Document ymp6vJy4gMjjwORxVygzz87L2
X
Petyped copies (originals not clear
attachment a
REVIEW OF ASBESTOS CONTAINING PRODUCTS
USED BV ENGINEERING DEPARTMENT
All negligible in section 01 & 2
J. C. Warner 7/28/72
1. General inventory of asbestos containing products.
a. Asphalt mastic - asbestos fiber filler
b. Braided coil and ring packing - asbestos yarn
c. Gloves - asbestos cloth
d. Heat suits aluminized asbestos cloth
e. Hot pads - asbestos paper
f. Insulation - see separate listing - item 2
g. Molded packing - asbestos fibers filler h. Sheet gasketing - asbestos fibers filler
'
i. Ribbon asbestos
2. Thermal insulation materials.
a. Code 102 calcium silicate - asbestos fibers reinforcing
b. Code 102.1 inhibited calcium silicate - asbestos fibers reinforcing
c. Code 104 - kaylo' 20 - asbestos fibers reinforcing
d. Code 130 - asbestos board - asbestos fibers reinforcing
e. Code 701 - asbestos roofing felt - asbestos fibers reinforcing
f. Code 70S - fibrated asphalt emulsion - asbestos fibers
reinforcing
,,
g. Code 709 - fibrated asphalt cut-back - asbestos fibers
reinforcing
*
h. Code 715 - asbestos cloth
i. Code 715.1 - asbestos cloth
j. Code 718 - fire resistive fibrated asphalt cut-back asbestos fibers reinforcing
k. Code 719 - fibrated asphalt dispersion - asbestos fibers
reinforcing
DIFINOANT'S
kxhwt i r *
DUP 0902838
129992
SC-DP-03780
REVIEW Cr ASBESTOS C0>rAININC PRODUCTS USED BY ENGINEERING DEPARTMENT
PAGE 2
"
l. Code 724 - asbestos paper
m. Code 724 - flexible braided asbestos tubing - asbestos yarn
n. Code 728 - "Tedlar" Neoprene - asbestos laminate asbestos paper
o. Code 729 - "Hypalon" Neoprene - asbestos laminate asbestos paper
p. Code 803 - fibrous adhesive - asbestos fibers reinforcing
3. Problem locations - no problem to 3-D personnel.
a. Insulation Storage Building - several small storage areas, maintained and used by laggers - no one there 90X of the time.
4. Problem Jobs (same degree of problem if any as in other- areas of Plant.)
a. Dismantling calcium silicate insulation - occasional small jobs, say 1/week, few large jobs, say 1/month.
b. Installing calcium silicate insulation - laggers
c. Waste disposal - when combined with dismantling jobs above.
DUP 0902839 120903
Retyped cepies (originals not clear)
ATTACHMENT B
. TABLE
ASBESTOS RELATED PR08LEMS, COMMENTS, ANO SUGGESTED SOLUTIONS
DESCRIPTION
COMMENTS
SUGGESTED SOLUTIONS
a. Asphalt Mastic
No problem unless sprayed
Do not spary
b. Braided Packing
Contained, consid ered safe to handle
Personnel monitoring to verify claim
c. Asbestos Gloves
Probable source of exposure
Personnel monitoring. Look for substitute
d. Heat Suits
Same as l.c.
Look to aluminized "Nomex" as substitute
e. Hot Pads f. Insulation 9- Molded packing
Same as l.c.
Separate listing
Contained, no problem
Same as 2.c. See Item 2 *" None required
h. Sheet gasketing
Contained, no problem
None required
a. Calcium Silicate
Probable source of high exposure
Personnel monitoring to verify claim. Look for substitute material.
b. . Inhibited Calcium Silicate
c. Kaylo 20
d. Asbestos Board
a. Asbestos Roofiitg Felt
f. Fibrated asphalt Emulsion
9* Fibrated asphalt Cut-back
h. Asbestos Cloth (listing tape)
Same as 2.a.
Same as 2.a.
Same as 2.a.
Same as 2.a.
Problem when sawed Same as 2.a.
Contained, no problem
None required
No problem unless sprayed
Do no spray
Same as 2.f
Same as 2.f.
Possible source^ of high exposure
Personnel monitoring
to verify claim. , Evaluate J-M Thermo-chem tape as substitute.
1 DUP 0902840
129904
TABLE PAGE 2
ASBESTOS RELATED PROBLEMS, COMMENTS AND SUGGESTED SOLUTIONS
ITEM
i. J.
k. 1. m. n. 0.
DESCRIPTION
COMMENTS
Asbestos cloth
Same 2.h.
(insulation fittings)
SUGGESTED SOLUTIONS
Same as 2.h.
Fire resistive Fibrated Asphalt Cut-back
Fibrated Asphalt Dispersion
Same as 2.f Same as 2.f.
Same as 2.f.
fSame as 2. .
Asbestos paper
Probably safe to handle
Personnel monitoring to verify claim
Flexible Braided Asbestos Tubing
Possible Source Personnel monitoring to of high exposure verify claim
"Tedlar" Neoprene Probably safe to Same as 2.1* Asbestos Laminate handle
"Hypalon" Neoprene Same as 2.1 Asbestos Laminate
Same as 2.1.
P- Fibrous Adhesive
Contained, no problem
None required
3. a. Insulation Storage Possible source Thorough vacuum cleaning, of high exposure repeat periodically. Personnel monitoring to verify claim.
.4 a. Dismantling
Possible source Soak with water. of high exposure Personnel monitoring
b. Installing
Calcium Silicate Insulation
Probable source Personnel monitoring. of high exposure Substitute as quickly as
possible.
c. Waste Disposal
Regulated by OSHA Follow 37 FR 11321 Part 1910.931 h.2.
DUP 0902841 J29903