CHAPTER 38 1954 Guide 870 >; Fia. 6. Pebfobmance Data fob Typical Commercial Solid Adsorbent Dehumidifier Then q = 1085 g--ra:i--ns p-e-r--m---in--ujt-e = 61.6 lb air per mi.nute nm. .irn t,h. at, must,b.e,, supplied to the17ro.6omgratomsmpaeinrtpaoinun3d0 F dew-point. i Note that this figure represents the minimum requirement for the arbitrary condi-,- j tions set forth and that in practice, safety margins should be added to the outside air, percentage figure and to the calculated internal moisture gain. ' VAPOR TRANSFER TO DEHUMIDIFIED SPACE | The walls enclosing a dehumidified space are subjected to a vapor pres sure differential. The pressure of the vapor outside the walls tends to force moisture through the walls into the dehumidified zone of relatively: low vapor pressure. As this process can be an unnecessary load on dehumidifying equipment, provisions should be made for keeping the vapor transfer to a minimum. Also, if the space is cooled below the ambient dew-point, there is a possibility that condensation may occur within to?, walls, unless vapor transfer is controlled. For these reasons a vapor bar-' rier should be located within the wall construction as near to the high vapor pressure side as feasible. To be effective, a barrier must be continuous and should be so located within the structure that it will be protected fro rupture. (See Chapter 10, Water Vapor and Condensation In Building Construction). & CHAPTER 39 AUTOMATIC CONTROL Basic Types of Control, Types of Controllers, Actuating Devices, Indicating and Recording Equipment, Actuated Controls, Automatic Control Application, Residential Control Systems, Steam Heating Systems, Hot Water Heating. Systems, Unit Heaters, Air Supply Ventilating Units, Unit Coolers, Refrigeration and Dehumidification Equipment, Central Fan Systems, Panel Heating Control, Individual Room Control, Zone Control, Design Coordination THE function of automatic control, as applied to heating, cooling, ven tilating and air conditioning, is to maintain temperature, humidity, and pressure, within pre-determined ranges. It coordinates the operation of the various controlled devices in proper sequence to produce the desired result.1'5 BASIC TYPES OF CONTROL Available automatic control equipment may be divided into, four main groups depending on the primary source of energy: 1. A self-actuated regulator is one in which all the energy necessary to actuate a valve or damper operator is supplied by the responsive element or bulb. Tempera ture changes at the bulb result id pressure or volume variations of the enclosed media which are transmitted directly to the operating device of the valve or damper. In struments of this type are available either with a rigid bulb or with flexible tubing from the bulb to the operating bellows or diaphragm. The flexible tubing may be furnished in varying lengths, and is generally protected by a flexible metal armor. 2. Electrically operated equipment utilizes electric current as a primary source of energy, its flow being regulated as required to operate motors, relays, or other con trolled items. Electrical controls may be divided into two classes: (1) those wherein the primary measuring device makes or breaks contacts to regulate the flow of the electric cur rent, and (2) those wherein the primary measuring device is a resistance wire com ponent of an electrical circuit. . 3. In pneumatically operated equipment the primary source of energy is compressed air usually at a pressure of 15 to 25 psig. The flow of this air is proportioned as re quired to operate valves, dampers, relays, or other controlled devices. 4. In hydraulically operated equipment the primary source of energy is a suitable "quid at a pressure of 15 to 25 psig or higher, which may be regulated after the same manner as compressed air. TYPES OF CONTROLLERS The basic types of controllers and their operations are: , 1; Two-position or on-off controllers are the simplest type and are clearly described By the name. With controllers of this type the valve or damper operator can assume on,y two positions, either open or closed. - Proportional or gradual acting controllers function to reposition the controlled hV1Ce' ky small increments to regulate the flow as the controller senses a slight mange from the desired conditions. The valve or damper or other device may take ny position, including open and closed. Automatic reset (or proportional plus reset) controllers function to reposition a aive or damper as in a proportional controller. In addition, a device in the controlr automatically resets the instrument whenever the controlled variable deviates anrf1 ^esired value due to load changes. The rate of reset is manually adjustable n must be set to meet the load requirements of the individual system. Controllers may also be designated by types as: a non-indicating con- 871