have less than SO ppm PCBs. if the total anoint of PCBs in transformers is actually the 400,000 pounds estimated in Table 6.1-5, the average concentration of PCBs in the 1.73 billion gallons of transformer oil that is in use would be about 30 ppm. This implies that at least one half of the batches of oil that are tested would have less than 50 ppn PCBs if care were taken to avoid contamination of the oil with materials used with askarel transformers. If only one half of the batdies were in fact contaminated to levels of less than 50 ppm, an expenditure of (11,400 analyses at $80 ) $912,000 for chemical analyses would make available (11.4 million gallons x 50t -) 5.7 million gallons of oil per year for recycling and resale. If the recycling of this oil saves $.40 to $.80 per gallon, the total cost of the ban on selling untested recycled transformer oil would be reduced by (5.7 million gallons x $.40 to $.80 per gallon $912,000 testing cost ) $1,368 to $3,468 million per year. Total costs would then be ($4.6 to $9.2 million - $1.4 to $3.6 million * ) $3.2 to $5.6 million per year. If, however, none of the batches of oil had over SO ppm PCBs, the total cost of the regulation would be the cost of the analyses (or a total of $912,000 per year if testing were performed on batches of 1000 gallons) or even less if the average batch size were larger.
64 HONS 0132*6
Disposal; the PCB Ban Regulation authorize* the disposal of transformer oil contaminated with SO to 500 ppn PCBe in large, high efficiency boilers meeting certain requirements of size, feed rate of the contaeiinatad oil, presence of excess oxygen in the stack gas, specified lnstrvmantation and monitoring procedures, and other specified operating conditions, the contaminated oil would have to be handled and labeled as PCS* during shipment and storage.
She regulations require that the EPA Regional MRdnistrator be notified at least 30 days before the first time each high efficiency boiler is used to bum transformer oil known or pc*aimed to be contaminated with PCBa. foe regulations further state that the contaminated oil camot be fed into the boiler Airing start-up or shut-down conditions and that the oil can ccmprise only ten percent of the fuel while the boiler is operating. Therefore, special holding tanks and metering pimps will be required to feed the transformer oil into the fuel stream in a controlled Mount during periods of stable operation of the boiler.
A raster of utilities have stated that they have power boilers that operate at combustion conditions similar to those specified for PCB Incinerator*.* A special holding tank and metering pimps will be required to feed oontasdnetsd transformer oil into a high efficiency boiler. Additional road construction, fencing, or other utilities may add to the coat of equipping a boiler to bum transformer oil in compliance with the regulation. This expenditure would probably only be made if justified by savings resulting fro* (1) decreased disposal coats and (2) the value of heat recovered in burning the transformer oil.
`Utter fra* Nancy Oormley (Allegheny Power Service Corporation) to B>A dated August 4, 1978. _ `letter from James Mulloy (City of Los Angeles Department of Hater and Power) to ERA dated August 7, 1978. `Attachment to letter from L. John Cooper (Nebraska Public tower District) to BPA dated August 4, 1976. "Goammnts of Otter foil tower Company on the Proposed AmenAnent* to 40 CPR 761.* Submitted to EPA by Jay D. My*ter, undated. `letter fraa S. A. All (Public Service Indiana) to EPA dated August 4, 1978.
65 HONS 013277
Disposal of used transformer oil in approved high temperature PCB incinerators has been quoted to cost $.08 per pound in tank truck lots (Rollins, 1978) plus perhaps $.02 per pound transportation (Versar, 1977, pp. 2-32). This is roughly $.75 per gallon. T&R Electric estlasted that fuel oil to replace transformer oil used in their boiler would coat $.42 per gallon.* Shipping costs to move transformer oil in dross bo boilers equipped to bum it will probably not exceed the ccmsercial trucking costs of $2.70 per hundred pounds for tripe under 100 miles (Versar 1977, p. 2-33). Fbr transformer oil weighing 8 poinds per gallon, this is equivalent to ($2.70/8 ) $.34 per gallon. Shipment of large quantities by tank truck would be considerably cheaper per gallon. The value of the oil to the company that owns and bums it would be equal to the savings in disposal cost ($.75 per gallon) plus the net fuel value ($.42 -$.34 $.08 per gallon). Even though most utilities might be able to obtain fuel for their power boilers at a lower cost than is paid by T$R Electric, the savings in disposal cost of $.75 per gallon could quickly pay for the estimated cost of installing additional handling facilities at the boiler.
