on the steam branch down to the radiator may be omitted if an overhead ^ valve, as shown in Fig. 13, is used. This method is also suitable for vacuum, sub-atmospheric, and orifice systems.
Convector Connections
Convectors often are installed without control valves, a damper being used to shut off the flow of air to retard the heat transfer from the con vector even though it is still supplied with steam. The piping connec tions for a convector with the inlet and outlet at the same end are shown in Fig. 14. There is no valve on the steam side but there is a thermostatic trap on the return. The damper for control is shown immediately above the convector. This piping is suitable for atmospheric, vapor, vacuum,
Chapter 32--Piping for Steam Heating Systems
return were on a vacuum, atmospheric, sub-atmospheric or orifice system, the treatment would be identical.
On all heating units it is important to use a nipple the full size of the outlet and to reduce the pipe size to the normal return size required, by the use of a reducing ell, as indicated in Fig. 21.
Pipe Coil Connections Pipe coils, unless coupled in a correct manner, often give trouble from
short circuiting and poor circulation. The method of connecting shown in Fig. 22 is suitable for atmospheric, vapor, vacuum, sub-atmospheric, and orifice systems.
Fig. 14. Convector Con nections Same End
Fig. 15. Horizontal Fin-Type Heating Unit
Fig. 16. Heating Unit Valves Behind Grille
!
Fig. 17. Heating Unit with Valves in Basement
u Cabinet type
Fin radiator
MIff
Fig. 18. Fin-Type Heat ing Unit in Cabinet
eindirect radiator
Full size of tapping Dirt pockef
Fig. 19. Piping Connec tions to Indirect Radiators
I
1
sub-atmospheric, and orifice systems of the up-feed type. A similar unit with connections on opposite ends and suitable for the same systems is shown in Fig. 15. This unit has no damper but requires a valve on the steam connection for control. When valves must be located so as to be accessible from the supply air grille, the arrangement usually takes the form indicated in Fig. 16. A convector located in the basement and supplying air to a room on the floor above may be piped as pictured in Fig. 17 for all systems except gravity one-pipe or. two-pipe systems. Convectors with damper control, installed in cabinets or under window sills, usually are connected as shown in Fig. 18.
Vapor systems with heating units in the basement where the returns are dry would be treated as in Fig, 19. Similar heating units where a wet return is available would be connected as shown in Fig. 20. If the dry
592
Indirect Air Heater Connections
Heating units for central fan systems have simple connections on the steam side. The steam main is carried into the fan room and has 'a single branch tapped off for each row of heating units. Each of these main branches is split into as many connections asmeed be made to each row, governed by the number of stacks and the width of the stacks. Each stack must have at least one steam connection, and wide stacks are more evenly heated with two steam connections, one at each end.
593