American-Standard Kewanee Square-Heat Generator UNITS M-335, M-425, M-505 FOR NO. 2, 4 OR 5 OIL - GAS - COMBINATION GAS - OIL PLAINTIFF'S EXHIBIT ASI-1199 LOW PRESSURE STEAM OR WATER 3.350.000 TO 5.050.000 Btuh THE MOST COMPACT GENERATOR AVAILABLE American-Standard DETROIT 32, MICHIGAN 28535 SUPPLEMENT TO BULLETIN 1349D FEBRUARY 15, 1962 Kewanee Square-Heat Generator THREE LARGER SIZES - WIDER RANGE OF FUELS The Square-Heat Generator described in Bulletin 1349D is extended in range of sizes to 3,350,000, 4,250,000, and 5,050,000 btu output (nominal 100, 125 and 150 boiler horsepower). Also available for firing with No. 4 and No. 5 oil in addition to No. 2 oil and gas. Check the many quality features of the Square-Heat Generator in Bulletin 1349D, as well as the added features in this supplement. 2- - 28536 Kewanee Square-Heat Generator BURNER FEATURES Units 335 through 505 feature full modulation with proved low fire start. Fuel and air supply are reg ulated throughout the firing range by a modulating motor controlled by a boiler mounted pressure or temperature modulating potentiometer. Enforced low fire start is provided by an interlock on the mod ulating motor. Combination electronic flame safeguard and programmer assures safe operation with prepurge, postpurge, and proved ignition for both fuels. BURNER FIRING HEAD Exclusive design of burner firing head provides quiet, stable combustion of gas or oil at all inputs. The radial-jet gas burner provides smooth firing with excellent flame retention. The pilot flame on the exclusive ring-type gas-electric ignition as sembly surrounds the oil spray and contacts the tip of each gas jet for smooth lighting with max imum safety. AIR-OIL UNIT The air-oil unit assembly includes air compressor and oil pump, belt-driven by one motor, and all nec essary accessories to provide the fine oil atom ization required for clean, efficient oil firing. A thermostatically controlled electric oil heater maintains uniform oil temperature to compensate for varying viscosities of residual oils. The multilouvered opposed-blade air damper provides accu rately measured air supply to match fuel supply for top operating efficiency at all firing rates. CONTROL CABINET The heavy-gauge steel, dust proof control cabinet is completely prewired and ready for connection to a source of power. Control cabinet components in clude Fireye FP-2 flame safeguard system, and all necessary relays, switches and controls for full automatic operation. 3- - 28537 RATINGS AND DATA KEWANEE BURNER DATA Unit Number M-335 M-425 M-505 Unit Number t M-335 M-425 M-505 Rating --MBh........................................... --horsepower................................ --steam per hour 212F. . . lbs --steam (gross)............... sq ft --steam (MCA net) . . . . sq ft Firing rate--oil, 140,000 btu............ gph --oil. 150,000 btu............ gph -gas.................................. MBh Heating surface..................................... sq ft Furnace volume................. .................... cu ft Safety valve capacity--steam per hour, lbs Minimum stack diameter.................... Supply size.............................................. Return size.............................................. Gas control size.................................. Gas pressure required....................... in wc Approximate dry weight.................... 3350 100.0 3452 13958 10490 30.0 27.9 4181 450 72.0 3350 12 8** 4 2'/2 7 7300 4250 126.9 4380 17708 13110 38.0 34.8 5312 562 88.1 4250 15 a** 4 3 8 8200 5050 150.8 5204 21042 15733 45.0 41.7 6312 675 103.4 5050 18 8** 4 4 8 10300 ** 150 lb. American Standard Flange DIMENSIONS (inches) Unit Number M-335 M-425 A--Boiler maximum width.......................... --Jacket width................................................. --Insulation thickness.................................. B--Length overall*........................................ C --Boiler length.............................................. --Jacket length.............................................. D --Boiler height.............................................. --Jacket height from floor.......................... E --Waterline height........................................ F --Steam or Water supply height.............. G--Smoke outlet height.................................. H --Steam or Water supply location............ K--Coil connection height............................. L --Return height.............................................. M--Base length................................................. N --Vent opening.............................................. O --Smokebox*.................................................... P --Burner to boiler......................................... R--Required tube replacement length . . . 54 53 2 131 91 95 78 80 641/2 83 52 27 66 >/2 7 121'/2 16 12 28 93 54 53 2 152 112 116 78 80 64V, 83 52 38 66Vj 7 142 V2 16 12 28 114 * Add 5 V2 inches for top smoke outlet M-505 54 53 2 172 132 136 78 80 64'/2 83 52 48 66V2 7 162 Vj 18 12 28 134 Input -Gas..................................... MBh 4181 5312 6312 -No. 2 oil, 140,000 btu. . gph 30.0 38.0 45.0 -No. 5 oil, 150,000 btu. . gph 27.9 34.8 41.7 Fuel Control-Gas.......................... Modulating Modulating Modulating -Oil............................. Modulating Modulating Modulating Air Control..................................... Modulating Modulating Modulating Flame Safeguard and Programming System.............. Fireye Fireye Fireye FP-2 FP-2 FP-2 Gas Controls (UL, 1000 btu/cf, 0.6 sp. gr.) -Required inlet pressure. . . . in wc 7 8 8 -Control group size....................... in 2VJ 3 4 Motors -- Electrical Characteristics.......................... -Forced draft fan hp 1 l'/2 2 208/220/ 208/220/ 208/220/ 240-60-3 H - 240-60-3 240-60-3 -Air atomizing air-oil unit . . . .hp 1 1 i 208/220/ 208/220/ 208/220/ 240-60-3 240-60-3 240-60-3 -Pressure atom izing oil pump . . hp V3 V3 S 230-60-1 230-60-1 230-60-1 Controls -- Electrical Characteristics.......................... 115-60-1 115-60-1 115-60-1 Oil Heater -- for No. 4 or No. 5 oil............................. watts 3000 3000 4000 tUnit suffix denotes fuel and type of fuel burning equipment: -- FG for gas -- FO for No. 2 oil (pressure atomizing) -- F02 for No. 2 oil (air atomizing) -- F05 for No. 4 or No. 5 oil (air atomizing with electric heater) -- FGO for gas - No. 2 oil (pressure atomizing) -- FG02 for gas - No. 2 oil (air atomizing) -- FG05 for gas - No. 4 or No. 5 oil (air atomizing with electric heater) 4- - 28538 Kewanee Square-Heat Generator STANDARD AND OPTIONAL EQUIPMENT UNITS M-335, M-425, M-505 STANDARD EQUIPMENT OPTIONAL EQUIPMENT ALL UNITS 1. Three-Pass ASME Code Boiler 2. Refractory Filled Extended Skid Type Base 3. Gas Tight Insulated Front Smokebox 4. Pyrex Observation Ports (Front & Rear) 5. 2" Firetubes 6. Gas Tight Rear Smokebox with Horizontal Discharge (Rear) Vent 87.. Wrap-around Insulated Steel Jacket Lifting Loops 9. Washout Plug Socket Wrench & Flue Cleaner with Handle 10. Operating Limit Control 11. Safety High Limit Control 12. Modulation Operating Control 13. Forced Draft Burner 14. Control Cabinet Mounted on Boiler Base Including: Fireye FP-2 Flame Safeguard and Programming Control, Magnetic Starter(s) Control Circuit Transformer, Control Circuit Fuse, Burner "On- Off" Switch, Indicating Lights (2), Necessary Relays, Numbered Terminal Strip, Engraved Nameplates 15. Air Flow Safety Switch 16. Blower Motor Horsepower & Voltages -- 1 HP; 208/220/240 V, 60 cy, 3 ph. (Unit 335) l'/j'HP, 208/220/240 V, 60 cy. 3 ph. (Unit 425) 2 HP, 208/220/240 V, 60 cy, 3 ph. (Unit 505) 17. Control Voltage -- 115 V, 60 cy, 1 ph. Includes Reduced Voltage Transformer 18. Modulated Firing Sequence with Low Fire Start 19. Modulating Motor with Low Fire Interlock 20. Gas-Electric Ignition Assembly Including: Ring Type Pilot Burner, 6000 V Transformer,Gas Valve,Gas Pressure Regulator,Gas Cock 21. Lead Sulphide Flame Detector 22. Listed Standard and Selected Optional Equipment Mounted, Piped, Wired, Ready for Field Connection to Fuel, Water, Steam and Elec tricity. (Exceptions: Items shipped separately to prevent shipping damage). 