CHAPTER 7
1950 Guide
able duct systems as installed aboard ship should be acceptable. Serious explosions can occur in a closed system, but proper precautions will reduce this hazard to a minimum.
It should be realized that when a room and the occupants have been com pletely grounded, there is always the possibility that the patient or the operator might receive a dangerous shock if a short circuit developed in any of the electrical equipment.
A comprehensive study of the explosion problem and of the general causes and prevention of operating room hazards, by the University of Pittsburgh the A.S.H.V.E. Research Laboratory, and the U. S. Bureau of Mines has led to a fruitful attempt to eliminate the explosive range of cyclopropane, one of the best but most difficult gases to handle. The use of helium as a diluent in the total gaseous mixture controls the oxygen concentration by displacement and, because of its flame quenching properties, it is the ideal gas for this purpose. In addition, a gaseous mixture containing helium is more difficult to ignite by electric discharges, and this quality also in creases the safety factor of anesthetic administration.
Operating Room Conditions
Little is known about optimum air conditions for maintaining normal body temperatures during anesthesia and the immediate post-operative period. An anesthetized patient displays dilation of blood vessels in the skin resulting in profuse sweating and (it has been believed) inability to regulate body temperature. From this it was concluded that all anes thetized patients suffered considerable heat loss, although there may be little more than 0.8 F variation in the rectal temperature during the course of the operation.26 The severe physiological effects, such as excessive sweating and rapid pulse, of high operating room temperatures on attend ants and patients during the hot months signify the need for proper cool ing. Statements of surgeons who operate in both air conditioned and non-air conditioned rooms strongly indicates that the recuperative power of the patient is greater when operated upon in air conditioned rooms.26
Although the comfortable air conditions for the operators are not identi cal with those for the patient, it is usually not difficult to compromise within a range of 55 to 60 per cent relative humidity and 72 to 80 F temperature. The work just cited reported that 68 to 70 F effective temperature not only furnished comfort for the operating room workers, but apparently pre vented exhaustion of the patient as evidenced by rapid convalescence in the recovery ward. Additional heat may be furnished to the patient locally or by suitable covering, according to body temperature in individual cases.
In the control of airborne infection in the operating room, the prevention of dispersal of infectious materials into the air, control of dust, and proper ventilation supersede attempts to remove or kill pathogenic organisms. The bacterial content of conditioned operating rooms is generally lower than that of non-conditioned rooms.
Bacterial counts aboard an air-conditioned submarine were found to be exceptionally low and not cumulative with time, although all of the air was recirculated for more than 12 hours27 without replenishment. The removal of bacteria by the process of air cooling and condensation of mois ture out of air, merits further study.23
The degree of air contamination can be reduced by proper ventilation if velocity of air over the floor does not exceed 50 fpm. Research is in
Air Conditioning in Prevention and Treatment of Disease
143
nroeress on the use of filtered air flowing through a system of mechanical leaners which protect the patient against infection from attendants and from bacteria-containing air in the corridor or ward.29
Operations are frequently postponed on allergic patients during asthmatic manifestations through fear of complications. The removal of airborne allergens, therefore, is in some cases an important function of the air con ditioning' system in preparing patients for operation.
Central system air conditioning plants and unit air conditioners prove satisfactory in operating rooms when producing between 8 and 12 air changes per hour of filtered and properly conditioned air, without recircu lation during the course of anesthesia. A separate exhaust fan system is usually necessary to confine and remove the gases and odors. Double windows are desirable and often necessary to prevent condensation and frosting on the glass in cold weather, and to minimize drafts. The air flow of 8 to 12 air changes in operating rooms should: (1) reduce the concen tration of the anesthetic to well below the pharmacologic threshold in the vicinity of the operating personnel, (2) remove the great amounts of heat and sometimes moisture, from sterilizing equipment if inside the operating room, from the powerful surgical lights, from solar heat, and from the bodies of the operatives, and (3) provide extra capacity for quickly pre paring the room for emergency operations. Much can be gained by ther mal insulation of sterilizing equipment and by thorough exhaust ventila tion of sterilizing rooms adjoining the operating rooms. An air conditioned recovery ward in connection with the air conditioned operating room, is of great value in stabilizing peripheral circulation and in reducing excessive loss of fluids on hot humid days.
NURSERIES FOR PREMATURE INFANTS
One of the most important requirements in the care of premature infants is the stabilization of body temperature. This is necessary because the infant's heat regulatory system is not fully developed, with the resultant tendency for environmental temperature to influence body temperature. The younger the premature infant, the greater is the tendency. As the infant's metabolism is low, heat production is not adequate to maintain a normal body temperature in a cool environment. The resistance to in fection is low, and the mortality rate is high. In general, the younger the. age of the premature infant, the higher the mortality rate.
Nurseries constructed for metabolic research should be air conditioned so that conditions are reproducible. Results of such studies may be in valid if environmental conditions are not identical, since fluid and electro lyte loss may vary greatly 'with change in environmental conditions.
Air Conditioning Requirements
The optimum air conditions for growth and development of premature infants were determined by extensive research30 at the Children's Hospital, Boston, Mass., using four valid criteria, namely, stability of body tempera ture, gain in weight, incidence of digestive syndromes, and mortality. Individual temperature requirements varied widely (from 72 to 100 F) according to the constitutional state of the infants and body weights. The optimum relative humidity was about 65 per cent, and the air move ment less than 20 fpm.
A single nursery conditioned to 77 F and 65 per cent relative humidity was found to fulfill satisfactorily the requirements of the majority of pre-