Document z7kw2RM6bxZLj1mrmmax1Man
total vent area 3 Draft curtains increase vent effectiveness
because they increase stack height and confine heated gases 4 Several small vents rather than a single vent of equal area are more effective, be cause gas temperatures decrease rapidly as the gas travels away from the fire 5 Roof height will not affect vent effective ness within the normal ranges of height
Smoke does not necessarily have a very high temperature High temperatures are only created in fairly free-burning fires Venting installed for life safety may not be too effective, therefore, as temperatures high enough to produce the necessary stack effect
may not be present Smoke could also flow under draft curtains and other obstructions until an adequate draft is created
So many variables affect the burning of combustible material that no exact mathemat ical formula can be used for computing the amount of heat venting required Vent sizes and ratios have therefore been developed from tests and experience, using theory only for guidance The National Fire Protection Association, however, has developed a guide for smoke and venting from which venting requirements may be estimated (NFPA Stand ard No 204, Smoke and Heat Venting Guide) Also, there are a variety of prefabricated vents available on the market They can be de signed to open automatically at predeter-
BEHAVIOR OF HOT OASES UNDER FLAT ROOF
CURTAIN BOARDS 8 RET
BEHAVIOR OF HOT GASES UNDER MONITORED AND CURTAINED ROOF
FlC 35-6 -- Drawings (not to scale) show how a monitored and curtained roof permits hot gases to be vented locally, allowing firemen to reach seat of fire inside a building and from its roof Monitors on top of roof allow hot gases and smoke to escape Curtain boards (extending down from the roof) prevent the lateral spread of smoke and heat illustration adapted from one of National Fire Protection Association
1053