Document zNYo2kj73bezyeZM9v9m6z73
USPHS/CDC/NIOSH/DPSE
iN] 304 :i iMG CONTROL TECHNOLOGY BRANCH
CONTROL TECHNOLOGY ASSESSMENT OF ASBESTOS FIFE LAGGING REMOVAL USING TWO NEGATIVE-AIR GLOVE BAG REMOVAL METHODS BY: BRUCE HOLLETT AND PHILLIP FROEHLICH
NAC SYKll&fiCIiIUM MAM 311, 1989
Background: Many workers are exposed to asbestos: Construction workers - Demolition, Renovation, Sprinkler Fitters, Sheet Metal, Roofing, etc.
Operations and Maintenance Plumbing, HW?, Electrical, House Seeping, etc.
Building Occupants - Office Workers, clients, students, customers, public, etc.
We proposed a pilot study in 1983 to assess need for research in the asbestos removal industry.
PILOT STUDY , 1984
PROTOCOL PEER REVIEW SPRING 1985
FOUR SCHOOL STUDY SUMMER 1985
I
WORKER PROTECTION ft ENVIRONMENTAL PROTECTION
CONTROL AT THE SOURCE THE BEST APPROACH
CONTAIN THE ASBESTOS BEFORE IT IS RELEASED INTO THE ENVIRONMENT.
JOINT PROJECT WITH EBl -SO
OF 1985
EBi PROVIDED FUNDING FOR ANALYSIS
niosh added equation of clearance and
EVJlKnON OF EFnCACY
HWBUI0000908
SOURCE CONTROLS
FOR WORK AND ENVIRONMENT FIRST PRIORITY GLOVE BAGS
WIDELY USED/OFTEN ALONE
Glove Bags were chosen as the first priority because they were widely used by the construction trades as well as by the O&M workers. They are often used as the only control measure. They seem to represent an economical source control technology.
HWBUI0000909
GLOVE BAG PHASE
OBJECTIVES IVAUME WORKERS' EXPOSURE
DURING GLOVE BAG- REMOVAL EVALUATE CLEARANCE SAMPLING
METHODS EVALUATE THE EFFICACY OF THE
GLOVE BAG REMOVAL METHODS
EmiXWTE WORKERS * By Personal Breathing Zoao Itall Ihnr Seq. * Half 4mj activity -> Monring and Afternoon * On* Start Ibnn sample on each wsntar AM 6. IM
EmmtXE CLEARANCE SAMSUNG METHODS * By comparing PCM * TEM- analysis talk metkods. I will describe acgressifeaad. nonaggmaiive* * Replicate sample* worn* taken on polycarbonate & cellulose ester media for tke* two* analyst*
EmUUATE THE EFFICACY OF THE GLC9FE BAG REMOVAL * By determining if tke peel tab me lower bf collecting samples' before* anA after-
SAMPLING STRATEGY A
OUTDOOR AMBIENT PRE-REMOVAL - 2 METHODS PERSONAL BREATHING ZONE
TWA AND SHORT TERM AREA DURING REMOVAL . POST REMOVAL - 2 METHODS
OUTDOORS AMBIENT *hJied 25 mm Cellulose Ester - foil wrapped Cast pomps at 3.5 1pm for the foil shift
FS ft POST REMOVAL -(First the room Is sealed off) * Two eight hoar sequential sampling periods >lst Non-Aggressive - Ihken In a dry quiet room per EBh Bine Book guidance. > Aggressive - Ikkan in a dry room with Mowers Blow down room wife leaf Mower - 3 passes keep air moving wife oscillating fens * Triplicate Replicate sampling - 25 ft 37mm
AREA DURING RfMCK&L * Duplicate Replicate sampling - 25 ft 37mm
PBZ*s 25mm cellulose esters in foil wrapped cowls
HWBUI0000911
PRE AND POST REMOVAL
SAMSUNG EQUIFV 1MNT
filters in opes bced cassettes and
MOUNTED ON A 9 POSITION S&MHJNG RING: 3 * 37mm cellulose ester 0.8 a 3 - 37bb |d|jcnkoaiteMB> vlRr t 5.0 m caBriow aster butao 3 . 25mm cellulose aster Mo
SAMPLING PUMPS: 6 cassettes on a maaifbld, neb witk 33 Ipm artfleas wite higk pomreO GE ami Gast ranmm. pomps^ 3 cassettes oo dopoot P4000 pomps
THREE MEHODS SIDE BY SIDE IN TRIPLICATE.
