CHAPTER 18
1957 Guide
/'
These maximum demands were measured by an attachment on the con densation meter, and therefore represent the amounts of condensation passed through the meter in the highest hours, rather than the true rate at. which steam is supplied. There might be slight differences in these two quantities due to time-lag and to storage of condensate in the system, but wherever this has been investigated it has been found to be negligible.
Table 9. Building Load Factors and Demands of Some Detroit Buildings
Building Classification
Load Factor
Lb of Demand peb (Houb) (Sq Ft op Equivalent Installed Radia tor Subpace)
Theaters..........................................................................................................
0.318 0.316 0.287 0.263 0.255
0.238 0.223 0.203 0.158 0.138 0.126
0.184 0.207 0.217 0.209 0.225
0.182 0.248 0.158 0.152 0.145 0.151
The load factor of a building is the ratio of the average load to the maximum load and is an index of the utilization. Thus, in Table 9, the theaters, operating for short hours, have a load factor of 0.126 as compared with the figure of 0.318 for clubs and lodges.
REFERENCES
I Comfort Healing (American Gas Association, 1938).
' Are Automatic Air Shutters Justified on a Gas-Fired Conversion Burner? by W. M. Myler, Jr. and H. W. Nelson (ASHVE Transactions, Vol. 55,1949, p. 111).
* Efficiency of Bituminous-Coal-Burning Space Heater, by J. W. Tieman and F. L. Bagby (ASHVE Transactions, Vol. 57, 1951, p. 89).
4 Heat Losses and Efficiencies of Fuels in Residential Heating, by R. A. Sherman and R. C. Cross (ASHVE Transactions, Vol. 43, 1937, p. 185).
5 The Stoker-Fired Warm-Air Furnace in the Research Residence, by S. Konzo (University of Illinois, Engineering Experiment Station, Circular 39, 1939, p. 98).
* Performance of a Hot Water Heating System in the 7= B = R Research Home at the University of Illinois (University of Illinois, Engineering Experiment Station, Bulletin No. 349, Jan. 4, 1944).
7 Fuels and Burners (University of Illinois, Small Homes Council, Circular G3.5, July 1949).
* Investigation of Oil-Fired Forced-Air Furnace Systems in the Research Re8'" dence, by A. P. Kratz and S. Konzo (University of Illinois, Engineering Experiment Station, Bulletin No. 318, Nov. 7, 1939).
5 Graphical Method of Calculating Heat Losses, by Paul D. Close (ASHVE Transactions, Vol. 49, 1943, p. 345).
10 House Heating (Industrial Gas Series, American Gas Association, Third Edition).
II Report of Commercial Relations Committee (Proceedings, National District Heating Association, 1932).
17 The Heat Requirements of Buildings, by J. H. Walker and G. H. Tuttle (ASHVE Transactions, Vol. 41, 1935, p. 171).
CHAPTER 19
WARM AIR HEATING SYSTEMS
Forced Warm Air Systems; Air Distribution; Supply Outlets and Return Grilles; Simplified Methods of Design for Perimeter Systems of Loop, Radial, and Ex tended Plenum Types; Return Duct System for Perimeter Installations; : Inside Wall Delivery Systems; Design.of Large Systems; Automatic Controls; Adjustment of System; Warm Air: Ceiling Panel Sys tems; Summer Operation; Gravity Warm Air Systems ' :.
WARM air heating systems may be conveniently divided into two classifications depending upon the manner in which the motive power for circulating the warm air is supplied. In gravity systems, the motive head is due to the difference in weight between the heated air leaving the top of the furnace casing and the cooler return air . entering the bottom of the casing. In a forced warm air heating system, all or part of the motive head is supplied by a fan. Although a great many gravity warm air heating systems are in use, only a limited number of new gravity installa tions are now being made. Emphasis will therefore be placed upon-the design and installation of forced warm air heating systems.
FORCED WARM AIR SYSTEMS In forced warm air heating systems, the air circulation is effected by motor-driven centrifugal fans, commonly referred to as blowers. The ad vantages of forced air systems are:
1. The furnace may be placed in any part of the structure. 2- Distribution ducts can be made small enough to be inconspicuous and out of the way, or be completely concealed from view where desired. ?f ^*.rculation of air is positive, and in a properly designed system,, can be con trolled in such a way as to give a comfortably uniform temperature distribution. 4. Humidity control is readily attained. 5. The air may be cleaned by filters or other means. . . 6. If properly designed or suitably adapted, the same air distribution system can he used for summer cooling as for winter heating.
us.of the fan permits flexibility in the location of supply and.return grilles as required to obtain proper distribution of air for comfort.
8. Ventilation air may be positively introduced and conditioned.
The construction features of forced warm air furnace units' and the unction and selection of the various parts of a system are discussed in l-'hapter 16 and other publications.1
AIR DISTRIBUTION
..The conditions of comfort obtained in a room are influenced greatly by the type of supply outlet used, and the locations of the supply outlets and tetum grilles. In general it has been found that changes in the type, air