Document yk6BEvG6jq93VGdz4dawQwOBD
PCBs--Compliance Is/And Our Responsibility
br
B. M. Panlah, Hartir IEEE J. J. Kelly. Member IEEE
Transformer Maintenance Institute Dir. S. 0. Mfers, Inc.
Akron. Ohio
Abatract - Federal regulations do not require the re moval of PCBs (polychlorinated biphenyls) from service in totally enclosed industrial and utility transformers earlier than normal. Many of the estlaated IkO.OOO askarel-fllled and 35 million oil-rilled units in service can and vlll be around for many years to corn.
During the state of frustration that the PCB control lieu# is in now, the beat route to go is to keep In formed of the latest state and local regulations, end to aake a "reasonable effort" to comply with existing U.S. regulations.
sections of TSCA. The first "Disposal and Marking Rule" took effect on April 18. 1978, while the 1979 "PCB Ban Rule" took effect on July 2, 1979. This lat est regulation supercedes coapletely the 1970 version^
II. Unraveling the SPA PCB Regulation
The law is clear -- choosing to keep PCB transformers In service requires proper identification; choosing to dispose of units requires the sms identification plue proper storage and disposal procedures. Either option requires accurate recordkeeping.
At least seven chemical waste landfills for non-liquid PCBs hart been approved by the EPA (Environmental Protection Agency).
On the other hand, until such time as EPA approved
PCB liquid Incineration becomes feasible--in terms of illstMirt snl backlog--don' t panic! Hold on to the
liquid In EPA approved containers, stors in an EPA approved manner, and Inspect weekly until Incineration
becomes practical. DQ1t contract for shipment to some facility that asg have an approved Incinerator
-
as you aay be subject to spill liability.
I. Introduction
Federal ZPA regulations do not require the removal of PCBs from service In totally enclosed Industrial and utility transformers sarllsr than normal. Therefore, easy of the estimated ibO.OOO askarel-fllled end five million oil-filled power end 30 million distribution units la serviee can end vlll be around for many years to come.I
But U.S. EPA regulations do control the use, maint
enance, handling, labeling, storage, and disposal of polychlorinated biphenyls (PCBs) within those trans formers A large power capacitors. Even though PCB has been the most listed Item In U.S. regulations, it has nut been totally banned nor Is this anticipated la the future.2
PCBs, known generlcally as "askarel", have been used
for 50 years for cooling and insulating electrical equipment in situations where high fire reelstance
was required. Another plus vis PCB chamlcil stability. But this same characteristic of persistence that made PCBs useful for Industrial purposes has made them har^ ful, especially their cumulative effect on the food chain from plankton (the simplest plant or aniuol) to fish, birds, and so on thru to the human species.*
A 1978 attempt at voluntary control via unsuccessful. Therefore, subsequent stages have involved government al regulations. The first step was the adoption of the Tonic Substances Control Act (Public Lav #9k-h69 known ns TSCA) which vent into effect January 1, 1977. The intent of TSCA has been to protect in a reasonable and prudent manner the public health and the enrironneat fruu further contamination from toxic chemical aubatancas and mixtures. PCB is only one of tbs eh^ teals to be regulated. Congress also mandated that detailed regulations be published to Implement certain
A. Definitions
Notable among the PCB associated terminology defined In Table I is a PCB itea. A PCB item is any PCB associated thing that deliberately or milntenttonally contains or has aa a part of it any PCB or PCBa at a concentration of 50 parte per million or more (0.005 per cent on a dry weight basis) and is therefore subject to EPA regulations.
Both askarel and PCB are rarely found on a transformer nameplate. Many people are more fmiliar with one of the insulating riuld tradenames, as Pyr*nolRt Inerteem*. Aroclor, and so on. Aa a matter of record, PCB urns Invented In 1929 by Swann Chemical, later bought owt by Monsanto Chemical. The late Dr. F. M. Clark patent ed its application for use aa an Insulating fluid far the General Electric Co. in 1931-5
Someone has Illustrated the meaning of quantity la parts per million (PPM) using thla analogy: One (1) part in a million is comparable to one (1) minute la 1.9 years! The definition of PCB Mixture Includes transformer oil and other liquid coolants that have bams 1 uadisi tently contaminated. Major transformer mammfactursf have acknowledged that "some oil-filled tramsformers aay contain varying concentrations of PCB." In thla regard It Is Illegal to dellbarately dilate PCBa. Thla precludes topping off a mineral-oil filled transformer that's contaminated with PCBa. At the sane time, it stands to reason If the oil level has dropped ever the passage of time below the transformer core, the addition of mineral oil aa a maintenance step only should not violate the Intent of the PCB regulation.
