Document xzmj0RY7GqKYGX44Jpr36MKVJ
American-Standard
Kewanee Square-Heat Generator
UNITS M-335, M-425, M-505
FOR NO. 2, 4 OR 5 OIL - GAS - COMBINATION GAS - OIL
PLAINTIFF'S EXHIBIT ASI-1199
LOW PRESSURE STEAM OR WATER
3.350.000 TO 5.050.000 Btuh
THE MOST COMPACT GENERATOR AVAILABLE
American-Standard
DETROIT 32, MICHIGAN
28535
SUPPLEMENT TO BULLETIN 1349D FEBRUARY 15, 1962
Kewanee Square-Heat Generator
THREE LARGER SIZES - WIDER RANGE OF FUELS
The Square-Heat Generator described in Bulletin 1349D is extended in range of sizes to 3,350,000, 4,250,000, and 5,050,000 btu output (nominal 100, 125 and 150 boiler horsepower). Also available for firing with No. 4 and No. 5 oil in addition to No. 2 oil and gas.
Check the many quality features of the Square-Heat Generator in Bulletin 1349D, as well as the added
features in this supplement.
2- -
28536
Kewanee Square-Heat Generator
BURNER FEATURES
Units 335 through 505 feature full modulation with proved low fire start. Fuel and air supply are reg ulated throughout the firing range by a modulating motor controlled by a boiler mounted pressure or temperature modulating potentiometer. Enforced low fire start is provided by an interlock on the mod ulating motor. Combination electronic flame safeguard and programmer assures safe operation with prepurge, postpurge, and proved ignition for both fuels.
BURNER FIRING HEAD
Exclusive design of burner firing head provides quiet, stable combustion of gas or oil at all inputs. The radial-jet gas burner provides smooth firing with excellent flame retention. The pilot flame on the exclusive ring-type gas-electric ignition as sembly surrounds the oil spray and contacts the tip of each gas jet for smooth lighting with max imum safety.
AIR-OIL UNIT
The air-oil unit assembly includes air compressor and oil pump, belt-driven by one motor, and all nec essary accessories to provide the fine oil atom ization required for clean, efficient oil firing. A thermostatically controlled electric oil heater maintains uniform oil temperature to compensate for varying viscosities of residual oils. The multilouvered opposed-blade air damper provides accu rately measured air supply to match fuel supply for top operating efficiency at all firing rates.
CONTROL CABINET
The heavy-gauge steel, dust proof control cabinet is completely prewired and ready for connection to a source of power. Control cabinet components in clude Fireye FP-2 flame safeguard system, and all necessary relays, switches and controls for full automatic operation.
3- -
28537
RATINGS AND DATA
KEWANEE BURNER DATA
Unit Number
M-335 M-425 M-505
Unit Number t
M-335
M-425
M-505
Rating
--MBh...........................................
--horsepower................................
--steam per hour 212F. . . lbs
--steam (gross)............... sq ft
--steam (MCA net) . . . . sq ft Firing rate--oil, 140,000 btu............ gph
--oil. 150,000 btu............ gph -gas.................................. MBh
Heating surface..................................... sq ft
Furnace volume................. .................... cu ft
Safety valve capacity--steam per hour, lbs
Minimum stack diameter....................
Supply size..............................................
Return size..............................................
Gas control size..................................
Gas pressure required....................... in wc
Approximate dry weight....................
3350 100.0
3452 13958 10490
30.0 27.9 4181 450 72.0 3350 12
8** 4 2'/2 7 7300
4250 126.9
4380 17708 13110
38.0 34.8 5312 562 88.1 4250 15
a**
4 3 8 8200
5050 150.8
5204 21042 15733
45.0 41.7 6312 675 103.4 5050 18
8** 4 4 8 10300
** 150 lb. American Standard Flange
DIMENSIONS (inches)
Unit Number
M-335 M-425
A--Boiler maximum width.......................... --Jacket width................................................. --Insulation thickness..................................
B--Length overall*........................................ C --Boiler length..............................................
--Jacket length.............................................. D --Boiler height..............................................
--Jacket height from floor.......................... E --Waterline height........................................ F --Steam or Water supply height.............. G--Smoke outlet height.................................. H --Steam or Water supply location............ K--Coil connection height............................. L --Return height.............................................. M--Base length................................................. N --Vent opening.............................................. O --Smokebox*.................................................... P --Burner to boiler......................................... R--Required tube replacement length . . .
54 53
2 131
91 95 78 80 641/2 83 52 27 66 >/2
7 121'/2
16 12 28 93
54 53
2
152 112 116
78 80 64V, 83 52 38 66Vj
7 142 V2
16 12 28 114
* Add 5 V2 inches for top smoke outlet
M-505
54 53
2 172 132 136
78 80 64'/2 83 52 48 66V2
7 162 Vj
18 12 28 134
Input -Gas..................................... MBh
4181
5312
6312
-No. 2 oil, 140,000 btu. . gph
30.0
38.0
45.0
-No. 5 oil, 150,000 btu. . gph
27.9
34.8
41.7
Fuel Control-Gas.......................... Modulating Modulating Modulating
-Oil............................. Modulating Modulating Modulating
Air Control..................................... Modulating Modulating Modulating
Flame Safeguard and
Programming System..............
Fireye
Fireye
Fireye
FP-2
FP-2
FP-2
Gas Controls
(UL, 1000 btu/cf, 0.6 sp. gr.)
