Document ykjQvG3pxY38zvKwvX77rXKQV
Monsanto
DIVISION
.
Organic
INSTRUMENT FUNCTION OUTLINE '
W. plant G. Krummrich
BLDG/DEPT
AUTH NO.
8.11.00
2471 .. . '
CEO LOOP NO.
.
.
FIC-414-1
ISSUED BY
C. J.
REV. BY
Hans
DATE
PLANT LOOP NO.
7/23/71
DATE
RSV
SHEET
1 OF
#8 CHLORINATOR CHLORINE FEED
1.0 NEED FOR LOOP
.
.
This new controller is required to accept the pneumatic output from the existing densitrol so as to make the required gravity Aroclor material in No. 8 unit for "mono" operation only. The Aroclor 1105 feed (for "mono") gravity is finished off in No. 8 chlorinator so tha-fe-No. 9 chlorinator can be .used for blowing (de-gassing).
1.1 DESCRIPTION OF LOOP
1.1.1 Function
.
-
*
'h
The function of this loop is to control the flow rate of chlorine to
#8 chlorinator by using the density measurement to reset the set
point when on "mono" operation.
For operation on "1016" refer to IFO FIC-10.
1.1.2 System Performance Required
The flow rate schould be + l%.of set point.
1.1.3 Accomplishment of Function
The chlorine flow is controlled by measuring the rate of flow in the
line using an orifice plate and a differential pressure transmitter.
The D/P transmitter sends an air signal (3-15 PSIG) proportional to
the flow rate to the indicating controller. The controller compares
s this signal with a set point flow rate which is determined by a density
' indicating controller (DIC-39). The controller sends a varying 3-15
PSIG signal to the chlorine control valve to compensate for variation
from the set point.
PCB-ARCH-EXT0374047
Msnsanto
-
.
DIVISION
Organic
INSTRUCT FUNCTION OUTLINE
. W. plant G. Krummrich . '
BLOG/DEPT
AU7H NO.
811.00
2471
CEO LOOP NO.
FIC-414-1
ISSUED BY
DATE
PLANT LOOP NO.
C. J. Hans
REV. BY
7/23/71
DATE
REV
SHEET
OF
3.0 OPERATION
3.1 NORMAL OPERATION
.
': '
. ' .
Set the specific gravity controller for #8 chlorinator in "auto". The set point will be determined by supervision. The densitrol ' will adjust the chlorine feed automatically to #8 to maintain the indicated specific gravity. Note:--The range of the densitrol for "mono" operation is to
3.1.1 Startup Instructions
a. Open manual valves in chlorine feed. line.
.
b. Bring specific gravity up to desired level with controller
"local-remote" in "local" position and on "auto.
c. When desired level is reached switch to "remote" to allow DIC-39
to adjust set point.
d. Check specific gravity manually every 2 hours.
3.1.2 Shut-Down Instructions
a. 'Close chlorine valves to distributor. b. Switch controller to local and move set point to "0".
.
3.1.3 Manual Operating Instructions
1 Place controller in "local" and "manual". Adjust air to regulate
control valve opening.
\
3.2n, INTERLOCKS
There are two interlocks on this system. (1) Cln valve will not operate if circ. pump is down, (2) on high temperature the CI2 valve will not operate (Hi temp, is 205C). The reset button on panel board must be pushed after interlock has come in.
3.3 ABNORMAL OPERATIONS
3.3.1 Air Failure -
Air failure to the loop will cause the feed valve to close and instru ment will indicate no flow.
3.3.2 Power Failure
Power failure to the loop will cause the feed valve to close due to
the interlock with chlorine pump; The instrument will indicate zero
flow.
.
.
"
' '
.
PCB-ARCH-EXT0374048