Since the value of used transformer oil as fuel is roughly equal to the cost of handling and transporting it, the total cost of disposal to those utilities that have suitable boilers will be the cost of equipping the boilers, there is not sufficient information in the record to support an estimate of the cost of installing this equipment, but this alternative disposal method should be considerably cheaper than ccsmercial approved PCB incineration for most of the 149 class A and B utilities.
Letter Sam Janes Thcnpeon (TSR Electric Supply Company, Inc.) to DA dated August 28, 1978.
66 HONS 013278
Satisfactory high efficiency incinerators will not be generally
available to the Many distribution utilities, transformer repair shape, and
industrial owners of oil-filled transformers, for instance, KR Electric
is a transformer repair shop that bums 200,000 gallons of used trmsformer
oil each year in a hot weter generator which has a flame temperature of
1700* P.* The regulations will require that this oil be disposed of by
incineration in high efficiency boilers or by other approved methods. This
will result in increased costs to TiR Electric both to dispose of this oil
n) to replace it.
-
If the retirement that waste oil be labeled as PCBe discourages general handling of this material, the value of the used oil to the company that generates it may be considerably less than its potential fuel value. The result may be disposal costs of up to $.75 par gallon. Since much of the waste oil is now used as supplemental fuel in amall boilers that will not meet the raquiments established by the regulation, the opportunity east of ths regulation may be up to ($.75 disposal cost + $.42 fuel value ) $1.17 per gallon of the oil that it incinerated In approved PCB incinerators.
The discussion of radiation of used transformer oil concluded that the value of reclaimed oil was such that testing of batches of oil to darnstrate that the PCB content la below 50 ppm will be justified for most of the transformer repair shops. The oil that will require disposal will ha those batches found to be contaminated above 50 ppe, that oil whidi hi degraded past the point where reclamation is feasible, and the oil ganeratad in maall batches by junk yards and other industrial concerns that handla transformers infrequently. It was estimated above that 5.7 million gallons psr year of available oil would be salvageable and contain lan thn 50 ppm FCBs.
1Lettar cram Jams Thompson (Tut Electric Supply Ocapany, Inc.) to EPA dated August 28, 1978.
67 HONS 013279
The maximum economic ooet would be incurred if the remaining oil were disposed of in approved high teeperature PCB incinerators. The total annual cost of this incineration is calculated in Table 6.3-3 to be $11.1 million per year. This total would be reduced considerably if the large utilities were willing to accept contaminated oil for burning in high efficiency boilers from other sources, but the Laments to the EM by the utilities did not express any Interest in making this service generally available.
The willingness of large utilities to make available their high efficiency boilers for burning used transformer oil nay be increased by the willingness of the mall utilities and transformer repair shops to psy up to $.75 per gallon for this service. The large utilities would incur no cost other than the cost of supervising the transfer of truck loads of liquids to their storage tanka and the monitoring and record teaaping costs that are incurred by the regulations on any disposal of PCBs. Given a perfect market, the large utilities might be expected to be willing to pay for the fuel value of the used oil. However, the market is likely to be very imperfect, and the actual^ price charged by the utilities for this service can therefore not be predicted. However, since the burning of oil by the large utilities will not cost them anything, the price that is charged will represent a transfer payment from the mall transformer shops md distribution utilities to the large utilities, and will not represent a real economic cost. Heal economic costs would result only from the higher transportation costs of moving the oil to the large utilities and from the greater value of the heat content of the oil to the mailer companies thm to the large utilities. Them economic costs are likely to be only a mall fraction of the costs incurred by incineration of this oil in approved PCB incinerators.