This paper vlll first cover changes that took place In the 1979 rule and also consider othsr PCB related legislation -- both existing and forthcoming-
Current PCB regulations apply to all persons who aammfacture, process, distribute In eoams, nee, or dimpose of PCBe. Our focus will be upon those who nme and dispose of PCBe.
B. In Service Units
Existing totally enclosad transformers cam eontlaus In definitely in service. Proper labeling, recordfeeeping* and voluntary inspection are the only neeeesnry galta lines.
However, free breathers aay be phased out by 1965. Thaee
3. D. Ilyers, Inc. 19Y9
HONS 014603
TDM FCB, FCBs
Table 1
Bavlroaae&tal Protection Agency FCB Regulation Terminology*
DBFnmog
Any chcaleal substance containing only a biphenyl nolecule that has been chlorinated to varying degrees or sny coablnatlon of substances which contain such substance.
FTIIgf
PCB liquids aad non-llqulda.
FCB Traaeforaer
FCB Contsalnated Transformer*
A^ transformer that contains 500 ppa PCB or greater.
\ Any transformer that contains 50 ppa or greater of PCB but less than 500 ppa PCB.
Askarel filled, retr^ filled unit, or mineraloil filled unit as found from tasting.
Typical oil-filled tranaformer or FCB retrefilled unit.
FCB Article
Any manufactured Item, other than a PCB container that contains FCBs and whose surface(s) has been in direet contact with PCBa.
Large high or low
voltage capacitors, transformers, PCB cooled aotors.
FCB Container
Any device used to contain PCBa, or PCB articles, and whose surfaee(s) has been in contact vlth PCBa.
Bottle, barrel, dna or box.
FCB Article Container
Any device used to contain PCB articles or PCB equlpaent, and whose surface(s) has not been in contact with PCBa.
Shipping or storage carton for capacitors.
FCB Bquipaaat
Any manufactured itea other than a PCB container or PCB article container that contains a PCB article or other PCB equipment.
Industrial television receiver, microwave oven, fluorescent light ing fixture.
FCB Item
Any PCB article, PCB article container, PCB container or PCB equlpaent, that deliberately or unintentionally contains or has s pari of it any PCB or PCBa at a concentration of 50 parts per million (ppa) or aore.
Aroelorjj, Inertsen8.
Pyraaol , contaminated transformer (mineral) oil, or eooleate ratr^ filled to treasfferae formerly containing PCB.
Source:
, Vol. bb , No. 106, Fart VI, pp 3151^-31558.
on FCB Transformer - Any transformer that contains less than 50 ppa PCB - tan not formally defined In this regulation.
Requirements for Labeling PC^Related Itaaa (For PCB ltM of 50 ppm or more only)
FCB tmwfonwr
tl'or units >^QQ tjtub only)
Largo FCB hig^voltage capacitor or capacitor* nount4 lo i protected location ouch as oa a pole, struc ture, or behind a fence, only one label need be
posted on the pole, structure or fence. A telephone is sufficient owner contact Identification.
Other FCB erticles-FCB cooled electric aotors, FCB hydraulic equipment and systeas, PCB heat-transfer equipment sad systeas not associated with tressfawwr mi cwcltor cooUn.
FCB equipment (containing a FCB traaeforaer or FCB larae hlah-voltaae capacitor).
FCB storage areas, FCB containers, and FCB article twtttotrrt________
FCB transport vehicles (actor vehicle or railcar) carerla. f- -- H to (99.l lb.) of FCB'..
See Figure 1 for required label forast
Figure 1
T9CA requires that FCB lteaa be identified as spe
cifically prescribed with the largest FCB aarfc
practical for a.PCB Its*. When a FCB article
or PCB equlpaent la too seal I to acccaodate
the saallest permissible else of Nark N^, MUrfc 1%
aay be used. Detailed requlrsasate fbr else, color
and durability are siren in the Federal
~
Part VI , P.31556.
1CAUTION i
CONTAINS
PCBa
HONS 014804
unit! eenelat of railroad transformers. primarily, with fn industrial units Involved.
1. Tramforaer Idsntlflcatlon
indicated that very little Mineral oil dielectric fluid will be contaminated with PCB beyond 500 ppm.
