Document ymw3ddErMJBqGoaaQZ5eNE6y2
UsS) Tiger Brand High Temperature
Applications:
These cables ore for use in power circuits located in wet or dry location either exposed or in conduit, where high am* bient temperatures are en countered and where oil, grease, corrosive fumes or fire hazard conditions exist.
Conductor Temperature
I25C (Max.)
Specifications:
Copper Conductor--Annealed uncoated'
Insulation--Silicone rubber -- *
Outer Covering--Asbestos braid
Finish--Black FHM (flame, heat, and moisture re sistant) -----This product is manufactured and tested in ac cordance with IPCEA Publications S-19-81 and $-28-357 where applicable and Underwriters' Lab oratories requirements for type SA.
TB1-403 HIGH TEMPERATURE
Type SRI Power Cable Table SR-E
UL Type SP Single Conductor
600 VOLTS
Oate Corrected: May. 1973
Size AWG
or MCM
14 12 10
8 6 4
2 1 1/0
2/0 3/0 4/0
250 300 350
500 750 1000
No. of Strands
7 7 7
7 7 7
7 19 19
19 19 19
37 37 37
37 61 61
Insulation Thickness
.100"
.045 .045 .045
.060 .060 .060
.060 .080 .080
.080 .080 .080
.095 .095 .095
.095 .110 .110
Braid Thickness
Mils
45 45 45
45 45 45
45 45 45
45 45 45
45 45 45
45 45 45
Approx. O.O.
Inches
.261 .280 .305
.370 .409 .458
.520 .598 .636
.683 .732 .798
.868 .926 .974
1.107 1.324 1.477
Approx. Net Weight Lbs./1,000 ft.
39 45 64
106 144 205
295 373 , 451
548 670 821
978 1146 1330
1831 2670 3490
Packing
500* Coils 500' Coils 500' Coils 1000' Reels 1000' Reels 1000' Reels
1000' Reels 1000' Reels 1000' Reels
1000* Reels 1000' Reels 1000' Reels 1000' Reels 1000' Reels 1000' Reels 1000' Reels 1000' Reels 1000' Reels
Diameter subject to +5% tolerance. For ampacities refer to Page TB1-801. For conduit sizos refer to Poge TB1-802.
U.S.S. AND TIGER BRAND ARE REGISTERED TRADEMARKS.
PLAINTIFF'S
EXHIBIT
uskl-i<
r ARCHITECTS/ENGINEERS
Hew to specify this product for purchasing purposes:
''Coble shall be U. S. Steel Tiger Brand TB1-403 or approved equalM