Document ymp6vJy4gMjjwORxVygzz87L2

X Petyped copies (originals not clear attachment a REVIEW OF ASBESTOS CONTAINING PRODUCTS USED BV ENGINEERING DEPARTMENT All negligible in section 01 & 2 J. C. Warner 7/28/72 1. General inventory of asbestos containing products. a. Asphalt mastic - asbestos fiber filler b. Braided coil and ring packing - asbestos yarn c. Gloves - asbestos cloth d. Heat suits aluminized asbestos cloth e. Hot pads - asbestos paper f. Insulation - see separate listing - item 2 g. Molded packing - asbestos fibers filler h. Sheet gasketing - asbestos fibers filler ' i. Ribbon asbestos 2. Thermal insulation materials. a. Code 102 calcium silicate - asbestos fibers reinforcing b. Code 102.1 inhibited calcium silicate - asbestos fibers reinforcing c. Code 104 - kaylo' 20 - asbestos fibers reinforcing d. Code 130 - asbestos board - asbestos fibers reinforcing e. Code 701 - asbestos roofing felt - asbestos fibers reinforcing f. Code 70S - fibrated asphalt emulsion - asbestos fibers reinforcing ,, g. Code 709 - fibrated asphalt cut-back - asbestos fibers reinforcing * h. Code 715 - asbestos cloth i. Code 715.1 - asbestos cloth j. Code 718 - fire resistive fibrated asphalt cut-back asbestos fibers reinforcing k. Code 719 - fibrated asphalt dispersion - asbestos fibers reinforcing DIFINOANT'S kxhwt i r * DUP 0902838 129992 SC-DP-03780 REVIEW Cr ASBESTOS C0>rAININC PRODUCTS USED BY ENGINEERING DEPARTMENT PAGE 2 " l. Code 724 - asbestos paper m. Code 724 - flexible braided asbestos tubing - asbestos yarn n. Code 728 - "Tedlar" Neoprene - asbestos laminate asbestos paper o. Code 729 - "Hypalon" Neoprene - asbestos laminate asbestos paper p. Code 803 - fibrous adhesive - asbestos fibers reinforcing 3. Problem locations - no problem to 3-D personnel. a. Insulation Storage Building - several small storage areas, maintained and used by laggers - no one there 90X of the time. 4. Problem Jobs (same degree of problem if any as in other- areas of Plant.) a. Dismantling calcium silicate insulation - occasional small jobs, say 1/week, few large jobs, say 1/month. b. Installing calcium silicate insulation - laggers c. Waste disposal - when combined with dismantling jobs above. DUP 0902839 120903 Retyped cepies (originals not clear) ATTACHMENT B . TABLE ASBESTOS RELATED PR08LEMS, COMMENTS, ANO SUGGESTED SOLUTIONS DESCRIPTION COMMENTS SUGGESTED SOLUTIONS a. Asphalt Mastic No problem unless sprayed Do not spary b. Braided Packing Contained, consid ered safe to handle Personnel monitoring to verify claim c. Asbestos Gloves Probable source of exposure Personnel monitoring. Look for substitute d. Heat Suits Same as l.c. Look to aluminized "Nomex" as substitute e. Hot Pads f. Insulation 9- Molded packing Same as l.c. Separate listing Contained, no problem Same as 2.c. See Item 2 *" None required h. Sheet gasketing Contained, no problem None required a. Calcium Silicate Probable source of high exposure Personnel monitoring to verify claim. Look for substitute material. b. . Inhibited Calcium Silicate c. Kaylo 20 d. Asbestos Board a. Asbestos Roofiitg Felt f. Fibrated asphalt Emulsion 9* Fibrated asphalt Cut-back h. Asbestos Cloth (listing tape) Same as 2.a. Same as 2.a. Same as 2.a. Same as 2.a. Problem when sawed Same as 2.a. Contained, no problem None required No problem unless sprayed Do no spray Same as 2.f Same as 2.f. Possible source^ of high exposure Personnel monitoring to verify claim. , Evaluate J-M Thermo-chem tape as substitute. 1 DUP 0902840 129904 TABLE PAGE 2 ASBESTOS RELATED PROBLEMS, COMMENTS AND SUGGESTED SOLUTIONS ITEM i. J. k. 1. m. n. 0. DESCRIPTION COMMENTS Asbestos cloth Same 2.h. (insulation fittings) SUGGESTED SOLUTIONS Same as 2.h. Fire resistive Fibrated Asphalt Cut-back Fibrated Asphalt Dispersion Same as 2.f Same as 2.f. Same as 2.f. fSame as 2. . Asbestos paper Probably safe to handle Personnel monitoring to verify claim Flexible Braided Asbestos Tubing Possible Source Personnel monitoring to of high exposure verify claim "Tedlar" Neoprene Probably safe to Same as 2.1* Asbestos Laminate handle "Hypalon" Neoprene Same as 2.1 Asbestos Laminate Same as 2.1. P- Fibrous Adhesive Contained, no problem None required 3. a. Insulation Storage Possible source Thorough vacuum cleaning, of high exposure repeat periodically. Personnel monitoring to verify claim. .4 a. Dismantling Possible source Soak with water. of high exposure Personnel monitoring b. Installing Calcium Silicate Insulation Probable source Personnel monitoring. of high exposure Substitute as quickly as possible. c. Waste Disposal Regulated by OSHA Follow 37 FR 11321 Part 1910.931 h.2. DUP 0902841 J29903