CHAPTER 19
1955 Guide
Fig; 7; Topical Basement Line Drawing fob Extended Plenum
Gravity Warm Air Systems
* v ' ' `
' '.
.465
Design of Extended Plenum Systems
The, extended plenum system of gravity warm air heating employs
horizontal ducts in the basement leading from an enlargement or Extension
of the customary plenum to the risers which distribute the conditioned
air to the various rooms, A typical basement plan for a system using ah
extended plenum is shown in Fig. 7.
Extended plenum gravity systems have been satisfactorily designed and
installed in small compact single-story houses where the heat losses do not
exceed 65,000 Btuh. The dimension from the floor to the bottom of the
joists should in.every case be at least 7 ft., To. design such a system the
procedure is the same as for the conventional system already described in
this chapter.
, It is understood that the length of leader pipe is the horizontal distance
measured from the register to the furnace. For takeoffs, use standard
fittings designed for extended plenum connection and allow the equivalent
length of one 90-deg elbow.
,:
Sizing an Extended Plenum
To size.an extended plenum, proceed as follows;
1. Make a layout of the furnace, extended plenum, branches and registers, similar to Fig. 7.\
2. Follow methods given in paragraphs 1, 2, 3 and 5, under Design Procedure for
a conventional system, to determine the diameters or equivalent rectangular sizes of the branches:-from the extended plenum to registers.
3. Starting with the most remote branch connected to an extended plenum, write
its equivalent size as if it were Sin. in depth. For example: an 8-in: diameter branch
is equivalent to. a 6-in. wide x 8-in. deep duct (see Table 9). As each additional
branch is reached, determine its rectangular equivalent size as if it were 8 in. deep.
In the last column^of Table 9 find the additional width of plenum required to supply
added branch. When all branches have been.included,.the sum of the widths
added, fpr each branch plus the width of the most remote.branch will give theequiv-
alentr.width. for a plenum of 8-in. depth.
.
depth, pi plenum to be selected should be that of the largest branch.. The
width selected can be determined from the lower section of Table 9 where a plenum
of desired depth can be found equivalent to the size computed for an 8-in. deep
plenum. For example: if the size,based on an^-in. plenum is found to be 22 x 8 in.
the plenum may be 17 x 10 in. or 14 X>l2iin. -Tiie extended plenum is not changed
in size from furnace to end of the plenum. .
.Return air intakes are to be sized by tile same method as for conventional
gravity systems.
..
.
Resign Examples
Examples 1. and 2 will illustrate the use of the tables in selecting warm air
and return air system sizes.
^,
Example 1; For a room which has a heat loss of 22,500 Btu per hr, select the size
01 hrst story warm-air system. There are three elbows, and the leader is approxi
mately 10 ft long.
Solution: Since 22,500 Btu is beyond the capacities shown in Table 6, it is neces-
ary to select two units of 11,250 each. From Table 6 in 10 ft leader column, and in
i-ion ^or three elbows, find 11,400 as nearest capacity which corresponds to Com-
^tion Number 4 in first column. Refer to Combination Number 4 in Table 1
na find that the leader should be 12 in. in diameter, and should be used with a 12
j,10- floor register or a 13 x 11 in. baseboard register with a 5^4 in. extension.
*5- Example 2: What is the size of a return air svstem of Type D which is to service
^000 Btu per hr?
'