HWBUI0000912
OTHER MONITORING
AMBIENT, SHORT TERM, EAM's Ambient outside samples on paired 25mm cellulose ester filters with 2" foil wrapped* cowls. ,, A 15 minute short term breathing zone sample on each woifcer, morning and. afternoon.
EfcM MEASURED RELATIVE LEVELS ONDf
HWBUI0000913
REMOVAL ACTIVITY
MONITORING Morning and afternoon sequential breathing zone and replicate area samples collected at 2.5 to 3.5 1pm.
Filters moKBtai in open freed cassettes.
Areas mounted on 4 position ring * 2 - 37 mm Polycarbonate 0.4u *2-25 mm cellulose ester 0.8u in aluminum foil wrapped 2"cow!s
DUPONT P4000 SAMPLING KJMPS
HWBUI0000914
His is a shot of the tm samflsf equipment. In the forefwitni the sampling tree used for centra! rmm sampling mi outside areas. In the teckgfovfid the Mobile Cart sampling tens used In the vicinity of the vioik activity. MMS are bated not to both of these imping trees. Th<wy provided real-time monitoring.
HWBUI0000915
TYPICAL SAMPLING LAYOUT
STAIRWAY i INTERIOR AREA SAMPLER WORKER gj MOBILE CART R POLY FLAP DOORWAY
AMBIENT AIR SAMPLE HUNG OUT UPSTAIRS
WINDOWS
HWBUI0000916
HWBUI0000917
VIDEO CONVENTIONAL
GLOVE BAG METHOD STUDIED
NIOSH CONTROL TECHNOLOGY ASSESSMENT A brief video presentation of the types of woik activities and equipment associated with the asbestos removal methods studied. Also a illustration of the monitoring and site preparations for this control technology study.
HWBUI0000918
FINDINGS WORKING CONCENTRATIONS
i*Z AND AREA MONITORING
r
HWBUI0000919
TWA EXPOSURE RANGES FOR
FOUR WORKERS AX FOUR SITES 14 &KS
FIBERS/CUBIC CENTIMETER (f/cc)
I
!1 I
\
WORKER A, B, C, D I EACELTTY ! t.2,3,4 NIOSH 7400 METHOD (B RULES)
Hen joq see a summary of the four workers* TWA exposures at all four sites.
Each vertical entry shows the range. Max and Min, and Mean for the specified worker and school.
Note that nearly all of the Dally TWA*s were above .1 f/cc and many were above 3. f/cc
The percentages are shown In the next slide.
HWBUI0000920
WDffiKER HEEMETOS ZONE FINDINGS
DAILY TWA LEVELS: 37 / 51 (73%) ARE ABOVE 0.1 f/cc *30 / 51 (58%) ARE ABOVE 0.2 f/cc
FRERYRATION VS REMOVAL LEVELS: PREPARATION AMG 0.02 f/cc REMOVAL WORK AMG 0.35 f/cc
SHORT TERM LEVELS: HIGH> 9.3 f/c 16 / 69 (23%) ARE ABOVE 1.0 f/cc
N10SH 7400 METHOD (B BUIES)
Daily TO*S reflect i significant exporan potential above recommended control limits. Activity related exposve levels sbovr that the removal exposures are an order of magnitude higher than the preparation mode exposures. Short Term levels were peaked by the anplanned episode with a 9.0 f/cc. Also die 1.0 f/cc level was exceeded 23% of the time overall.
