Document ymkeyEvGEr0Obmk2nmDdR1rZn
470
CHAPTER 18
1957 Guide
Btu per lb coal, and for other heating values of coal they must be multiplied by the ratio of 12,000 divided by the heating value of fuel used.
Example 6: A building in Scranton, Pa. has a calculated heat loss of 240,000 Btu per hr based on an inside design temperature of 70 F and an outside design temperature of -- 10F. What will-be the estimated normal seasonal anthracite or coke consumption for heating if 13,000 Btu per lb fuel is bumed in a hand-fired boiler, with automatic control, at a seasonal efficiency of 80 percent, and what part of the .total will be used during November, December; and January?
Solution: From Table 6, U is 0.0444 of coal or coke per 1000 Btu per hr heat loss per degree-day. Correcting for the outside design temperature of --10 F from Table 3, the value of V is 0.875 X 0.0444 = 0.0389. From Table 2, D is 6218 and from the problem, N is 240.
Substituting in Equation 4,
F = 0.0389 X 240 X 6047 = 56,500 lb.
Fuel used over any period is, according to the theory of the degree-day, propor tional to the number of degree-days during the period. From Table 2, the average numbers of degree-days for November, December, and January, in Scranton are 693, 1057 and 1141 respectively, a total of 2953. The yearly total is 27,000, so that during these three months the estimated consumption is
^ X 56,500 = 27,000 lb.
Estimating Steam Consumption
In estimating steam consumption the efficiency is generally assumed at 100 percent. If for low-pressure steam an average heating value of 1000 Btu per pound of steam is used, no correction is necessary. In comparing values from different cities, correction should be made for design, tempera ture (see Table 3) when the unit figures are in terms of heat loss but not when the values are in terms of building volume or floor space.
Where the heat loss is calculated in Btu per (hour) {degree difference in temperature) the simple Equation 5 may be used:
,, H X 24 X D
,-v
where
F = pounds of steam required for estimate period. H = calculated heat loss, Btu per (hour) (degree difference). 24 = hours in one day. D = number of degree-days for the period of estimation. 1000 = Btu delivered per pound of steam condensed.
In this method the number of degree-days automatically takes care of average inside and outside temperature difference. When degree-days are taken from Table 2, an average inside temperature of approximately 70 I is assumed throughout the period. If an average inside temperature other than approximately 70 F is to be used, the number of degree-days should be obtained for the new base.
Example 7: An eight-story building in Pittsburgh is operated with a daytime temperature of 70 F. The calculated heat loss is 10,500 Btu per (hr) (degree temper" ature difference). What is the estimated average yearly steam consumption to building heating?
Solution: Since the average inside temperature is approximately 70 F, the degree-
Estimating Fuel Consumption for Space Heating
471
days from Table 2, based on 70 F may be used. Therefore, from Table 2, Pittsburgh has 5048 degree-days per normal season. Inserting in Equation 5:
F = Lff X 24 X 5048 _ 1000
lb of eteam.
Consideration has been given to the difference in steam utilization of different types of buildings, and Table 7 shows actual average units for these various types. These figures were obtained from operating results in 896 buildings located in all sections of the United States. Being aver
ages, and for small groups in each type, the figures may need considerable modification to allow for local variations. It should be especially noted
that the steam used for heating water for service is not included in the values given in Table 7.
Table 7. Steam Consumption op Buildings with Vabious Types op Occupancy*
Type op Building
No. Bldgs
Average Volume Heated
Space 1000 Cu Ft
Steam fob Heating
Lb per DD per 1000 Cu Ft
Average Hours op Occupancy
Office............. Udine *H TUnlr Uttice and Printing umee and Theater
Utfcce and Stores or Shops
Bank........
Department Store Stores... Loft........
Warehouse..
.....................................................
49 26
3000 1895 4950 1615
3400
n rrS
0.617 n'nSS
11.1 il).t
Hotel and Club
Apartment or Residence.............................................. Theater... Uarage..........
Manufacturing
Church___
Hospital......... School...
Municipal or "FWl*TM!
................................. '
Miscellaneous
73 51
1
15 7
1425
3215 1387
(L962
0.532 1.194 0.592 0.390 0.479
" Principles of Economical Heating, National Association of Bunting Owners and Managers
1.9 22.0 11.5
21.4
7n p ", ? A store m rmiaaeipma witn a neatmg system designed to maintain est.imlTj m 0 F weather has 250,000 cu ft of heated space. What would be the
imated average yearly steam consumption of purchased steam for heating?
nor icon0"' According to Table 7, a store would use 0.624 lb of steam per degree-day ,,,,J cu ft heated space. From Table 2, Philadelphia has 4523 degree-days per
rmal year. Inserting in Equation 4:
F = 0.624 X 250 X 4523 = 706,000 lb of steam.
Degree-Day as an Operating Unit
of "th 6 c e^ree"<^ay also widely used as a means of comparing the efficiency
Sin th1 consumPt*on ,f one period with another /or the same building. consumption is proportional to the weather (degree-days),
,jiy smce fhe periods to be compared may not have the same weather conbeen03' cornParison can be made only after the fuel consumptions have oumh00111?11^ on a comParable weather basis, that is, upon the actual under .degree-days, occurring for a given month and year in the city
consideration Since fuel consumption is proportional to the number