EPA thus antieloates that aost transformer owner/ operators will nake such an assumption.
Under tbs latsst PCB regulation, all items Hated In
Table II should now display the appropriate PCS label*
(figure 1).
'
Beeulreasnts for PCB*^cordheplna
a. Who Must Comply
Since July 2, 1978, an Inventory Must be kept concern-, log the atatus of your PCB Items. The requirements apply to each facility owner or operator who has on hla premises:
. One or more PCB transformers and/or
2. Schedule over a period of time, as the tmrtgst per mits, a one tine PCB analysis teat on each aloeraloll-fllled transformer of unknown PCB concentra
tion beginning with the aoat critical units -- by location (near a waterway) and by disposition (near the end of life expectancy), first, those unite tested and found below the 50 ppm PCB standard would thus be exempt fron all disposal requirements and any PCB spill associated problem. Secondly, testing would serve as a preventive Maintenance tool. Since there is evidence that over 100 ppm PCB in mineral oil reduces the Inpulse strength of oil, testing would Indicate suspect units.9
. 50 or aore PCB large high or low voltage capacitors (See Table 111) and/or
. At least hS kilogram (99.4 lbs) of PCBs.
These records will fora the basis for a required an nual document prepared by each facility. It should be available on July 1, 1979, and each succeeding July 1 thereafter, for nultiplaat companies in scat tered locations, one record for the entire corporation could be Maintained at a central location.
Current law requires that records are to be Maintained la the individual companies*own file, subject to re quest of copies or on-alte EPA Inspection upon the presentation of appropriate credentials, along with written notice of the facility to be Inspected.
b. What Data Required
. Total weight In kilogram of PCBs and PCB ltens In containers including identification of container contents, such as liquids or capacitors (total weight mens excluding the weight of the containers).
. Total niasber of PCB transformers and total weight In k'logram of eny PCB liquids contained in the transformer.
. Total nwber of PCB large high or low voltage capa citors.
. Location of PCB Iten.
Use namplate Information to determine PCB weight re quirements. Tour annual reports Must be kept for at least five (5) yean after a facility ceases to own or operate PCB related item in the prescribed quantities.
failure to keep proper records la a violation of the lav. Civil penalty of up to $25,000 could be iaposed for violatloa of TSCA; each day the violation con tinues Is considered e separate violation.
c. Bow Acepetable Records Generated (To test or not to tost!)
Teotlag for PCB concentration in transformer mineral oil le not required in the latest PCB ruling. There fore, consider two possible options.
1. Do nothing (t.e, do not test). Un!ess there is a specific reason to believe e given transformer has mots than 500 ppm PCB, seams the unit to have 50 to 499 ppm PCB. Available IPA information has
As Tabls 7 shows, a distinction has now been made be tween PCB transformers, those containing 500 or sore ppm, and PCB contaminated units, those containing be tween 50 and **99 ppm, and non-PCB transformers, those with less than 50 ppm PCB.
Those units that contain less than 500 ppm do not require labels. However, special identification of "PCB contaminated units" (50-499 ppm) my be the best way to assure special treatment. Obviously, such action necessitates scheduled one-tlae PCB analysis, but it facilitates compliance with the law. Thus, these two suggested steps provide:
. Inmdlate Identification for ongoing Inspection of units and recordkeeping.
. Minimise future disposal costs.
. Meet probable testiog prerequisite prior to any con tracted transformer maintenance work.
Consider this typical Laboratory data (about lBOQ samples of Mineral oil):
PCB Concentration
.1 > 1*99 ppm .2 50 - 1*99 ppm
3- < 50 ppm
4. 0 ppm (Pure mineral Oil)
Percentage of Samples Tested
10* 2k* 26* 40*
Two out of every three units tested will likely com tain less than 50 ppm PCB.
As transformer oils are tested for PCB-cooteat, baaed am the 50 ppm EPA standard for PCB Item, waits eaa than be properly labeled, where beneficial.
3. Voluntary Periodic Inspection
Consider all possible precautions that can prevent a
pill-
...
a. Establish a checklist for periodic Inspections.
1. Insure that units are structurally sound.
Label, for PCB items containing 50-499 ppm are not required before October 1, 1979. 3
*QNS
014805
,2 Cfcae*
fBBfcgt liilu (eorvrt, iund-holt or
bushlaga).
). Cheek sampling velvet and other fitting*.