HWBUI0000921
FACILITY #1 milY TWA
N10SH 7400 (B RULES)/TEM YAMATE
WORK DAY
# 4 TEM
# 4 PCM # 3 TEM
# 3 PCM 1=35"
# 2 TEM
# 2 PCM # l TEM # 1 PCM
=i-A TORKER -
HUB WORKER _ ^3C WORKER m WORKER
0.0 0.4 0.8 1.2 1.6 2.0 2.4 2.8 3.2 3.6 4.0
PCM FIBERS/CC -TEM Asbestos Structure/CC Note: Day #1 afternoon B end C samples overloaded
Note: Day one workers B and C samples were overloaded with particulate. Unable to coant.
The TEM analysis was done on the same Cellulose Ester 25mm Alter that the PCM Personal Beathlng Zone analysis was. Due to limited support these are toe only worker 1BZ samples done by TEM.
HWBUI0000922
WORKER GLOVE RAG EXPOSURE OBSERVATION & CONCLUSION
WORKERS WITH LIMITED TRAINING AND EXPERIENCE HAVE EXPOSURES ABOVE NIOSH RECOMMENDATIONS AND OSHA CRITERIA LEVELS.
i GLOVE BAGS ALONE DO NOT SUFFICE IN CONTROLLING EXPOSURES UNDER THESE CONDITIONS.
It is prodent to use respiratory protection doling any glove beg operation doe to potential leaks.
OSHA permits the ose of high efficiency, air purifying respirators for asbestos; However, NIOSH recommends that type C positive pressure, snppiled air respirators be osed if levels exceed the REL.
As a minimom it is appropriate to seal off the air ducts and doorways to avoid contamination from an accidental release doling glove bag work.
More extensive work should likely Include the nse of decontamination facilities and negative air.
HWBUI0000923
Glove Bag Evaluation Status
Negative Air Technology
Two types of negative air glows enclosures have been studied. The AERO-PUB CAPSULE manufactured by Aerospace America, Inc. and a Custom Fabricated Glovebag designed to operate under negative pres sure conditions. Preliminary PCM results would indicate that both methods produced adequate control to meet the OSHA PEL and the NIOSH REL. However, TEM analysis of the post removal aggressive sampling have shown many thin fibers. Pfe are awaiting TEM analysis of some of the working area samples to quantity the workers actual fiber exposure levels.
HWBUI0000924
VIDEO OF NEGATIVE-AIR
GLOVE BAG METHOD STUDIED
NIOSH CONTROL TECHNOLOGY ASSESSMENT A brief video presentation of the types of work activities and equipment associated with the asbestos remora] methods studied. Also a illustration of the monitoring and site preparations for this control technology study.
HWBUI0000925
Negative Air Glovebag
PCM Results BELOW LOD
LOD FIBERS/CC BY NIOSH 7400 METHOD
x 1/1,000
10
8
6
4
2
0 BBZ b-2
IA a-2
QA b-2
EX b-2
SAMPLE TYPE
SSHArea A ES3 Area BAG E23Area D
AERO-PIPE CAPSULE/AEROSBICE AMERICAJNC.
These results are aD below the LOD and therefore differences reflect the sample volume. The lower less than concentrations representing longer times for sample collection. Two short term samples of 20 minute duration were taken in area D. The also were below the LOD around < 0.05 f/ec.
We hare received preliminary results of our TZM on these personal breathing zone samples. They indicate higher concentrations of asbestos that most be confirmed by a more complete analysis which Is pending. The pre and post TEM analysis shows many fine fibers outside tike PCM range.
HWBUI0000926
Negative Air Glovebag
PCM BELOW LOD is TEM as/cc
TOTAL FIBERS BY NIOSH 7400 METHOD n TEM 0.150-
0.120-
J3S9
0.090-
gi
P-B&C^D
0.060 -
i
0.030 -
1
0.000 FRZ TEM IA TEM (K TEM
SAMPLE LOCATION AND TYPE AERO-FIFE CAPSULE/AEROSBUCE AMERKAJNC.
EX
PCM results an presented to the left of TEM for: Personal Breathing Zone (PBZ), Interior Area (IA), Outer Area (QA) and the HEKA Exhaust (EX).
The PCM data represent two samples each. The TIM data is from an anetehed half of one of the two 0J n MCE filter samples used for the PCM. Oar laboratory had poor etching results.