23. Factory Firetest 24. Starting Service 1. Explosion Relief Door 2. Vertical Discharge (Top) Vent 3. Instantaneous or Tank Type Hot Water Coils 4. Flue Gas Temperature Gauge 5. Room Thermostat Control 6. DC Voltmeter 7. Alarm Bell 8. Circuit Breaker(s) 9. Manual Potentiometer with Manual-Automatic Switch 10. Other Than Standard Voltages 11. One Year Service Period 1. No. 767 Low Water Cut-Off 2. Kewanee Water Column 3. Safety Valve(s) 4. Compound Steam and Vacuum Gauge 5. Water Gauge, Glass and Try Cocks STEAM UNITS 1. No. 157 Combination Water Column, Low Water Cut-Off and Pump Control 2. No. 51-2 Combination Water Feeder, Low Water Cut-Off and Alarm Switch (Not Mounted) 3. Second Low Water Cut-Off Surface Blow-Off HOT WATER UNITS 1. No. 764 Low Water Cut-Off 2. Relief Valve(s) 3. Combination Altitude Gauge &Thermometer 1. No. 51-2 Combination Water FeedeivLow Water Cut-Off and Alarm Switch (Not Mounted) 2. Second Low Water Cut-Off PRESSURE ATOMIZING OIL UNITS 12.. Forced Draft Pressure Atomizing Oil Burner for No. 2 Oil Two-Stage Oil Pump Assembly with Gauge, Relief Valve, '/j HP Motor 3. Variable Capacity Oil Nozzle 4. Oil Solenoid Valve 5. Modulating Oil Metering Valve 6. Oil Filter (Not Mounted) 1. Direct Spark Electric Ignition 2. Oil Controls for FM 3. Oil Controls for FLA *4. Oil Controls for Local Code Requirements AIR ATOMIZING OIL UNITS 1. Forced Draft Air Atomizing Oil Burner for No. 5 or Lighter Oil 2. Air-Oil Unit Including: Air Compressor, Motor, Air Pressure Regulator, Air Metering Valve, Inlet Air Filter, Check Valve, Air Pressure Safety Switch, Air Gauge, Oil Pump Assembly with Gauge 1. Oil Controls for FM 2. Oil Controls for F1A *3. Oil Controls for Local Code Requirements 4. Omit Electric Heater For No. 2 Oil 3. Air-Oil Unit Motor Horsepower and Voltage -- 1 HP, 208/220/240 V, 60 cy, 3 ph. 4. Thermostatically Controlled Electric Oil Heater 3000 Watts (Unit 335 and 425) 4000 Watts (Unit 505) 5. Air-Oil Atomizing Nozzle 6. Oil Solenoid Valve 7. Modulating Oil Metering Valve Air Purge Relay and Valve 9. Oil Strainer (Not Mounted) GAS UNITS 1. Forced Draft Radial-Jet Flame Retention Type Gas Burner 2. UL Gas Control Group Including' Automatic Motorized Gas Valve, Automatic Solenoid Safety Gas Valve, Gas Pressure Regulator, Modulating Gas Volume Control Valve, Gas Pressure Gauge, Gas Cock 1. Gas Controls for Other than Standard Pressures 2. Gas Controls for FM 3. Gas Controls for FIA 4. Gas Controls for Local Utility Requirements. 1. Manual Fuel Changeover Switch COMBINATION GAS-OIL UNITS + 1. Automatic Fuel Changeover Switch * On Special Application Only. 5- - 28539 Kewanee Square-Heat Generator TYPICAL SQUARE-HEAT GENERATOR SPECIFICATIONS FOR UNITS M-335, M-425, M-505 The contractor shall furnish and install . . . Model No................. SquareHeat Generator(s) for (No. (2)(4)(5) oil), (gas), or (combination gas--No. (2)(4)(5) oil) firing. The unit(s) shall be of 3-pass firebox design with arched upright crown sheet and two passes of firetubes, and constructed in accordance with the ASME Code for (15 lbs. steam) (30 lbs water). The unit(s) shall contain not less than . . . cubic feet of furnace volume and shall have a gross output rating of not less than .... MBh. Heat release shall not exceed 61,000 Btu per cubic foot of furnace volume. Normal water line of unit(s) shall not exceed .... inches. A pyrex observation port shall be provided at the rear of the firebox. Front flue access cover, with refractory securely keyed in place and of a size permitting easy access to all fire tubes, shall be mounted on a gastight, insulated front smokebox. Gas-tight rear smokebox shall be pro vided with a (rear) (top) outlet. Unit(s) shall be provided with a wrap-around steel jacket with 2" min eral fiber insulation and smooth enamel finish. All tubes shall be set with a roller expander at each end. No welding of tubes to the tube sheets nor use of refractory baffling to provide the second or third pass will be permitted. Unit(s) shall be assembled and wired, with burner, controls, trim, in sulated steel jacket and refractory filled skid type base installed at the factory. Fuel burning equipment shall be forced draft type; Factory assembled, wired, mounted, and tested. The entire unit shall bear the Underwriters' Laboratories label and shall be ready for field connection to power and fuel supply. Equipment shall include forced draft fan with air damper; dual high limit controls; modulating operating control; flame sensing device; and control cabinet containing Fireye FP-2 electronic flame safeguard and programmer, burner on-off switch, necessary switching relays, two indicating lights for major operations, numbered terminal strips, color-coded wiring and engraved nameplates. All motors shall be for .... volts, .... cycle, .... phase operation. Controls shall be 115 volt, 60 cycle, single phase. Magnetic motor starters with thermal over-load protection and a step-down control cir cuit transformer shall be provided in the control cabinet when other than 115 volt motors are specified. Fuel burning equipment shall be set and adjusted by a factory-author ized representative to bum .... G.P.H. of No. (2)(4)(5) oil (and)(or) ............C.F.H. of..............Btu cu. ft. (natural)(manufactured) (L.P.) gas having a . . . . sp. gr. with .... inches W.C. pressure at inlet of burner manual gas cock. Unit efficiency, based on flue gas analysis, shall be not less than 80%. Note: Specify job altitude if over 2,500 ft. above sea level. FOR PRESSURE ATOMIZING OIL UNITS Oil burner shall be of the pressure atomizing type for No. 2 oil with a two-stage oil pump assembly with internal relief valve mounted on the boiler skid. Burner shall include variable-flow oil atomizing nozzle; oil solenoid valve; oil metering valve; gas-electric ignition assembly with ring-type pilot burner, 6000 volt ignition transformer, automatic gas valve, gas pressure regulator and gas cock; air flow safety switch; lead sulphide flame detector; low fire interlock; and all necessary con trols and linkage for modulated firing with proved low fire start. Fuelair control shall provide modulated regulation of the air damper and the oil metering valve by means of a motor operator. FOR AIR ATOMIZING OIL UNITS Oil burner shall be of the air atomizing type for No. 5 or lighter oil with an air-oil unit consisting of air compressor, motor, air pressure regulator, air metering valve, inlet air filter, check valve, air pressure safety switch, air gauge, oil pump assembly and relief valve mounted on the boiler skid. Burner shall include air-oil atomizing nozzle; oil sole noid valve; oil metering valve; air purge relay and valve; thermosta tically controlled electric oil heater (omit for No. 2 oil)t gas-electric ignition assembly consisting of a ring-type pilot burner, 6000 volt igni tion transformer, automatic gas valve, gas pressure regulator and gas cock; air flow safety switch; lead sulphide flame detector; low fire in terlock; and all necessary controls and linkages for modulated firing with proved low fire start. Fuel-air control shall provide modulated regulation of the air damper and the oil metering valve by means of a motor operator. FOR COMBINATION GAS-PRESSURE ATOMIZING OIL UNITS Gas-oil burner shall consist of a combination radial-jet flame retention type gas burner and pressure atomizing oil burner for No. 2 oil in cluding all necessary controls for modulated type of operation with proved low fire start. Gas controls shall include a main gas control group consisting of an automatic motorized gas valve, an automatic so