4. Check pumps and cooling radiator* for leak*.
b. Satabllsh a consistent schedule for auch tnspee-
Atlon (monthly nlnlauM).
e. Consider diking and curtrlng for units near weterways.
\ d. Begin to establish a spill prevention plan - a
cries of operations procedures to be followed in the performance of a PC activity (operating or teeting apparatus).
c. Begin to prepare a control and countermeasure plan-to be followed when a release of PCBs occurs at a PCB use or servicing operation.
4. Maintenance
Routine maintenance (oil testing, and so forth) bv tha owner or outside contractor of all units is permitted.Howevejjacontractor performing transformer eervleing Is required to obtain a special annual n authorisation.
PCB contaminated transformers (50-499 ppm PCB) may be
topped off, refilled or rebuilt with dielectric
fluids containing leas than 500 ppm PCB. Existing
natural filled unite nay be topped off with PCB die
lectric fluid. However transformer repair. Including
rewinding of eollalsnotpermitted on units of 500 or
ore p|u PCB.
But, PCB transformers retro-
fllled to PCI contaminated units may then be rebuilt.
During the next five years, EPA will be examining the use ef eubetitute insulating fluids In older units to determine the feasibility of phasing out all use of PCBs.
C. Out-of-Servlce Units
All out-of-service PCB Items (Table II) must also be properly labeled, whether spare units or those await ing disposal.
81m. April It, 1978. PCB liquid. ( 570 pp.) auit b. 41spewed of in only an EPA approved incinerator. All non liquid PCBs can be disposed of In an EPA approved chemical waste landfill.
The various PCB items must be labeled and stored as summarised In Table III for PCI Items containing more than $0 ppm PCB, unleas otherwise stated.
A transformer declared as a spare can remain In a substation. If the unit is declared for disposal, then It mint be moved to an EPA approved storage raclllty pending appropriate disposal.
1. Per--nent Disposal
The only known way to permanently remove PCB* from the environment la high temperature (at lea.'t 1200C) in cineration with proper dwell time. EPA regulations ro longer permit etorage of PCB liquids > 50 ppm. How ever, at present only two approved Incinerators are
Several other companies have applied. One was approv ed, but local ordinal,..# shut the facility down. Becuus? of thia delay In obtalalng permits --d delivery of
*Ih* flret Incinerator still may not be EPA approved until September 1, 19T9.
equipment. It will probably be several pears before sufficient Incineration capacity will be available.
Until such tins ss IPA spproved PCB liquid inn Inert tion becomes feasible, hang looseI Even now,prac tical logistics -- distance and backlog -- make 1--dlate Incineration difficult. Therefore, hold oa to the liquid in CPA-DOT approved containers. Store properly and inspect It weekly until dispoael is practical.
Fortunately, the EPA recognizes the imitations of technical and economic feasibility to loeinerate all PCB items. Therefore the law permits disposal of PCB solids.contaminated liquids (90-499 ppm) at ETA approved chemical waste landfills or high efficiency chemical boilers. Ac least se-er approved chemical waste landfills are now "open". The boiler rating must be at least 50 million BTU per hour and must meet certain stack gas characteristics.
Since disposal In landfills will not result In PCB destruction, other new approaches now in the prototype stage may become available; e.g., the use of micro wave radiation.
PCB transformers, notably, can be permanently disposed of in a chemical waste landfill if all these coodltlome are met:
. The unit must be drained of all free-flowing liquid, and the liquid mu*t be treated in the manner pre scribed for PCB liquids in Table 111.
. It must then be filled with a suitable solvent (such as kerosene, xylene, toluene) In which FCBn are readily soluble. (Some of these liquids are also hazardous.)
. The solvent must be left In the unit for st least 18 hours, and the unit must then be drained thor oughly.
. The drained solvent -- which Is new a PCB item -- must be treated In the manner prescribed for PCB liquids in Table III.
Any PCB contaminated transformer f50-499 ppm PCB) requires only these steps:
. Transformer drained of all free flowing liquid.
. The dielectric fluid stay be disposed of in a chemical waste landfill or high efficiency boiler.
. Drained transformer carcass stay then be disposed of in a municipal landfill or sold for salvage.
2. Temporary Storage for Disposal
Storage for disposal means temporary storage of PCB* that have been designated for disposal. Table IT lists the provisions for temporary storage of PCB articles, equipment or containers.
Wien storage Is desired prior to disposal, coot--la sted PCB liquids (50-499 ppm) and non-liquid PCBs must he stored in an EPA approved storage facility.