-Required inlet
pressure. . . . in wc
7
8
8
-Control group
size....................... in
2VJ
3
4
Motors -- Electrical
Characteristics.......................... -Forced draft fan hp
1
l'/2 2
208/220/ 208/220/ 208/220/
240-60-3 H - 240-60-3 240-60-3
-Air atomizing
air-oil unit . . . .hp
1
1
i
208/220/ 208/220/ 208/220/
240-60-3 240-60-3 240-60-3
-Pressure atom
izing oil pump . . hp
V3
V3
S
230-60-1 230-60-1 230-60-1
Controls -- Electrical
Characteristics.......................... 115-60-1 115-60-1 115-60-1
Oil Heater -- for No. 4 or
No. 5 oil............................. watts
3000
3000
4000
tUnit suffix denotes fuel and type of fuel burning equipment: -- FG for gas -- FO for No. 2 oil (pressure atomizing) -- F02 for No. 2 oil (air atomizing) -- F05 for No. 4 or No. 5 oil (air atomizing with electric heater) -- FGO for gas - No. 2 oil (pressure atomizing) -- FG02 for gas - No. 2 oil (air atomizing) -- FG05 for gas - No. 4 or No. 5 oil (air atomizing with electric heater)
4- -
28538
Kewanee Square-Heat Generator
STANDARD AND OPTIONAL EQUIPMENT
UNITS M-335, M-425, M-505
STANDARD EQUIPMENT
OPTIONAL EQUIPMENT
ALL UNITS
1. Three-Pass ASME Code Boiler
2. Refractory Filled Extended Skid Type Base
3. Gas Tight Insulated Front Smokebox
4. Pyrex Observation Ports (Front & Rear)
5. 2" Firetubes
6. Gas Tight Rear Smokebox with Horizontal Discharge (Rear) Vent
87..
Wrap-around Insulated Steel Jacket Lifting Loops
9. Washout Plug Socket Wrench & Flue Cleaner with Handle
10. Operating Limit Control
11. Safety High Limit Control
12. Modulation Operating Control
13. Forced Draft Burner
14. Control Cabinet Mounted on Boiler Base Including: Fireye FP-2
Flame Safeguard and Programming Control, Magnetic Starter(s)
Control Circuit Transformer, Control Circuit Fuse, Burner "On-
Off" Switch, Indicating Lights (2), Necessary Relays, Numbered
Terminal Strip, Engraved Nameplates
15. Air Flow Safety Switch
16. Blower Motor Horsepower & Voltages --
1 HP; 208/220/240 V, 60 cy, 3 ph. (Unit 335)
l'/j'HP, 208/220/240 V, 60 cy. 3 ph. (Unit 425)
2 HP, 208/220/240 V, 60 cy, 3 ph. (Unit 505)
17. Control Voltage --
115 V, 60 cy, 1 ph. Includes Reduced Voltage Transformer
18. Modulated Firing Sequence with Low Fire Start
19. Modulating Motor with Low Fire Interlock
20. Gas-Electric Ignition Assembly Including: Ring Type Pilot Burner,
6000 V Transformer,Gas Valve,Gas Pressure Regulator,Gas Cock 21. Lead Sulphide Flame Detector
22. Listed Standard and Selected Optional Equipment Mounted, Piped,
Wired, Ready for Field Connection to Fuel, Water, Steam and Elec
tricity. (Exceptions: Items shipped separately to prevent shipping
damage).
23. Factory Firetest
24. Starting Service
1. Explosion Relief Door 2. Vertical Discharge (Top) Vent 3. Instantaneous or Tank Type Hot Water Coils 4. Flue Gas Temperature Gauge 5. Room Thermostat Control 6. DC Voltmeter
7. Alarm Bell 8. Circuit Breaker(s) 9. Manual Potentiometer with Manual-Automatic Switch 10. Other Than Standard Voltages 11. One Year Service Period
1. No. 767 Low Water Cut-Off 2. Kewanee Water Column 3. Safety Valve(s) 4. Compound Steam and Vacuum Gauge 5. Water Gauge, Glass and Try Cocks
STEAM UNITS
1. No. 157 Combination Water Column, Low Water Cut-Off and Pump Control
2. No. 51-2 Combination Water Feeder, Low Water Cut-Off and Alarm Switch (Not Mounted)
3. Second Low Water Cut-Off Surface Blow-Off
HOT WATER UNITS
1. No. 764 Low Water Cut-Off 2. Relief Valve(s) 3. Combination Altitude Gauge &Thermometer
1. No. 51-2 Combination Water FeedeivLow Water Cut-Off and Alarm Switch (Not Mounted)
2. Second Low Water Cut-Off
PRESSURE ATOMIZING OIL UNITS
12..
Forced Draft Pressure Atomizing Oil Burner for No. 2 Oil Two-Stage Oil Pump Assembly with Gauge, Relief Valve, '/j
HP
Motor
3. Variable Capacity Oil Nozzle
4. Oil Solenoid Valve
5. Modulating Oil Metering Valve
6. Oil Filter (Not Mounted)
1. Direct Spark Electric Ignition 2. Oil Controls for FM 3. Oil Controls for FLA *4. Oil Controls for Local Code Requirements
AIR ATOMIZING OIL UNITS
1. Forced Draft Air Atomizing Oil Burner for No. 5 or Lighter Oil 2. Air-Oil Unit Including: Air Compressor, Motor, Air Pressure
Regulator, Air Metering Valve, Inlet Air Filter, Check Valve, Air Pressure Safety Switch, Air Gauge, Oil Pump Assembly with Gauge
1. Oil Controls for FM 2. Oil Controls for F1A *3. Oil Controls for Local Code Requirements 4. Omit Electric Heater For No. 2 Oil
3. Air-Oil Unit Motor Horsepower and Voltage -- 1 HP, 208/220/240 V, 60 cy, 3 ph.
4. Thermostatically Controlled Electric Oil Heater 3000 Watts (Unit 335 and 425) 4000 Watts (Unit 505)
5. Air-Oil Atomizing Nozzle 6. