absorbed by the CaSO, and thus desired limits can be set up and monitored. In an article describing the use of detec tor, the manufacturer reports that he has checked coils in ten seconds. This method be applied for moisture limits be tween 2 and 60 milligrams. Corrections must be made for variations in the desiccant grain size, quantity of air pmawl through the desiccant, and difference in instrument and com ponent temperatures.
Karl Fischer Method. In systems containing refrigerant and oil, moisture may be determined by measuring the dielectric' strength, or by the Karl Fischer Method.12 In this method a sample from the unit under test is condensed and cooled in a mixture of chloroform, methyl alcohol, and Karl Fischer reagent. Then the refrigerant is allowed to evaporate as the solution warms up to room temperature. When the refrigerant has evaporated, the remaining solution is titrated immedi ately to a dead stop electrometric end point, and the amount of moisture is determined. This method requires a sample of 60 to 60 g, and takes about one hour to perform. It is generally felt that it is not accurate below 15 ppm; however, as the method does not require that oil be boiled off the refrigerant, it can be used for checking complete systems. Reedu points out that additions to the oil must be checked in order to malm make sure that they do not interfere with the reactions of the method. The Karl Fischer Method may also be used for deter mining moisture in oil alone.12-12
Infrared Spectrometer. Another method reported in the literature is the use of the infrared spectrometer.1* This method utilizes infrared light passed through chemicals that show selective absorption. The energy of light transmitted through a sample, when compared to the energy at the source, is a measure of the moisture content Oil is likely to be a problem, because the hydrogen absorbs infrared-light at nearly the same wave length as the hydroxyl band in water,' thus decreasing the sensitivity of the instrument to moisture^' A- fairly large sample of refrigerant is required for accuracy, although Gray17 reports making the test instrument part of a system to test desiccants, thus securing an infinite sample. Gray also reports that this method is entirely suitable for Refrigerant 12, but that it cannot be used for Refrigerant 22.
Instrument described by Taylor,M Taylor described an in strument specifically designed for moisture analysis and based on the principle of Faraday's Law. Refrigerant and direct current applied to the electrodes causes the water to break down into H and 0. The current flowing due to electrolysis is directly proportional to the amount of water present, in accordance with Faraday's law. Taylor used the instrument for a pure refrigerant, but he believes that oil interfere with accurate measurement. In tests on desiccants. Gray found this method quick and accurate with Refrigerant
22.
Method described by Brisken.19 A method utilising a very small sample, which can be used on a unit charged with oilj is described by Brisken- A modified Aminco-Weaver Water Vapor indicator was used in order to study the migration of moisture in a hermetically sealed cycle. The Aminco-Weaver instrument uses the electric conductance of a thin hygroscopic film to measure moisture content, and the use of a gas of known moisture content for comparison purpose avoids the necessity of securing absolute conductance measurements. The instrument requires as little as five cubic centimeters of vapor to secure a test. Although it is* objectionable if oil coats the detector, a small oil trap reduces this hazard, and fjftaning the detector is a quick and relatively easy task. Although this instrument has been used effectively,- gives fast results, and requires only insignificant amounts of refrigerant.
its operation and the interpretation of the data require a care ful and intelligent operator. '
A point of interest for any method of moisture determina-'
tion can be found in Reference 19 where a report on migration
in a hermetic system is given. In his tests, Brisken found that
the true moisture levels could be found only after the system
had been running long enough to establish equilibrium be
tween the moisture content of the vapor and the liquid, and
where the cellulose of the motor had given up to the system
the amount of water that it could not hold at operating tem
perature. It is.well to remember in this connection that each
refrigerant has its own moisture equilibrium curve between
liquid and vapor phases, and that where the moisture content
is determined in a static system, these curves must be
utilized.
Weaver30 originally developed the method in which the electri
cal conductivity of a film in equilibrium with the moisture
contained in a gaseous refrigerant is measured.
Sight Glass Indicator. In fully charged systems, a sight
glass indicator can be utilized in the refrigerant lines. This
device consists of a colored chemical button visible through
the sight glass, which indicates excessive moisture by a change
in color. This method requires that the system be run for a
reasonable length of tima in order to allow moisture to cir
culate over the button. Obviously, this method compares
moisture only qualitatively to a fixed standard. It has been
used on factory-dehydrated split systems, in order to make
sure that they are dry after field installation and charging.
Special Considerations. Although all methods described in
this section can be used effectively to measure moisture, their
use in the factory requires certain precautions. Operators
must be trained in the use of the equipment, or if the analysis
is made in the laboratory, the proper method of securing
Rxmplpq must be understood. Sample flaw!TM must be dry and
free of contaminants, lines must be clean, dry, and properly-
purged. Procedures as to weighing of the sample, time during
cycle, and location of sample part, should be clearly defined
and carefully followed. Checks and calibration of equipment
must be made on a regular ba^g, if consistent readings are to
besecured.
CHARGING
The accuracy needed when charging refrigerant or oil into
a unit depends on its size and application. Charging equip
ment must also be adapted to .the particular conditions of the
plant.' Either manual or automatic charging devices are used.'
Manual Charging. Most' manual devices require the
operator to fill a cylinder to a given point, and then discharge
that volume into the system. To minimize operator error, the
liquid column is magnified. If the accuracy required is plus
or minus a. quarter .of an ounce, for example, the column
fihnnlH be so thin that one inch of column length equals a
quarter of an ounce. Since this device is primarily volume
charging, the temperature of the liquid must be kept constant
when charging, or the necessary corrections for temperature
variations must be made. Heat lamps can be used to keep the
temperature constant and avoid the necessity of coriection. '
The disadvantages of manual charging are.obvious. It is
time consuming and subject to operator error.
'
Automatic Charging. This method combines both speed and
accuracy. Automatic charging boards charge by weight, and
fully automatic boards check the vacuum in the unit, evacu
ate the charging line, and meter the desired amount of oil and
refrigerant into the system.
Automatic charging boards are rather complex and must be
carefully maintained to avoid malfunctioning- A visual
metering device for flow observations or direct measurement
Factory Dehydrating, Charging and Testing
761
of the quantity charged into the system is therefore rearm-'
mended.
Special Considerations
As a general rule, refrigerant and oil must -be carefully
handled during charging. Also, the decision, of where to charge and in what order, may have a great deal of bearing on the life
0f a system. If a complete unit is charged prior to perform
ance testing, the presence of Uquid refrigerant in the crankport may cause damage due to slugging. If the oil is added
after the refrigerant is already in the crankcase, excessive fuming and oil vapor lock may occur with possible bearing
damage.
'
Obviously, refrigerant lines must be dry and clean, and all
purging lines must carefully be kept free of moisture and
norv^nHongahle gases. Also, new containers must be connected
with proper purging devices. Carelessness in observing these precautions may result in excessive moisture in the refrigera
tion system.. Oil drums must be stored lying on their sides to prevent
accumulation of dirt and water on top which might get into the oil as soon as a drum is opened. Drums of oil should be
opened in the last moment before charging, even when the oil must be degasified. Regular checks for moisture or contamina tion must be made at the charging station, and samples for
analysis must be taken from each lot of refrigerant and oil
after delivery.
TESTING FOR LEAKS
Loss of refrigerant by leakage has always been a serious problem to industry and, consequently, testing for leakage is extremely important. Extended warrantees and critical re frigerant charges add to the importance of proper testing.
Basically, allowable leakage rate depends entirely upon the system or component characteristics. Any leak on. the.lowpressure side of a system operating below atmospheric pres sure is dangerous, no matter how large the refrigerant charge. A system having four to six ounces of refrigerant and a fiveyear warranty must have virtually no leak, whereas in a sys tem having ten to twenty pounds of refrigerant the loss of an ounce of refrigerant in a year is not critical It must be recog nized that there is a certain element of risk in establishing any leak sensitivity, because a small hole could conceivably open up in time or even during shipment. It is also entirely possible that small leaks will vanish later due to impurities in the sys tem which may close the openings.