Marking and Storage Costs! The change in the definition of PCB material from a concentration of 500 ppm to a concentration of 50 ppi extends the Impact of the PCB Marking and Disposal Regulations to all used
68 HONS 013280
TABLE 6.3-3
Cost of Disposal of Transformer Oil from Mall utilities, transformer Atpair steps, and dtKer Sources
total Amount of Transformer oil In Service x Mount Available Each Year x Mouit Hot Owned fay Urge Utilities Mowt Available Per Year * Moult Reclaimed and less than 50 ppa PCBs Ibtal Available tor FViel x Coat of Incineration and lost Fuel Value Maxinn Oast Per Year:
1.7 billion gal. 41
22% 15.2 million gal.
5,7 million gal. 9.5 million gal. $1.17 per gal. $11.1 million per year
69 HONS 013281
transformer oil that is being stored for disposal or reuse and to the oil that is being transported for disposal. At a very mininun, special PCB storage areas will be required at each of the 149 large utilities that maintain their own transformers. These major storage areas were previously estimated to cost $2000 to construct and to result in annual operating costs of $2,125 per year (Versar, 1977, pp. 2-6). Total costs incurred because of the inclusion of transformer oil may therefore be equal to ($2000 per site x 149 locations ) $300,000 in initial construction costs and ($2125 x 149 ) $320,000 per year thereafter. The regulation alao permits bulk storage of used transformer oil and the provisions of the Spill Prevention Control and Couitermeasure (SPCC) plans of the oil spill prevention program become the storage criteria. Since almost all utilities have SPCC plans, this option probably results in no additional costs being Incurred.
Additional marking costs will be incurred in applying pcb labels to drums, tanka, and trucks used to transport usad oil to the disposal sites. Because any tank used to contain transformer oil must be considered to be a PCB container, special decontamination will be required before it could be usad for any other service. Therefore, it ia likely that each high efficiency boiler facility will have a dedicated truck trailer tank that is used to haul PCBs. Application of labels to these tanks will cost only a few dollars per year.
6.4 PCBs Controlled by the Regulation
A certain anoint of used transformer oil has been used in the past as fuel in various boilers and power generating units. When possible, the oil has been reclaimed for uae in transformers. Other uses include road oiling and re-refining into lubricating oil. Only a very rough estimate can be made of the anoint of PCBs released to the environment by past practices in handling used transformer oil.
If it is assailed that pest practices resulted in the use of one-half of the oil as fuel in boilers operating at conditions that
70
HONS 013282
destroyed 98* of the PCBs present and that the retaining PCBe would eventually enter the envirornent, the burning would have been expected to destroy (.98 x .5 x 400,000 lb FCBs e ) 196,000 pounds of the PCBs in transformer oil. The effect of the regulation is to require the eventual disposal of all transformer oil in high efficiency boilers that will destroy 99.9* of the FCBs present. Therefore, FCB releases to the envirornent may be reduced from (400,000 - 196,000 ) 204,000 pounds to (400,000 x [1 - .999] - ) 400 pounds, o: a net reduction of about 200,000 pounds of FCBs.
6.S Sunnary - Economic Impacts:
Ban on reclaiming oil for resale:
$3.2 million to $5.6 million per year (may be reduced if EM
exempts processing and resale from the ban requirements).
Limitations on disposal of oontaainatsd transformer oil:
Cost of storage tanks, etc., cannot be estimated from at high efficiency boilers: information in the record.
Cost of incinerating oil generated by other than large utilities:
up to $11.1 million per year if
larqe utilities do not accept oil for burning in their boilers. Cost may be reduced considerably
if large utilities make this service available.
Cost of special storage area for tranaformer oil at utilities:
$0 to $300,000 initially plus $0 to $320,000 per year starting 30
days after promulgation of the regulation.