lenoid safety gas valve, gas volume control valve, gas pressure regula tor, gas gauge, and gas cock. Oil controls shall include a two-stage oil pump assembly with internal relief valve; variable-flow oil atomizing nozzle; oil solenoid valve; oil metering valve. Controls for both fuels shall include a lead sulphide flame detector; air flow safety switch; low fire interlock; and gas-electric ignition assembly consisting of a ringtype pilot burner, 6000 volt ignition transformer, automatic gas valve, gas pressure regulator and gas cock. Fuel-Hir control shall provide modulated regulation of the air damper, the gas volume control valve, and the oil metering valve by means of a motor operator. Changeover from one fuel to the other shall be accomplished by means of a manual fuel selector swatch in the control cabinet. No changes in linkage, burner position, or mechanical adjustment shall be necessary when changing fuels. The fuel selector switch shall provide, through the com bustion control relay, proper ignition timing for the fuel being burned. Owner's representative shall be present to receive instructions in care and maintenance of the unit at the time it is started up by the service representative. Contractor shall provide a free service period of 90 days after startup. NOTE: Select applicable paragraphs below according to fuel and unit size. The following equipment conforms to UL requirements. Specify additional controls if FM or FIA insured, or subject to special local utility requirements. FOR GAS UNITS Gas burner shall be of the radial-jet flame retention type including a main gas control group consisting of an automatic motorized gas valve, automatic solenoid safety gas valve, gas volume control valve, gas pressure regulator, gas gauge, and gas cock; gas-electric ignition as sembly consisting of a ring-type pilot burner. 6000 volt ignition trans former, automatic gas valve, gas pressure regulator, and gas cock; air flow safety switch; lead sulphide flame detector; low fire interlock; and all necessary controls and linkage for full modulation type of operation with proved low fire start. Fuel-air control shall provide full modula ting regulation of the air damper and the gas volume control valve by means of a motor operator. FOR COMBINATION GAS-AIR ATOMIZING OIL UNITS Gas-oil burner shall consist of a combination radial-jet flame retention type gas burner and air atomizing oil burner for No. 5 or lighter oil with all necessary controls for modulated type of operation with proved low fire start. Gas controls shall include a main gas control group con sisting of an automatic motorized gas valve, automatic solenoid safety gas valve, gas volume control valve, gas pressure regulator, gas gauge and gas cock. Oil controls shall include an air-oil unit consisting of an air compressor, motor, air pressure regulator, air metering valve, in let air filter, check valve, air pressure safety switch, air gauge, oil pump assembly and relief valve; air-oil atomizing nozzle; oil solenoid valve; oil metering valve; air purge relay and valve; thermostatically controlled electric oil heater (omit for No. 2 oil). Controls for both fuels shall include lead sulphide flame detector; air flow safety switch; low fire interlock; and gas-electric ignition assembly consisting of a ring-type pilot burner, 6000 volt ignition transformer, automatic gas valve, gas pressure regulator and gas cock. Fuel-air control shall pro vide modulated regulation of the air damper, the gas volume control valve, and the oil metering valve by means of a motor operator. Changeover from one fuel to the other shall be accomplished by means of a manual fuel selector switch in the control cabinet. No changes in linkage, burner position, or mechanical adjustment shall be necessary when changing fuels. The fuel selector switch shall provide, through the combustion control relay, proper ignition timing for the fuel being burned. 6- - 28540