An EPA approved storage facility has been defined as a roofed, walled and diked enclosure with aa imper meable floor, such as Portland cement concrete or steel. Bo storage facility may be located at a site which is below the 100 year flood water elevation (that is, a flood lhat has an average frequency of occurrence in the order of onee in 100 years). Therw-
HONS 014806
Table III
Permanent Disposal or Long Tore Storage of PCB's Pending Disposal (Por PCI items of 70 ppm or more, unless otherwise stated)
Disposal Mens the Intentional or accidental discharging or other completion or termination of the useful Ilfs of an object or subfynce.
TZM PCI liquids (> 500 ppm)
disposal provisions \
Disposal In EPA approved hi-temp, incinerator. Ho storage permitted.
PCI contaminated nlnersl oil dlslsetrlc fluid (50-499 ppm)
Disposal In EPA approved hl-temp. Incinerator; EPA approved chemical waste landfill or an high efficiency boiler.*
PCI contaminated waste liquid ($0-499 ppm) euch ss hydrau lic or heat transfer fluids.
Disposal In EPA approved hl-temp. incinerator; EPA approved chemical waste landfill or an EPA approved high efficiency boiler.*
Sam-liquid PCBe; contem-
laated soil, rags, or other debris from uncontrolled spill (trash* trees* lumbar).
Disposal In EPA approved hl-temp. Incinerator; or EPA approved ehemlcal waste landfill.* However, ltens may be considered to have been disposed of if they were deposited In a chemical waste landfill before 4/18/78.
Ron-liquid PCS waste; dredge spoils, municipal sewage-
trsatasnt sludge*
Disposal In EPA approved hl-temp. Incinerator. EPA approved ehemlcal waste landfill* or by other EPA approved method.* The digging up of debrio smd other Items disposed of In s landfill prior to 4/18/78 Is not required but the intent of the rule is that you can't add to an existing site end let It sit.
PCS transformers {> 500 ppm)
Disposal in EPA approved hl-temp. incinerator or EPA approved ehemlcal waste landfill, following procedure given in article text.*
PCS contaminated trsnsformer (5<V499 ppm)
Disposal in municipal landfill or sold for salvage following procedure given in article text.
PCS largo high or low voltage capacitors (mors than 3 pounds or 1 quart of PCS liquid)
Disposal in EPA approved hl-temp. incinerator; disposal permitted until 1/1/80 In EPA approved chemical waste landfill.*
PCS small capacitors (less than 3 pounds or 1 quart of PCS liquid)
Capacitors owned by capacitor manufacturers or PCB article manufacturers (production quality-control rejects, etc.) to be disposed of la hi-temp. Incinerator; disposal permitted in EPA approved chemical waste landfill until 1/1/80. All other small capacitors nay be disposed of ss nMetpal solid waste.
PCS hydraulic machine (dle-castlng)
Disposal ss municipal solid waste or sold for salvage following piotciBrnse given in article text.
Other PCS articles
Disposal In EPA approved hi-temp Incinerator, EPA approved chemical waste landfill; following thorough draining and proper disposal of PCB liquid,*
PCS container ( > 500 ppm)
Disposal In EPA approved hi-teM. incinerator or EPA approved chemical waste landfill (following temporary storage at an EPA approved facility until properly drained and PCB liquid has been properly disposed of).*
PCS container (50-499 ppm)
Disposal as municipal solid waste, following proper draining smd disposal of PCB contaminated liquid.
Long tern storage of this item is permitted in ETA-DOT approved containers and/or located in an EPA-approvod facility until 1/1/8M.
HQHS 014007 5
Table XV Tognrary Storage of PCB Items Pending Disposal
rrm
STORAGE PROVISIONS*
Ben-leaking PCB artlele or equipment.
___________________________________ 11______
Storage In temporary area up to 30 days instead of standard EPA defined facility. Check weekly for leaks. Long term storage required after 30 days in roofed and diked enclosure vith Impermeable floor until 1/1/8L. Check at least once everv % days for leaks.**
Bon-leeklng structurally undem^sd large high voltage PCB capacitor , PCB contma-
1nated tre&gforaer
^
Long term storage on skids next to an EPA defined storage facility until 1/1/83. This make* e facility imediately available If a leak should
develop. Reason: In case of delay in the construction of proper incineration facilities or for new capacitors to be used at a construction site; cheek weekly for leaks.
