CHAPTER 22
1956 Guide
of 150 milinches per foot, or 600 milinehes for 4 ft. If the first floor radi ators are located 3 ft above the mains, second floor radiators 12 ft above the mains, third floor 21 ft, and fourth floor 30 ft, the heads are 450, 1800, 3150, and 4500 milinches, respectively.
In forced circulation systems flow is produced mechanically by means of a pump driven by electricity, steam, or other source of energy. As
Hot Water Heating Systems
537
Table 1. Iron and Copper Elbow Equivalents*
Fitting
Iron Copper Pipe Tubing
Fitting
Iron Copper Pipe Tubing
Elbow, 90-deg...................... Elbow, 45-deg......................
Elbow, 90-dejs long turn___ Elbow, welded, 90-deg........
1.0 0.7
0.5 0.5
1.0 0.7 Radiator or convector.... 0.5 Boiler or heater........ 0.5
2.0 3.0 3.0
3.0 4.0 4.0
Reduced coupling................ 0.4 0.4 Tee, per cent flowing
Open return Irend................ 1 0 1.0 through branch :b
Open gate valve.................. 0.5 0.7 Open globe valve................ 12.0 17.0
100 50 .
1.8 1.2 4.0 4.0
25............................... 16.0 20.0
* The friction in one 60 deg standard elbow is approximately equal to the friction of a length of straight pipe of the same nominal size and 25 diam long. Hence, one elbow equivalent in feet of pipe equals 25 diam (id inches) divided by 12.
b Applies to conditions of flow in hot water heating system.1' *
M ILIN C H E S PER FOOT O F PIPE
FRICTION --
Fig. 1. Heads Resulting from Temperature Difference (Gravity Systems)
forced circulation velocities are higher than those in gravity systems, and as the friction in a heating system varies almost as the square of the velocity, a given error in the calculation or assumption of the velocity is less im portant in a forced circulation system than in a gravity circulation system, and, consequently, it is easier to design a satisfactory forced circulation system than a satisfactory gravity circulation system.
FRICTION LOSS
Values of friction loss due to flow of water in the various parts of a heat ing system must be known in order to design either gravity or forced circu lation systems. The friction loss of fittings is customarily expressed in equiv-
Ta chart is based on 20 deg temperature difference between flow and return risers,
o unu friction when temperature-drop is other than 20 deg, multiply the actual heat conveyed by
(( ------------2200
\\ ... , ...
" ..................
V\aaicttmj temp, drop/
reat^ the corresponding friction.