The other half from the remainder of the PCM hare been submitted to the same laboratory which did the pre and post analysis to eliminate this TEM inteiiaboratory variability factor.
Negative Air Glovebag
PRE and POST TEM as/cc
AHERA TEM METHOD as/cc 0.8
0.6
0.4 .26
02 -.031
0.0 Pre n
.00026 Arab n*15
.78 jiggggg jiff ip iiiiii
rm
ilall Hill'.074
Post a*5
SAMPLE LOCATION AND TYPE
mA ^ B&C Ambient .. AERO-PIPE CAPSULE / AEROSPACE AMERICA,INC.
1 !
i
l i i i
Fire pre mod post abatement samples were taken for six and a quarter hours using aggressive sampling in a poly enclosure at eight to ten liters per minute for a minimum sample volume of 3000 liters.
Both the post sample sets are significantly higher than pre using a t-test on tn(concentration) with p-values 0.0014 for area A and 0.0013 for area B/C
The 15 outdoor ambients were at or below 0.0012 as/cc. As shown above all of the mean values for both area A (0.26 - 0.78) and for area B/C (0.0130.074) well above this ambient level.
HWBUI0000928
PLOT OF STRUCTURES
BY LENGTH AND DIAMETER
. . r.- - * *
STRUCTURE LENGTH, MICROMETERS
STRUCTURE DIAMETER, MICROMETERS AHERA TEM METHOD/ AERO-PIPE
This slide shows the size distribution of asbestos structures from all fifteen outdoors ambient samples. The region outlined in tike upper right quarter defines the ranges risible to PCM analysis for a 3:1 and 5:1 aspect ratio.
Clearly there would not he a large mnmher of PCM fibers on any one filter. The mean concentration for these samples was 0.0012 as/cc.
------ PCM METHOD 7400 . * I CHRYSOTllE M * A I AMPHIBOLE S a L` I AMBIGUOUS r C C I AMBIGUOUS C WW 1 NON ASBESTOS M
I CHRYSOTllE r 1 CHRYSOTllE C 0001 AMPHlBOlE u I AMBIGUOUS 0 N N N I NON ASBESTOS r V V V I NON ASBESTOS C
I CHRYSOTllE B x x x I AMPHlBOlE f DOOI AMPHlBOlE C Z Z Z I AMBIGUOUS M _ v V V 1 NON ASBESTOS B
PLOT OF STRUCTURES
BV LENGTH AND DIAMETER
STRUCTURE LENGTH, MICROMETERS
-- --,,--............................. i
001
0 032
01
--i 0 32
i ................... 1.0 3.2 <0 0
RE AREA A
STRUCTURE DIAMETER, MICROMETERS AHERA TEM METHOD/ AERO-HPE
This slide shows the size dlstribntion of asbestos structures from all fire pre-removal aggressive samples. The region outlined in the upper right quarter defines the ranges visible to PCM analysis for a 3:1 and 5:1 aspect ratio.
Cleaiiy there would mot be a laige number of PCM fibers on any one filter. The mean concentration for these samples was 0.26 as/ce.
--- 7*00
1 chrysotilc m I Ai*HIB0LE B t AMBIGUOUS F C C I AMBIGUOUS C * * I HON ASBESTOS M
iI CbnHRRTYWSOl ITLlLlf F
-I---C--H--R-Y--S--OTTILLE| C OOOI AMPHIBOLE t AMBIGUOUS m n n t mon'amestos F v y I NON ASBESTOS C
PLOT OF STRUCTURES
BVT LENGTH AND DIAMETER
STRUCTURE LENGTH, MICROMETERS
-- ,................... ............ . i - -- ............... .. ...................................
001
0.032
0.1
0.32
1.0
3.2
10.0
POST AREA A
STRUCTURE DIAMETER, MICROMETERS AHERA TEM METHOD/ AERO-PIPE
This slide shows the size distribution of asbestos structures from all five post-removal aggressive samples. The region outlined in the upper right quarter defines the ranges risible to PCM analysis for a 3:1 and 5:1 aspect ratio.
Clearly there would not be a large number of PCM fibers on any one Alter. The mean concentration for these samples was 0.78 as/cc.