Leaking PCB articles and .Mi-lit______________________________
Stored In non-leaking EPA-DOT approved containers for up to 30 days (containing sufficient sorbent materials to absorb llauids PCtel
PCB containers containing non liquid KBs (soil, rags) or lleuld PCBe (50-1*99 om).***
Storage in temporary ares up to 30 days Instead of standard EPA defined facility, provided a spill prevention control and counter measure plan prepared.
Leek, leakage or leaking means any Instance In which a PCB article, container or equlpamnt has any PCB am any portion of its exterior surface.
Date PCB item removed from service noted on the KB item.
It Is no longer permissible to store dnam of liquid PCBe (> 500 PPM).
for*, imediately contact your rational office of U.S. Geological Survey for a hydrological nap that docu ments whether or not your praaaot alt* la adaquat* or should be relocated.
3* Boeordhseolng
Za conjunction with dlspoaal requirements, the trans former oneer/operator must keep the following data for the annual ecopoaltc record, documenting the atatua of KB ltana elated for disposal:
. Date renewed fron service.
. Date placed Into storage pending disposal.
. Date placed In transport for disposal.
. Total weight (la kilogram) and Identification of KBa la FCB containers.
. Total number of PCI transformers end total weight (In kilograms) of nay KBe contained In the trans formers.
. Total number of large high or low-voltage PCB capacitors.
. Location and nams of ownsr of initial storage or disposal facility (Bill of lading).
It le peralsaible to determine the weight of PCB by calculation (using valid assumptions of the density of the PCB chemical substance or mixture) if the volume of the container or transformer la known.
failure to keep these proper record# is a clvi^ vio lation of the PCB law.
D. KB Spills
Spills and other uncontrolled discharges of liquid KBa are defined as disposal; therefore, proper procedures nuat be undertaken.
Ignoring or attempting to conceal a leak, a spill, or other uncontrolled discharge of PCB Is engaging In mlavful disposal and subject to cjggaj pro--cutlorn.
1. Preventive Action
Weekly inspection for all Items temporarily stored la non-EPA approved facilities or on skids; 30 day mini mum Inspection for all item stored in sn EPA approsad facility. Experience has already shown that inspec tion for leakage should be aade more often than every 30 days -- even with new PCB containers, la antici pation of possible rules for hazardous spills, spill prevention is the only sure vey to treed a spill sit uation.
2. Corrective Action
a. In the Event of Minor PCB Leakage
Proper actions_to..he taken consist of:
. Transfer leaking containers and articles, and their contents, to properly marked, nonleaking containers.
. Use sorbents such as imbiber beads to eleen up any spilled or leaked material iamedlately.
. Dispose of (or store for future disposal) residue -- indicated in Table III or IV.
b. In the Event of a Major Spill MOHS Oi^lO
A PCB spill is any discharge of sufficient magnitude to give reason to euapect that It hma produced, at any point In the surrounding soil, gravel, sludge* fill, rubble, or other land-baaed substances, n PCB centms ination level exceeding 50 ppm. The following nee surea must be taken in the event of a spill.
. Transfer leaking containers and artlelee. and their contents to properly marked, nonleehlng containers.
. Use sorbents to clean up any spilled or leaked mate rial imediately.
. Dispose of (or store) residue ee indicated In Table III or XV.
. Conduct tests, using EPA-approved sampling teehniftMt end laboratory Methods, to determine If PCB eonceutration in soil. etc., exceeds 50 ppm.
. Decootlost# areas containing uore than 50 ppm of PCI in accordance with EPA regulations.
M
Several companies hare already established their own epeelel tesMS that are sent out to handle PCB spills and clean up. Contracted cleanup services certainly could also be an option.
Ill, EPA Approved Methods of Testing for PCB Concentration
Implementation of the foregoing guidelines requires first e procedure to readily identify transformers containing PCB Mixtures.
--Although testing for PCB content in oil by electron capture gas chromatography (GC) is the most prevalent laboratory nathod,T the Betistetn field test can be a preliminary test to detect PCBe at a level of five (5) per csnt (50,000 ppm) or greater. Very few units are this grossly contaminated.
Since evidence has shown that more than 100 ppm PCB la mineral oil tends to reduce the Impulse strength of oil, testing would indlcats suspect units. The technology to rsmovc PCBs from mineral oil Is being actively developed to assure the transformers max* Imam design lightning strike capability.9
IV. Other PCB Associated Federal sad State Laws
Taplsmemtstlnn of the foregoing present and projected regulations la no way precludes compliance under other regulatory rulings. In fact the Intent of the various statutes Is integrating all facets of the PCB problem yet without doing so at cross-purposes.
