February 2, 1971 Fire-Resistant Requirements For Capacitor Dielectrics?^
R. H. MUNCH - OUKKNY
fS
II cM
W. R. Richard - WRICH H. 3. Bergen - HBEM
T. L. Ooseage - T003S J. R./Savage - JSAVA J. IK Pallon - JFALL
J. 0. Bryant - JBRYA
The subject la ''moot" and difficult to asseas In the search for new and especially f or replacement dielectrics for Aroclor 1242.
My purpose In writing la primarily to document two pending changes at OK and Westlnghouse to adopt specialized use of Aroelor 1232 and 1221. Both are leas fire resistant than Aroelor 1242.
At this point It seema apropos to- Insert that Westlnghouse and other makers of Aroelor 1242 capacitors have been Invol ved with occasional user complaints that the capacitors were on fire. Weatlnghouae got "off the hook" by Indicating that Aroelor 1242 is not a fire extinguisher.
It Is also well for us to have In mind that the capacitor makers do not have the background experience nor the capabi lity that Monsanto has In the area of our fire testing labo ratory. By and large the capacitor makers think merely In terms of the flash point and fire point of the fluid and try to correlate this with what the Underwriters said many years ago about what an askarel should be.
Pursuant to our effort for better understanding of the sub ject question, I questioned Don McClain of Westlnghouse and Dr. Boudreau of 01 for their views about fire resistant re quirements relative to use of Aroelor 1221 and 1232 in the two new applications. Both Immediately sensed the reason for my probe - both smiled, as based on the following:
I. Westlnghouse: They may use about 250,000 lbs/yr of Aroelor 1232 for coupling capacitors. The criterion for selecting Aroelor 1232 la that It provides the flat capacitance response required at lower temperatures In this application. As the capacitors are located out-doors and as the Aroelor 1232 replaced mineral oil, fire resis tance was not a critical consideration. Of course. It la felt that Aroelor 1232 provides better fire resistance than mineral oil.
II. General Bloctrio: They Intend to use one or two hundred thousand pounds per year of Aroelor 1221
MONS 098426
-2-
as a slnpla ("out of our oatalogua") axpadlant to gat Aroolor 1254 eonplotoly out of thalr oapaoltor oparutlons, in oonfornanea with tha PCS pollution problun raqulransnta. fha Aro
olor 1254 waa blandad with 250 of TCB as tha
dlolootrle usad for aany yaara In DC eapaoltoro. On switching to Aroolor 1221 for this specialised application. dl fait that Aroolor 1221 would giro
at laast sons flro-ro#ltanoo. Now that wa know of thalr lntaraat in Aroolor 1221 It aaaaa likely that wo oan offor than a fluid that would ba functionally nora attraetiwa than Aroolor 1221.
Conolualona
I. Both OK and wastlnghouse dononatruted wllllng-
naaa to uaa dlalaotrlo fluids laaa flro realstant than Aroolor 1242 -- but only as expedients in snail apaolaity applloatlona.
IS. Nor tha larga "serosa tha board* Aroolor typo aapaoitor applloatlona thay atrlva to adhara to tha equivalent flro raalatanoa of Aroolor 1242. Both ara lnellnad to "band a little" as nay ba naadad. Tha problan that ronalna la that this oannot ba lntarpratad In flnlto tarns until tha
flra-raalatanoa of Aroolor 2242 la posted In noro
conclusive tarns than naraly flash and flra points, oo that oonparisons oan ba uada against othar
fluids on a nora raallstlo basis.
III.
However, all of this serves to undarwrlta tha cor-
raotnasa of our judgenents to naka and offar MCS 1016. relative to both flra-raslatant and aeologloal vlawa.
P. 01. Banlgnus
MONS 098427