------ PCM METHOD 7*00 * I CHRYSOTILE M A * I AMPHIDOLE B e e i ambiguous r C C ( AMBIGUOUS C r W t NON ASBESTOS M
1 CHRYSOTILE F a I CHRYSOTILE C 0 0 1 AMPHIB0LE M o a 1 AMBIGUOUS 8 ,, H N I NON ASBESTOS r r t 1 NON ASBESTOS C
a 1 CHRYS0TI E B
rx x a I AMPHlf cO D O I AWPMIl
VZ ZV VZ 1I AMBIC
M T0S 8
EFFICACY CONCLUSIONS NEGATIVE AIR METHODS THIS UNIT MET THE OSHA PEL AND NIOSH REL FOR CONTROL OF WORKERS EXPOSURE TO ASBESTOS. FURTHER STUDY IS NEEDED TO DETERMINE THE SOURCE OF THE FINE ASBESTOS FIBERS SEEN IN TEM ANALYSIS.
AERO-HPE CAPSULE/AEROSRCE AMERICAJNC.
I
HWBUI0000932
Negative Air Glovebag
PCM Results vs TEM as/cc
PCM TOTAL FIBERS/OC BY NIOSH 7400 METHOD x 1/1,000
i1
1! 1
i1
-I 111
1f: t 1E M177, 1 TTrm
1--------------------- 1 -US
m41 1
1 1 ' 1 I^ 1
Iw,
PBZ n*2 vs TEM IA n-2 vs TEM QA n! l vs TEM
SAMPLE TYPE
Rem
Prep me Rem EUD Rem
CUSTOM NEGATIVE-AIR RAG/ INTERSCIENCE RESEARCH
PCM results are presented to toe left of TEM for: Personal Breathing Zone (PBZ), Interior Area (IA), Outer Area (QA). Area B samples were taken during removal activity. Area C Prep samples were taken daring Preparation activity and C Rem were taken daring removal activity in area C.
The PCM data represents two samples each. The TEM data is from an inetched half of one of toe two 0.8am MCE filter samples used for the PCM. Since this TEM method may nndereonnt embedded fibers, toe other half have been submitted to toe same lab that performed etched pre and post TEM analysis.
Negative Air Glovebag
PCM Results
TOTAL FIBERS/CC BY NIOSH 7400 'METHOD x 1/1.000
1BZ "2
IA n-2
QA b-2
SAMPLE TOPE
E23B Real SIC Prep gS3C Rem EH1 D Rem
CUSTOM NEGATIVE-AIR BAG/ INTERSCIENCE RESEARCH
These results an all below the OSHA PEL and NIOSH REL. TEM analysis ban shown there are asbestos structures present here although not as numerals as In die other study. It is noted that these PCM results would hare indicated higher levels in Oils survey. Each abatement environment well present a different relationship between the PCM results and the actual fiber distribution as shown by TEM.
HWBUI0000934
Negative Air Glovebag
FRE and POST TEM as/cc
AHERA TEM METHOD as/cc x 1/1,000
1.0103-------------------
_________00'65 i
Pre n5
100058
.......
Amb n*I5
vQvVvV'. =L Best n*5
SAMPLE LOCATION AND TYPE
BUSC AND D E23Ambient i15 ESJC BD CUSTOM NEGATIVE-AIR BAG/ INTERSCIENCE RESEARC
five pre and post abatement samples were taken for six and a quarter boars using aggressive sampling in a poly enclosure at eight to tea liters per minute for a minimum sample volume of 3000 liters.
Area D post samples are significantly lower than the pre. Using a t*test on ln(concentration) yield ? p-values of 0.10 for area C and 0.0001 for area D*
The 15 outdoor ambients were at or below 0.0011 as/cc. As shown above all of the mean values for both area C (0.010 - 0.0005) and area D (0.010 0.014) wore flighty above ambient load.