6.6 Post Per POud of FCBs Kept from the Environment
If It is saw--d that the restrictions on disposal and
reclaiming of transformer oil will continue for the 30 year life of the
newest oil fillad tranfocmers:
Ban on reclaiming and special disposal requirements *
*3.2 million to S5.6 million + 0 to $11.1 million + 0 to $.3 million , $48g to $2550
200,000 lbs/30 years
par pan! FC3e
71 HONS 013283
7.0 IMPACTS ON TRANSFORMER SERVICE COMPANIES 7.1 Present Status There arc presently about 300 mall companies that service the
transformers owned by mall utilities and by industry.* The services offered by these ccnpanies include field testing and servicing of transformers and complete shop maintenance and rebuilding services.
7.2 Requirements of the Regulation The regulation requires that all oil-filled transformers be
considered to be FCB contaminated transformers unless the concentration of FCBs in the oil has been demonstrated by chemical analysis to be less than SO ppi. The regulation bans the sale of any new or reclaimed transformer liquids unless they are tawwi to contain less than SO ppn FCBs.
7.3 Iamect of the Regulation The major impact of the regulation on the mall transformer
service companies results from the change in the definition of PCBs Cram a concentration level of S00 ppa to a level of 50 ppa. Many of these companies have discontinued servicing askarel transformers because of the potential liability that could result from spills or worker exposure, and because of the relatively high price of building the required storage areas for FCB materials. Companies who do not have oil storage facilities meeting SFCC requirements are now required to Install special storage areas for the storage of oil filled transformers and used transformer oil.
Transformer service companies will face increased coats from the ban on reclaiming FCB contaminated transformer oil for resale, and
*Latter 5cm Robert L. Sanfomn (Electric Apparatus Service Association) to efa. undated.
72
HONS 013284
increased disposal costs. These costs were discussed in detail in Chapter 6, and the companies should be able to pass them along to their customers. The fact that the regulation allows reclamation of PC3 contaminated oil for use in the owner's transformers but not for resale will provide an econonic incentive for utilities and large industrial concerns to perform their own aaintanance rather than contract it out. However, there is not sufficient information available to support any quantitative estimate of the resulting aarket shifts. The economic impact of restrictions on these activities will be dependent on the extent to which EPA grants exemptions for these activities.
7.4 PCBs Controlled by the Regulation There was no information presented on the aneuit of PCBs entering
the environment as the result of improper storage of transformer oil by transformer service shops. Therefore, no estimate can be made of the reduction of PCBs entering the environment that will result frcm the improvement of storage conditions at these facilities.
7.5 Suwaary - Economic Impacts Information is not available frcm the record to make estimates of
these impacts.
73 HONS 013285
8.0 minim; machinery*
8.1 Currant Use of PCB-Cooled Mining Machinery Motors
In the late 1960s and early 1970s, PCBs were used as a motor coolant In three types of electric motors manufactured by Reliance Electric for Joy Marvufactur ing Oxnpany. Joy used these motors in three nodels of low seam mining machinery: CM3 continuous miners. 9CM continuous miners, and 14BU10 loaders. Table 8.1-1 susnarizes the production statistics and present usage of these machines.
Che snail coal mining company in Pennsylvania is operating the three remaining Model CM3 continuous miners known to be in service. This company also has portions of several other CM3 miners which they have purchased for parts. Two of the machines in use have had the PCB-coolant replaced with a silicone fluid and two of the three motors on the third miner have also been filled with silicone. If the motors were not completely cleaned and rewowd at the time the silicone fluid was introduced, it is probable that the motors still oontain low levels of PCBa. for the purposes of this analysis, it will be mumd that they are contaminated with PCBa at levels in excess of SO ppn. Fifty-four of the fifty-seven 901 continuous miners sold in the United States were located by Versar during the course of a telephone survey. Two of the three machines which could not be located were recently sold on the used1machinery market. It is assuned that these two machines are still in use. Thirty-five of the model 901 miners are currently Idle, fifteen are being used to nine coal, three are in use for maintenance or construction, two are in use on spare sections, and one is being used in a training progrmn at a vocational school.
The 14BU10 loaders were originally sold to eighty-eight different mining operations, the majority of than snail; sixty of these mines have three or fewer of these loaders. Based upon the expected service life of the machines and a survey of thirty-six mines, it is estimated that essentially all of these loaders are still in service.
