of and 1937American Society
Heating
Ventilating Engineers Guide,
Fig. 1. Chart for Estimating Dollar Value of Heat Loss from Bare Iron Pipes. (See Table l)a
This chart is based on 100 linear feet per 1000 hours. For fractions or multiples of these factors, multiply by proper percentage. `
heat equivalent to more than a ton of coal per year shows the necessity for insulating such surfaces.
STEAM AND HOT WATER LINES The conductivities of various materials used for insulating steam and hot water pipes are given in Table 5. . In this table the conductivities are given as functions of the mean temperatures or the mean of the inner and
670
36--Chapter
Insulation of Piping
* Table 1. Heat Losses from Horizontal Bare Iron Pipes
Expressed in Btu per linear foot per degree Fahrenheit difference in temperature between the pipe and surrounding still air at 70 F
Nominal Pipe Sice.
(Inches)
:m
H
l
.1M 2
2H
3
3A
4
4H
5 6. 8 10 12
120 F
Hot Water
150 F
180 F
210 F
227.1 F (5 Lb)
Temperatube Difference
50 F'
80 F
110 F
140 F
157.1 F
0.543 0.660 0.791' 0.979 1.09
L34
1.58 1.88 2.13' 2.36 2.60 2.87 3.39 4.32 5.32 6.25
0.573 0.690 0.829 1.02 1.15 1.40 ' 1.67 1.99 2.24 2.50 2.75 3.02 3.56 4.55 5.61 . 6.62
'
0.605 0.729 0.878 1.087 1.220 1.491 1.778 2.100 2.380 2.650 2.920 3.200, 3.775 5.050 5.925 6.995
0.638 0.762 0.920
1.15
L29
1.58 : 1.87 2.22 2.51 2.78
3.08 3.38 4.01 5.14 6.34
7.46
0.656 0.781 0.953 1.184 1.335 1.637: 1.937 2.301 2.585 2.873 3.170 3.493 4.115 5.270 6.551 7;670
Steam
297.7 F (50 Lb)
337.9 F (100 Lb)
227.7 F
267.9 F.
0.742 0.886 1.084 1.345 1.520 1.866 2.215 2.641 2.972 3.312
3.655 4.030 4.755 6.120 7.592 ,8.900
0.796 0.955 " 1.166 1.450 1.640 2.015 2.388 2.853 3.215 31582 3.956 4.368 5.153 6.635 81245 ' 9.670
Table 2. Heat Losses frosI Horizontal Bare Copper Pipes
Expressed in Btu per'linear foot per degree Fahrenheit difference in temperature between the pipe at S10 F and surrounding stiU air at 70 F
Nominal Pipe Rites
(Inches)
Vi %
i
m m
2
Outside Diameter
(Inches)
0.625 0.875 1.125 1.375 1.625 2.125
Temperature Dippehsncx
140 F
0.405 0.478 0.550 0.623 0.695 0.841
Nominal Pipe Size
(Inches)
VA
3
3A
4 5
6
Outbids Diameter (Inches)
2.625 3.125 3.625 4.125 5.125 6.125
Temperature Difference
140jF
0.986 1.131 1.276 1.422 1.713 2.004
Table 3. Radiating Surface per Linear Foot of Pipe
Nominal Pipe Size . (Inches)
A H
l
m ia
8urpach Area
(Sq Ft)
0.22 0.275 0.344 0.435 0.498
'
Nominal ! Pipe Size
(Inches) .
' -2
2A
3
3A
4
Surface |
Area
U
(Sq Ft) . |
0.622
0.753 0.917 1 1.047~
1.178
Nominal Pipe Size (Inches)
5 6 8 10 12
Surface Area
(Sq Ft)
1.456 1.734 2.257 . 2.817 3.338