The two most iaportent PCB associated documents are (1) The Resource Conservation and Recovery Act (RCRAP.L. #9b-50, 1976). Involving hasardous waste manage ment and (?) Section 311 of the Federal Water Pollu tion Control Act (PWFCA-P.L. #92-500, 1972).
Even though detailed rules of RCRA nay not be pub lished until nld-1960 and Section 311 Is under a court injunction declaring It void, existing state lawa Indicate that the prudent way to go would be to prepare even no*.* for inevitable U.S. regulations In erne form or another. 1
Suggested steps that should be tsdten Includes
1. Inventory of PCB ltesm - In service units, spares or units pending disposal (Required under current PCB rule).
2. One-time PCB in oil analysis (best way to assure proper transformer treatment).
3. Tracing of PCB wastes (manifest system).
Several states already require a manifest system ("eradls-t^gravs" paperwork) for off-slte dis posal. The manifest Is defined as the form used for Identifying the quantity, composition, origin, routing, and destination of PCB liquids and solids, during transit from the point of generation to the point of storage or disposal.
Therefore, begin a bound logbook containing this data (compliance under RCRA and/or state lav).
h. Assigned clear responsibilities!!
a. Make sure that specific technical and legal people are involved In day-to-day dacisloas on PCB storage and disposal.
b. Inform other company personnel as to the latent information on how to make a "reasonable effort" to comply with all regulations.
5. Transportation for disposal.12
a. Train shipping personnel.
1) Proper packaging and labeling:
Per EPA-Departaent of Transportation (DOT) specified containers for PCB liquids or nomliquid PCBs. Mineral oil dielectric fluids of unknown concentration any be shipped via United Parvel Service (UPS), but sskarsl liquid should be shipped with a Class B poison label. Therefore, aakarel cannot bs shipped by UPS.
2) Response control and countermeasure plan when PCB release occurs.
b. Provide truck drivers with complete bill of lading and current response information la case of an accidental spill. Include phone nunbera of site destination point and reg ional EPA. Start reporting now harmful quantity discharges near waterways to the Rational Response Center: (800) kgt 08og (under FVPCA, Section 311).
6. Keeping abreast of state legislation - transit of hazardous wastes; both home state sad those thru which shipping likely will go.
7. Review of off site disposal agreements. Written contract should spell out In detail what you am PCB generator will do and what disposal contractor will do. When do title, ownership end rlshs transfer frm the PCB generator to disposal corntractor?
8. CAUTIOH: You cannot asstae PCBs are being propel ly disposed of. You should follow thru - sake regular checks of waste contractor and routine on site Inspections. Evaluate the facility In terms
of competence, staffing, permits, problem history and general suitability for PCB disposal, las fa
cility received U.S., State and local approval for disposal?13
V. Other Options Available to Owners of PCB Transformers
Rstrofilllng or replacing a PCB transformer arm *>* alternatives, in addition to retaining PCB omits.
A. RetrofUl Aakarel-Filled Unit With Boa-PCl Alternative Coolant^*
The residual mixture should be tested at leeat an nually (preferably more frequently) to determine its exact PCB content, as It will flora*** as It seeks
equilibria.
M0NS 014809
Using retref111 procedures only ona tins will probably
T
till result la contaminated transformer that would' haw* to bo treated as on aakarel unit in all
other respects. Therefore, retroflll la actuality MUlli a serins of retrofllls smd/or nbuqnt filtering with activated carbon.
Ivm than tho unit ttlll night be treated aa a PCB Item, depending upon concentration; however, the po tential economic liability beconea considerably leas than the cost of decontamination In the event of a pill Involving a concentrated PCB.
Dlapoeal of both existing PCB liquid and flushing
liquid requires Incineration.
long as disposal
thru incineration remains a problem, the best lo
cation for PCBa la the transformer Itself.
However, when sufficient facilities do become approved, retroflll may be the primary vehicle in preparing Tor ultimate disposal of PCB transformers and thus phoning out of askarel-fllled transformers.
B. Replace the Ankara!-FIlied Unit
If a transformer le located near a drainage canal, strew, or waterway the only safe option Is to replace the unit with one containing a non-FCB coolant, gas dielectric or an air-cooled, dry unit.
Location, use and nameplate capacity required would determine this final choice.
