CHAPTER 25
1960 Guide
tioa" from & direct measurement of the reverberation time. Another method of measuring R is to use a standardized sound source of known sound power level Lw and apply Equation 23 backwards. Such a standard sound source is commercially available.** Tt should be pointed out that the value of R found from Equation 24 should be augmented by the natural air. absorption before use in Equation 23. It should also be pointed out that Equation 23 is not accurate for & room of unusual shape, such as a long room with a low ceiling.
For estimating purposes, approximate values of the room constant R may be obtained from Fig. 18 as a function of room size for five classes of rooms.
Hoe .value of the second and third terms of Equation 23 (including 0.5 db) is plotted in Fig. 19 with distance r from the source as the abscissa, with the sound pressure level in decibels as the ordinate and the room constant R in sq ft as the param eter.
The directivity factor Q is given at the bottom left-hand ride of the graph. The procedure for using the graph is:
Determine the room constant A and the directivity factor Q for the particular direction 9 of interest. Enter fig. 19 at the bottom at the distance r. Then move diagonally to the left until the value of Q is reached. Then move vertically until the value R ia reached. Then read the relative sound pressure level from the ordinate. An example is shown by the dotted line in Fig. 19 for r -- 7 ft, Q -- 2, and R -- 2000 sq ft. The relative sound pressure level is added algebraically to the sound power level to yield the sound pressure level at the distance r and the angle 6 in the room (see Equation 23).
It is seen from Fig. 19 that the noise from a ventilating duct is less at distances far from it than nearby. Moreover, at large
distances, the levels produced in the room depend only on the
power level of the source and the room constant and not on
the directivity factor and the distance r.
Example 5: To illustrate the application of the noise criteria and coatrol procedures outlined in this chapter, calculation will be made for the required treatment for the ventilation system supplying the library reading room of Fig. 20. This room bias a total volume of 80,000 cu ft and may be considered as an average room for acoustic properties (see Fig. 18). The total air
s7 R= r ROOM CONSTANT
IN SQ FT
_ S= TOTAL AREA OF BOUNDARIES
OF ROOM IN SQ FT
3=AVG. ENERGY ABSORPTION COEFFICIENT OF THE
SURFACE OF THE ROOM
THE ABSOLUTE SPL (OB RE Oj0002 MICROBAR) EQUALS THE SUM OF THE ORDINATE ANO THE
PWL (DB RE 10*13 WATT) OF THE NOISE SOURCE AT NORMAL ROOM TEMPERATURE AND
PRESSURE CONDITIONS. The Gsfcwc's position Is at a dbtooce r and on angle 0 with rupee* fo the duet opening. Q it determined from ff and from the duet dimensions (tee Fig. 18). To we tte graph proceed os for the example diown by the dotted Coe for r = 7 ft, Q = 2, and R " 2000 tq ft. The sound pressure level in dm room equals fte soa of (be onfinafe and Ibe sound power level. Nonnof room temper ulure and pressure condition* are assumed.
Fig. 19 .... Curves for Determining the Sound Pressure Level in die Room Relative to the Sound Power Level
Sound Control
361
Table 10 .... Summary of Calculations for Example 3 on Ventilating Noise Levels in Libary Reading Room
Octore Frequency Bands
ton
20-
75-
150-
300-
60O-
1200-
2400-
4800-
75 cps 150 cps 300 ^s 600 cps 1200 cps 2400 cps 4300 cps 10,000 cps
1. I'W<4etDH>................................................... 2. AttenuatioD(.trif!.t do.......................... 3. Attenuationowad b>................................... 4. Attenuation^.* hi................................... 5. Attenuation^^ i..................................
6. Total duct attenuation...........................
101 5 --
-- 13 --
18
96 5 --
-- 7
-- 12
91 5 2 l 4
--
12
86 5 7 4 1
--
17
81 5 7 7 --
--
19
76 5 6 7
-- --
18
71 5 11 8 --
--
24
66 5 12 10
-- --
27
7. Z/!T(*rllU Mll4i)................................................... 8. JLf1000 eps-tn.............................. ..........
9. Q..................................................................... 10. Rel.L, at 7 ft............................................. 11. Lp at 7 ft..................................................... 12. L(*ii fitiw)................................................ 13. Rel.* far field.................... ...................... 14. Reverberant L,............................................... 15. Criterion ,............................................... 16. Required attenuation.................................. 17. Attenuation 4 ft pkg. unit.......................
S3 0.5 2
-22 61 89
-26 63 60 3 7
84 1.3 2
-22 62 90
-26 64 51 13 n
79 2.5 2.2
-22 57 85
-26 59 43 16 14
69 5.1 2.7
-21 48 75
-26 49 37 12 30
62 10.2 3.2 -20 42 71 -26 45 32 13 40
58 20.4
3.6 -20
38 67 -26 41 30 11 40
47 40.8
3.9 -20
27 56 -26 30 28
2 38
39 816
4.1 -20
19 48 -26 22 27 --
33
supply to the reading room ia 6000 cfm which is equally divided between four 12 x 18 in. supply grilles located along one wall. The supply of outdoor air is from a central fan system which bandies a total of 25,000 cfm at 2-in. water static pressure and requires a 15 hp motor.
Solution: It is necessary to determine the noise level in the reading room as a result of the ventilating system, both for the position of the nearest listener to a grille, and for a position remote from the supply grilles since it is impossible to toll be forehand which will be greater. The required attenuation for acceptable octave band noise levels will then be determined.
Analysis of Fan and Duet System
The acoustic power level of the fan should be computed from Equation 18 when the specific power level is available. In this example it is assumed that the specific sound power level is not known. Therefore, employ the approximate Equation 19
For duct AB:
Lw - 100 + 10 log 15 + 10 log 2 114.7 db
Of this total acoustic power generated by the fan the interest is in the part that reaches the reading room. At each duct branch the power will,divide approximately as the ratio of the branch duct area to the total duct area after the branch. Thus at Station B (Fig. 20) the acoustic power delivered to the IS r 48 in. duct, neglecting any attenuation in the system, will be:
For duct BC:
Lw = Lp from duct AB + 10 log (At***k/A*rti)
- ns +1 log
^j . m db
fan will be 108 db- Assuming that the branch Gtting3 at D, E and F are similar to that at C in Fig. 20, the unattenuated fan acoustic power delivered to each of the four 12 x 18 in. grilles will be approximately
For duct DH:
Lw -- 108 -- 10 log 4 - 102 db
The octave band spectrum of the centrifugal fan noise is given by Fig. 6. This chart indicates that the power level in
At Station C the power division gives: For duct CD:
Lw = 111 + 10 log I ----------- 12-- f-------------1 - 108 db 6 1_(18 X 24) + (12 X 48)J
Thus neglecting, at first, the attenuation in the connecting duct system, the total acoustic power delivered to the room by the