PLOT OF STRUCTURES
BY LENGTH AND DIAMETER
STRUCTURE LENGTH, MICROMETERS-:
10 0
5b
il H
&1 8
ia
0 S6
0 Ul 0 0J2 0 i
0 J2 10 AMBIENT
J2
10 0
STRUCTURE DIAMETER, MICROMETERS .. AHERA TEM METHOD/ CUSTOM GL0VEBM2
This slide shovrs the size distribution of nsbestos structures from nil fifteen outdoors ambient samples. The region outlined in file upper right quarter defines the ranges risible to PCM analysis for a 3.T and 5:1 aspect ratio,
Cleariy there would not be a large number of PCM fibers on any one filter. The mean concentration for these samples was 0.0002 as/cc.
----- PCU METHOD 7400 . 4- I CHRYSOTllE U a & I AUPHIBOLE B a a i ambiguous r c c i awoiguous c H w I NON ASBESIOS U
. I CKRYSOIIIE r
t CKRYSOTILE C
0 0 0 I AMPKIBOLE M
a N
a NH
I I
AMBIGUOUS B NON ASBESTOS
V V I NON ASBESTOS
o o I CHRYSOtitC U x * * 1 AMPHlBQlE 1 O O I AHPIIIBOIE C l l i. I AMtliGUOUS U V v V I NON ASULSIOS
PLOT OF STRUCTURES
BY LENGTH AND DIAMETER
STRUCTURE LENGTH, MICROMETERS
10 0
56
i 2 i 8l 00 56
0 01
0 0J2
01
0 J2 - -.*1 0
ri 2
IRE AREA C/D
i0 0
STRUCTURE DIAMETER, MICROMETERS AHERA TEM METHOD/ CUSTOM GLOVERAG
This slide shom the size distribution of asbestos structures from all fire pre-removal aggressive samples. The regioB outlined In the upper right quarter defines the ranges visible to PCM analysis for a 3:1 and 5:1 aspect ratio.
Clearly there would not be a huge somber of PCM fibers on any one filter. The mean concentration for these samples was 0.01 as/cc.
------ PCM METHOD 7400 I CHRTSOTILE u A A I AMPHIBOLE B B B I AMBIGUOUS F C C I AMBIGUOUS C * w t MOM ASBESTOS M
I CHRTSOTILE F a I CHRTSOTILE C OOOI AMPHIBOLE U I AMBICUOUS B N M N I NON ASBESTOS F v r v t NON ASBESTOS C
a I CHRTSOTILE B * x x I AMPHIBOLE F OOOI AMPHIBOLE C X Z Z I AMBICUOUS U V V V I NON ASSES IOS U
PLOT OF STRUCTURES
BY LENGTH AND DIAMETER
STRUCTURE LENGTH, MICROMETERS
J 01
0 0.32
0 I . 0 J2
I0
J 2 ' ' ;0 J
POST AREA C
STRUCTURE DIAMETER, MICROMETERS AHERA TEM METHOD/ CUSTOM GLOPEGAB
This slide shows (he size distribution of asbestos structures from all fire post-removal aggressive samples. The region outlined in the upper right quarter defines the ranges risible to PCM analysis for a 3:1 and 5:1 aspect ratio.
Clearly there would not be a large number of PCM fibers on any one Alter. The mean concentration for these samples was 0.0055 as/cc.
------ PCM METKOO 7400 ICMRrSOTIlE U a IAMPHIBOlE B a a IAMBIGUOUS F C C t AMBIGUOUS C WW I NON ASBESTOS U
I cwrsomc F I CHRTSOHlE C 0 0 0 I AMPHIBOLE M a e I AMBIGUOUS B N N N I NON ASBESTOS f v v v I NON ASBESTOS C
a I CHRTSOmC U x xx I AMPHIB0LL l Q O O I AMPHIBOlE C Z J J I ANBIGUOU5 U V V V I NON ASBIS I US U
EFFICACY CONCLUSIONS NEGATIVE AIR METHODS
t si
THIS UNIT MET THE OSHA PEL AND NJOSH EEL FOR ` CONTROL OF WORKERS EXPOSURE TO ASBESTOS.
FURTHER STUDY OF THIS CONTROL, UNDER VARIED WORK CONDITIONS, IS RECOMMENDED.
CUSTOM NEGATIVE-ABL*WG/ INTERSCIENCE RESEARCH.
HWBUI0000939