*AlI figures end information in this Chapter are from Versar, 197B, except where noted.
74
HONS 013286
Itabl* 8.1-1 Da at PCB-Ctaolad Electric Motors In Minina IhdilmiY^
Ibrlilw
Mete Ifeoduoed
RSr----------------Stilt In Swioa with RB Motore
RBMMn par Machine
CUI1 Cbntinuoua Miner
17
9CX Continuous Mier
14KH0 leader
97
5M> a 34
^are Jtotors
3
0<41 *1, '
1 3 2
Ibtal KB Utters
heher of
Ibtal
focal
Geliana of
flaltea of
GalIona
KBa per ttttor KB per Wahlie KB
94
12 H
<3 S
15 115
917 4 |
2, we
(1) Sopt m noted in (31 ani (4) below, U data ia fm Vmv, 1918.
(2) Jpfradaataly 2S0 of thane Mdiiim now have air-cooled actors. (31 19 In uae for production, 4 for other wee
`
<41 Orel Ggeeits of It. A. R. BenwnuU> (Joy MnufacturliR Qomw) at the PCS Ban Regulation Ifteeriiwp, August 29, 1971.
<91 Satieetad, beeed on percentage of loaders that have bem oowertod.
For the past few years, Joy has been converting the motors on the loaders to air-oooling. As shown In Table 8.1-1, there are approximately 250 loaders and 17 spare motors that still contain FCBs.
The motors on the continuous miners and the loaders require occasional topping-off with additional fluid at the mines. The aaount of fluid which is required is small but is necessary for the continued operation of the machines.
8.2 Requirements of the Regulations
The PCB Ban Regulations require or permit the following with respect to the continued use and servicing of PCB-oooled mining machinery motors:
e PCBs may be used in mining equipment until January 1, 1962.
e PCBs may be added to mining equipment motors at the mines until January 1, 1982.
e PCB motors in the loaders must be rebuilt as non-PCB cooled
motors whenever the motors are returned to a service hop for servicing.
e PCB motors on continuous miners may be rebuilt as PCB actors
until January 1, 1980.
-
e Any PCBs used to service or repair PCB-cooled motors mist be stored in accordance with the storage for diapoeal
requirements of Amex III ($761.42).
e processing and distribution in ccamerce of PCBs for purposss
of servicing mining equipment is permitted after July 1, 1979, for persons who are granted an exemption inder TSCA $6(e)(3)(B).
8.3 Cospllance Costs
Continuous Miners: The regulations allow rebuilding of the motors in the two models of Joy continuous miners as PCB motors until July 1, 1979. This deadline could be extended to January 1, 1980, If SPA grants the service shops an exemption from the 'processing* and 'distribution in
76 HOMS 013288
ccamsrce' bans. There are no non-FCB motors that can be used in place of the PCB motors on the continuous miners, and space limitations on the machines prevent converting these motors to air cooling. Since the PCB motors on the continuous miners require rebuilding after about 12 months of service*, all of these machines will have to be retired frcm use within bout a year after the effective date of the ban on rebuilding the motors.
Because of the time limits in the authorization, the market for used 9CM and CU43 continuous miners will virtually disappear. Though this chinary may be technologically obsolete before January 1, 1962, there are undoubtedly numerous small firms which cannot afford the capital investment required for new machinery and thus rely on older used machines to fill their needs. In addition, larger firms often use older machinery for spare equipment or in mine construction. Therefore, the outers will be confronted with equipment that they must retire prematurely, losing the reminder of the machine's useful life or the Income that could result from the sale of the machinery.
Bight companies still use 9CM or CU43 continuous miners for coal production. Six of these companies are relatively mall, with production ranging from 0.7 to 4.2 million tons per year. The other two are large conglomerates with much higher annual productions, in addition, six machines are performing operations other than production. The market value of these machines is roughly $40,000 each (Versar, 1978). Tttsle 8.3-1 ammrlias the costs that would be incurred by each of the companies that still use the continuous miners for coal production. Table 8.3-1 omits the 42 miners that are idle or in non-production uses because the percentage of thorn ulnars that have any value is not known. If each of then has a value
"Testimony of nr. Ed Hamer (Joy Manufacturing Co.) at the EPk PCB Bearings, Chicago, Illinois, July 19, 1977.
