HEATINC VENTILATING AIR CONDITIONING CUIDE 1944
Burning Oil Fuel3 is intended to provide a standard method for con ducting and reporting tests to determine the heating efficiency and per formance characteristics when oil fuel is used with steam heating boilers. In 1938 the Society adopted a Standard Code for Testing Stoker-Fired Steam Heating Boilers4 which is intended to provide a test method for determining the efficiency and performance characteristics of any stoker
Table 2. Steel Heating Boiler Standard Ratings2
Hand-Fired Ratino
U Mechanically-Fired Rating
Steam Radiation
Sq Ft
Catalog
Water Radiation
Sq Ft
Btu per Hour in Thou sands
Net Load
Steam Radiation
Sq Ft
Heating Surface
Sq Ft
Grate Area Sq Ft
Steam Radiation
Sq Ft
Catalog
Water Radiation
Sq Ft
Net Load Furnace Vol
ume, Oil, Gas Btu per Steam or Bituminous Hour in Radiation Coal Cu Ft Thousands Sq Ft
1,800 2,200 2,600 3,000 3,500 4,000 4,500 5,000 6,000 7,000 8,500 10,000 12,500 15,000 17,500 20,000 25,000 30,000 35,000
2,880 3,520 4,160 4,800 5,600 6,400 7,200 8,000 9,600 11,200 13,600 16,000 20,000 24,000 28,000 32,000 40,000 48,000 56,000
432 528 624 720 840 960 1,080 1,200 1,440 1,680 2,040 2,400 3,000 3,600 4,200 4,800 6,000 7,200 8,400
1,389 1,702 2,020 2,335 2,732 3,135 3,540 3,945 4,770 5,608 6,885 8,197 10,417 12,500 14,584 16,667 20,834 25,000 29,167
129 158 186 215 250 286 322 358 429 500 608 715 893 1,072 1,250 1,429 1,786 2,143 2,500
7.9 8.9 9.7 10.5 11.4 12.2 13.4 14.5 16.4 18.1 20.5 22.5 25.6 28.4 30.9 33.2 37.4 41.2 44.7
2,190 2,680 3,160 3,650 4,250 4,860 5,470 6,080 7,290 8,500 10,330 12,150 15,180 18,220 21,250 24,290 30,360 36,430 42,500
3,500 4,280 5,050 5,840 6,800 7,770 8,750 9,720 11,660 13,600 16,520 19,440 24,280 29,150 34,000 38,860 48,570 .58,280 68,000
525 643 758 876 1,020 1,166 1,312 1,459 1,749 2,040 2,479 2,916 3,643 4,372 5;100 5,829 7,286 8,743 10,200
1,695 . 2,089
2,461 2,853 3,335 3,830 4,330 4,834 5,850 6,885 8,490 10,125 12,650 15,183 17,708 20,242 25,300 30,359 35,417
15.7 19.2 . 22.6 26.1 30.4 34.8 39.1 43.5 52.1 60.8 73.8 86.8 108.5 130.2 151.8 173.5 216.9 260.3 303.6
aAdopted by the Steel Heating Boiler Institute in cooperation with the Bureau of Standards, United States Department of Commerce Simplified Practice Recommendations R 157-35.
or boiler combination burning any type of solid fuel such as anthracite or bituminous coal.
The Steel Heating Boiler Institute has adopted a method for the rating of low pressure boilers based on their physical characteristics and ex pressed in square feet of steam or water radiation or in Btu per hour as given in Table 2. The' detailed requirements of this code were outlined in Chapter 13 of The Guide 1939.
The Institute of Boiler and Radiator Manufacturers has adopted a method of rating cast-iron heating boilers based upon performance obtained under tests. This code5 now applies to sectional boilers having a grate width of 41 in. or less. Eventually the Institute intends to include all sizes of cast-iron boilers in this program of testing and rating.
See A.S.H.V.E. Transactions, Vol. 37, 1931. p. 23. See A.S.H.V.E. Transactions, Vol. 44, 1938. p. 366. *1 = B = R Testing and Rating Code for Low Pressure Heating Boilers (Institute of Boiler and Radiator Manufacturers.)
242
CHAPTER 12. HEATINC BOILERS
BOILER OUTPUT AND EFFICIENCY
Boiler ratings are usually expressed either as gross output or net load. The gross output is the quantity of heat available at the boiler nozzle with the boiler normally insulated. This output is stated in Btu per hour or square feet equivalent direct radiation. The gross output of large heating boilers is frequently stated in terms of boiler horsepower.
Net load is the total amount of radiation that normally can be sup plied with heat by the boiler. It is expressed in the same units as gross output and is equal to the gross output less allowances for piping losses and pick up.
The term efficiency as used for guarantees of boiler performance is usually construed as follows:
1. Solid Fuels. The efficiency of the boiler alone is the ratio of the heat absorbed by the water and steam in the boiler per pound of combustible burned on the grate to the calorific value of 1 lb of combustible as fired. The combined efficiency of boiler, furnace and grate is the ratio of the heat absorbed by the water and steam in the boiler per pound of fuel as fired to the calorific value of 1 lb of fuel as fired.
2. Liquid and Gaseous Fuels. The.combined efficiency of boiler, furnace and burner is the ratio of the heat absorbed by the water and steam in the boiler per pound or cubic foot of fuel to the calorific value of 1 lb or cubic foot of fuel respectively.
Solid fuel boilers usually show an efficiency of 50 to 75 per cent when operated under favorable conditions at their rated capacities. Oil- or gas-fired boiler-burner units usually show an efficiency of 70 to 80 per cent.
SELECTION OF BOILERS
Factors Involved in Boiler Selection
The maximum design load on a boiler is the sum of the following four items:
1. Radiation Load. The estimated heat emission in Btu per hour of the connected radiation (direct, indirect, or central fan) to be installed.
The connected radiation is determined by calculating the heat losses for each room in accordance with data given in Chapters 4, 5, and 6. The sum of the calculated heat losses for all the rooms represents the total required heat emission of the connected radia tion expressed in Btu per hour. As practically all boilers are now rated on a Btu basis, it is unnecessary to convert the radiation load to equivalent square feet of equivalent radiation.
2. Hot Water Supply Load. The estimated maximum heat in Btu per hour required to heat water, for domestic use.
When the hot water supply is heated by the building heating boiler, this load must be taken into consideration in sizing the boiler. A common practice is to add 240 Btu per hour to the radiation load for each gallon of storage tank capacity. For more specific information see Chapter 46.
3. Piping Tax. The estimated heat emission in Btu per hour of the piping connecting the radiation and other apparatus to the boiler.
It is common practice to consider the piping tax in average house heating systems to be equal to 25 per cent of the net load (items 1 and 2). In large jobs, or where there is much bare pipe, it is better to compute the heat emission from both bare and covered pipe surface in accordance with data in Chapter 18. The estimated heat loss from the pipe should be added to the net load when estimating the gross boiler output.
4. Warming-Up Allowance. The estimated increase in the normal load in Btu per hour caused by the heating up of cold radiation.