Leak Detection Methods
Water Submersion Test. The most popular method of leak detection in use in the refrigeration industry today is the water submersion test. In this method a component or unit, under positive pressure of dry gas is placed in a water bath and observed for bubbles that indicate a leak, This method is simple and reliable, and requires a minimum of operatortraining. Some precautions must' be taken, however, to avoid errors.
The tank in which the item under test is submerged should be clean and well lighted. The water should be filtered and heated to free it of all trapped air. Carriers should permit observation of all portions of the tested unit, and should be designed to carry as little air into the tank as possible, be-
cause bubbles released by the carrier tend to1 distract the observer or may cause errors. The pressure used should be as "gh as possible, dependent on safety requirements. Apressure of 250 lb seems to be generally osed.
r^ie sensitivity of the' water submersion test cannot be clearly defined, since pressures and timp in the tank may
vary considerably, but the minimnm leak rate that can be' consistently determined, is 1/1000 standard cc per sec. This is roughly equivalent to one ounce of refrigerant per year.-' However, a considerably higher leak rate per year must be . expected because a number of individual leaks smaller than the minimnm observable oould possibly exist and add to the-leakage found by test
To establish the length of time that the unit should be under water, a calibrated leak should be used to establish the bubble frequency. If the desired rate results in a bubble per minute, then the unit should be in the water a minimum of three minutes, to allow the observer a chance to confirm a leak.. The sensitivity of all the systems discussed in this chapter is at a marirngm, if the leak checking can be accomplished be-' fore painting, since a fine opening can be temporarily sealed by paint. It is also to be noted that water can seal small leaks. < Units should, therefore, be thoroughly dried before further Iftftk testing is done.
A modification of the submersion method is application of soap suds to a component or unit under pressure. This system has fundamentally the same sensitivity as the submersion method, but it is considerably slower, and is used only oh very large systems, or as a method of finding a leak for repair purposes.
Pressure Testing. Another leak detection method that falls into the same sensitivity range is the pressure method. The unit or part is either pressurized or evacuated, and then the pressure decrease or rise is measured against time. It is impor tant to maintain constant temperatures in order to eliminate pressure variations. -
Pressure testing is simple and reliable, takes very little plant investment, and determines total leakage. Disadvantages are that the time required to measure a significant change is fairly, long, and that the location of the lealTM cannot be determined.
Halide Leak Testing. Units or components charged with, refrigerant containing a halogen may be leak tested with a halide torch or an electronic leak detector. Halide torches normally produce an almost colorless flame or flame of faintly, blue color, but its color will change to a greenish blue in the presence of a halogen, varying in intensity with the size of the leak.
The sensitivity of the halide torch is about the same as that of the preceding methods, although sensitivity depends on the pressure in the unit and on the color perception of the opera tor. To test a unit at ambient temperatures, a small charge of refrigerant gss is backed up with air or nitrogen pressure to insure a driving force of reasonable magnitude.
Halide torches are influenced by refrigerant contamination,and become ineffective in locating amall Ipnka when the unit has a large leak. If the torch is used, each joint must be probed carefully for small leaks; therefore the unit or part must be leak tested while all joints are exposed.
Electronic Leak Testing. The electronic type leak detector consists of a probe that draws air over a platinum diode whose positive ion emission is greatly increased in the presence of a halogen gas. This increased emission is translated into a visible or audible signal. Electronic leak testing shares with' halide torches the disadvantages that every suspect area must' be explored, and that contamination makes the instrument less sensitive, but it haa some marked advantages. The main advantage is increased sensitivity. With a well maintained' detector it is posable to identify leakage at a rate of I- X 10"* standard cc per sec which is roughly equivalent to the loss of one ounce of refrigerant in 100 years. Another advantage is that the detector can be calibrated in a-number ofways, so that a leak can be quantitatively measured..The instrument also can be desensitized to the point that leaks,below a pre-