77 HONS 013289
TABLE 8.3-1 Cost Inpact of Forced Retirerent of PCS
Ccrrpany No.
Nuriber of Continuous Miners
Model CU43
1* 2* 3* 4* 5 6* 7 8* (Other Uses)
TOTAL
Nunber of Continuous Miners Model 9CM in Service
21
------
C^porUmty Cost Due to Absence of Used Equipment Market
$ 120,000 $ 120,000 $ 80,000 $ 40,000 $ 40,000 $ 40,000 $ 80,000 S 200,000 S 240,000
960,000
*
awll producer production).
(less
than
five million
tons
per year
total ccrpany
78 HONS 013290
of 9*0,000, the additional cost could be as much as SI.7 million. In no case does the economic impact exceed one percent of the value of the coal mined annually by any of the affected companies. It is assuned that replacement machinery could be obtained in time to prevent any inter ruptions in coal production.
Loaders; the PCS motors used on the loading machines can be converted to air cooling at a cost of $3,100 per motor. The motors usually require rebuilding after 18 to 24 months of service*, so most of the motors will be available for this conversion without incurring additional downtime for the machines. Joy Manufacturing Company has stated that its service hop has the capacity to convert all of the PCB motors presently used on loaders to air cooling by the end of 1981. Since the PCBs will be removed from these motors for purposes of disposal, this activity is not affected by the ban on 'processing* of PCBs.
The total coat to convert the 517 PCB motors used on the loaders will be (517 x $3,100 ) $1.6 million. There should be no interruption of coal production due to the conversion program because PCB motors will be allowed to continue in use until January 1, 1982, and most of the conversions will occur when the motors will require normal rebuilding. It is anticipated that maintenance requirements will be greater for the air cooled motors than for the PCB cooled motors, but it is not possible to estimate the total economic iiqpact of the resulting Increased maintenance coats.
Storage Coats; Each mine would be required to store PCBs used for maintenance in a storage area that meets the requironents of Annex III. Joy sells the PCBs in one gallon cans. A non-laaking 55 gallon drue protectad from the rain would meet the requironents of Annex III and would be of sufficient size to store all the PCBs any mine would require. Each of the 96 companies possibly Involved (88 loader owners and 8 continuous miner owners) would need such a storage area. The cost for a barrel and a
Testimony of Mr. Ed Warner (Joy Manufacturing Company) at the ERA PCB Bearings, Chicago, Ulinoia, July 19, 1977.
79
HONS 013291
label may amount to $50 each foe a total cost of $4,800. The recordfeeepirn required for storage areas may increase this cost by a factor of tie to three, for a maxinun expected cost of $14,400.
Exception Application; It is assumed that Joy Manufacturing will apply for an exemption under TSCA $6(e)(3)(9) in order to be allowed to rebuild the loader motors and to be allowed to distribute FCBs to the mines for maintenance. The estimated $1,600 cost of preparing this petition is developed in the chapter on unintentional product contaminants.
8.4 pC8a Controlled by the Regulation
The electric motors in use on mining machines contain about 2419 gallons of FCBs (Table 8.1-1). This is equivalent to toout 27,500 ponds of FCBs with a density of 11.37 pounds per gallon. The regulations will stop the losses of FCBs from these motors by requiring that they be sewpped or rebuilt as air cooled motors by January 1, 1982. There is no infonation in the record on which to base any estimate of the rate at which FCBs are lost from these motors. Therefore, no estimate can be amris of the rxnber of pounds of FCBs that will be prevented fra entering the environment.