VI. Conclusion
Much criticism has been directed toward the expense of SPA regulation. It Is a fact that the long term effect of PCB on the food chain may not be known for years. 15
Yet public support for costly environmental protection remains strong.1 That's because of the high cost of the alternative -- not regulating.11
la any event, while the Issue of PCB control continues la a state of frustration, the best route to go is to keep informed of the latest state and loeal regulations and to sake a "reasonable effort" to comply with exist ing federal regulations (required narking, record keeping,voluntary inspection, and suggested one-tine PCB analysis of transformer alnersl oils).
9. B. 1. Rsab, o. clt.. August 3, 1970 and April li, iSiy.
10a. R. 8. Clsublnger, "A Guide to the Reseueee foe nervation and Recovery Act, Chemical Sul--ring Magaxlne, McGraw-Hill. New York. H.Y., January 29, 1979, PP 79-01.
b. Richard Sobel (Allied Chemical Corporation), "How Industry Can Prepare for RCRA," Ibid, pp.
82-85. c. T. K. Maugh 11, "Toxic Waste Disposal a Growing
Problem." Science.American Association for the Advancement of Science (AAAS), Volume 20k, ?) May 1979, p. 819. 11. W. 0. Beebe (Potomac Electric Power Company) - .. "Askarel/Polychlorinated Biphenyl (PCB) Pro cedures," Minutes of the kgth Annual International Conference of Doble Clients, 1979, Doble Engi neering Co.; Watertown, Mass., Section 10B-1. 12. Ken Snow (Flying Tiger Line) "Shipping Natardous Material," Chemical Engineering Maaaiine- McGrmw Hill, New York,*.*., November 6, 1970, pp 102
100 (Discussion of Dept, of Transportation DOT regulations.)
13. Allan Hall, "Waste sites may be major liability for CPI" Chemical Week. May 2, 1979, p 10.
lk. T. O'.leil A J. J. Kelly, "Silicon- Retroflll of
Askarel Transformer*',' Minutes of the 13th Floctrlesl/Eleetronic Insulation Conference, Chicago, IL Sept. 29, 1977. p. 167. 15a. John Walsh, "EPA and Toxic Substances Law: Deal ing with Uncertainty," Science. Voluse 202, 10 November 1970, p 598.
b. Bruce N. Ames (Professor of Biochemistry, U. of
California, Berkeley),"identifying Environmental
Chemicals Causing Mutations and Cancer."Science.
Vol. 20k, 11 May 19T9. p 507.
-
16. Luther J. Carter, "Public Support for Environ
mental Protection Remains Strong," Science. Volimae
203, 12 January 1979, p 15k.
17. Nicholas A. Ashford (Associated Professor of
Technology A Policy, Massachusetts Institute of
Technology), "A plea for a new kind or realism,"
The New York Times, Business Section, December
17, 1978.
VII. References
1. Microeconomic Impacts of the Proposed PCB -SsaJXsfiulatloms. Versar. Inc. (EPA #560/6-77-35. Hay 1970.
pp 7, 37-30. 2. D. E. Hutchinson, American Electric Power Service
Corporation "Regulatory Status of the PCB Sub stitutes," 1979 Winter Meeting, Hew York,Hew York, IEEE Power Engineering Society, February 6, 1979,
,, 4-7. 3. Edward L. Rank (Retired, General Electric Co..Pitta-
field, Mass.) in conversation held at Transformer Consultants, Div. S. D. Myers, Inc. Akron, Ohio,
Auguet 3, 1970, sod April 11, 1979. k. R. R. Parrish A J. J. Kelly "Warning: TSCA May be
Haxardous to Your Professional Health," Plant Engineering*. May 11, 1979, p. 133. The~197& law
Is found In the Federal Register. February 17, 1970, Vol. k3. Ho. 3k, Part V, pp 7150-7l6k. The 1979 "PCB Baa" Rule published May 31, 1979, la located in the Federal Register. Vol. Uk Ho. 106, Part VX, pp 3151k-31550. 5. E. L. Raab, op. clt., August 3, 1970. 6. Stepe d A may be required under Section 311 of the Water Control Act. Some states already have such. T. 0. Hettinger, S. Safe, V. Zltko, The Chemistry of PC2lCRC Press, Cleveland, Ohio 197k, pp 207,
210-212. ____
0. U.8. Navy HEF88 (Naval Environmental Protection Support Serv.)Information Bulletin,! July 1970.
HONS 014810