Document zQ4Kk1yoVz2VexRVzYVyVjnra
ZONOLITE
CONSTRUCTION PRODUCTS DIVISION
WRG 001520
v. -if PLAINTIFFS V,v |{ EXHIBIT
" *11 WRG-719
-- *
->
T. P.' Felt
`-
Mi :
November 5, 1973
.
FROM: SUBJECT:
vX. J. 3ourke
CC: T. F. Egan
R. 0. 'deBastian
Fitzgerald Letter of 1C/V73 . W. J. Sinaccre
on Sprayed Fireproofing
I had a meeting with Joe Fitzgerald on 10/18/73 at his office in City Hall in regard to this letter.
We went over our new physical properties report which you sent out to us as Bulletin .^31* I left copies with him for future reference. The city is net outlawing Mcno-Kote for use in plenums. They are only concerned with using sprayed fireproofing where it can be knocked off by workman at some future time. He is thinking of the elevator repair man walking on some beams in a shaft while repairing the elevator. He is also concerned with fireproofing left exposed in stairwells where ordinary use of these stairs leads people to try to rub off or knock off the Mono-Kote for kicks.
N'hat might have brought this on is when the employee cf the John Hancock Center tried to burn down the building. Joe went to inspect the damage and found in the mechanical rooms that the fireproofing had either fallen off or been knocked off the steel by the employees and not the fire. He mentioned this to me after it happened about a year ago.
He has no objections if we seal the Mono-Kote with Caraweld "C" or Thoroseal as .long as we do not lose the fire rating and it gets a hand surface. Joe also mentioned that a new fire prevention code is coming out shortly to be put into ordinance form by the City Council. I will try to get you a copy if possible in advance to see how it may relate to us in the sprayed fireproofing business.
/ $??e >' i
r. ~
i* '>
'" v'.-.r
October 4, 1973
1 Memorandum:
.i
'
-v i-
: :-1 ; v -':J To: ? : 1 7V.. .; . }- *,," ' n . rv.' . *"
- Mr. George Wienold ; cChhi<ief Plan Examiner
Architectural Plan Examiners
> 1 *Vi * J- ..
*- -V.'
4 '
;t
J .'-
Fire Prevention Plan Examiners
. - I
Patrick Noonan Chief Code Enforcement Officer
Austin Sullivan Chief Iron Inspector
From:
Joseph Fitzgerald Commissioner of Buildings
Re: Sprayed Fire Proofing
Section 81-14 of the Municipal Ordinance requires that all ducts be made of sheet metal or other approved materials. Various materials have been approved as a substitute material such as concrete, concrete block, etc.
/ Sprayed fire proofed steel however is not one of those materials [ . I approved and is not to be used as an exposed- surface in a duct. \
, >
Please see to it ;that the mechanical and architectural plans. .....
correspond one to the other in this regard and that no sprayed . -
. fire proofing be allowed in the ducting systems.
, -c .s.
* -*
Because of the erosion that can be expected over the many years
of a building's expected life span sprayed fire proofing is not to
be allowed in any areas where it may be subject to erosion factors ; C
examples would be in stairwells, elevator shafts, mechanical;.../ . v
4
;,.. shafts and In mechanical or equipment rooms at locations frequented'I*
by maintenance personnel.
'