8.5 Stannary-Economic impacts
loaders - rebuild motors $$3,100
-
Continuous Miners-premature scrapping of 24 operating machines #$40,000
$1,600,000 960,000
42 other miners #0 - $40,000 Storage costs - 96 storage areas
0 to 1,700,000 14,400
Sumption application
TOTAL
1.600 -------S275T;<HM
(plus up to $1,700,000 for idle miners)
80 MOHS 013292
8.6 Cot Per Pound of PCBs Kept fran the Environment
I it Is assumed that the regulation will prevent the entry into the snvironnent of all the PCBs presently in use, and that all of the KBs would otherwise be lost:
Cost per pound
$2,576,000 to $4,276,000 27,'MO pounds---- `------
$94 to $155 per pond PCBs
61 HONS 013293
9.0 EUBCTICMMaiETS*
9.1 Current Usage
large electromagnets are installed over conveyor belts to 1aa'nn tramp iron from nonmagnetic connodities such as coal and grain. Most of these electromagnets are cooled with 100 to ISO gallons of mineral oil. Hhere increased fire safety was required, the magnets were often filled with PCB based askarel liquid. The three magnet manufacturers <4 used PCBs were:
Stems Magnetics, Cudahy, His. Cries Magnets, Erie, Pa. Dings Co., Milwaukee, His.
Dings Co. stopped using PCBs in mid-1976; the other two manufacturers have not used PCBs since 1971 or 1972. A total of about 250 PCB magnets were manufactured; approximately 200 of these may still be in use in the United States. Most of the PCB magnets are being used in coal mines, coal preparation plants, and In coal-fired generating stations. It is possible, but not confined, that some of the PCB magnets may be used on grain conveyors because of the flamaability of grain dust.
The electromagnets are of ccrapletely welded construction, and very few leakage incidents ham occurred with either oil-filled or PCB-filled magnets. Based on design considerations, electmagnets would be expected to be less likely to fall than transformers. Those leaks that have occurred have been caused by physical abuse or lack of adequate maintenance. Maintenance requirements do not expose workers or the environment to contact with PCBe. Since the magnets are suspended over conveyor belts, diking is not feasible, and any leakage would be uncontrolled. However, PCBs dripping onto the coal would be expected to be destroyed in power generating boilers, thus making the only loss to the environment that of leachate from contaainated coal in storage piles. The total mount of PCBs presently in use in electroeiagnets is probably (200 magnets x 13S gallons per magnet x 11 pounds per gallon x .7 pound PCB par pound askarel ) 207,900 poinds of PCBs.
*All information in this chapter is frcm Versar, 1978, Chapter 9, except as noted.
82
MOMS 013294
9.2 Requlrunts of the KB Ban Regulations
Oontlnued use: PCB-filled electromagnets are defined as a totally enclosed use of FCBs and therefore may continue to be used Indefinitely.
Servicingi Minor servicing which does not require the rmsYiisl of the coil from the casing is authorized until July 1, 1984. Removal of the coils is prohibited.
Sale of PCBst Banned after July 1, 1979, unless CPA grants an exception fran the 'distribution in commerce" ban.
Reclaiming PCBs; for reuse by the owner of the PCB transformer
or electromagnet! authorized, for sale: banned unless an exmaption is
granted by EPA.
.
Disposal! By incineration in an approved high teaperature PCB Incinerator. Drained PCB electromagnets may be disposed of in approved chemical waste landfills; the liquids drained frcm the magnets must be incinerated in approved incinerators.
9.3 Post Impacts of the PCB Ban Regulations
Continued use: Hie regulations inpose no additional requiraments beyond the labeling previously required by the PCB Disposal and Marking Regulations (EPA, 1978a).
Ban on manufacture! Hie ban on the manufacture of new PCB magnets is not expactad to have a significant iapect on either the manufacturers or uasrs of these magnets. According to the magnet manufacturers, the PCB electromagnets could be replaced with oil-filled units at an average coat of $8,000 per magnet. However, the use of mineral oil in these applications would significantly increase the fire risks. Hie manufacturers regularly furnish silicone-filled magnets for use where more effective fire resistant characteristics are required than those achievable with mineral oil. Such silicone-filled units are 40 to 50% more expensive
83 HONS 013295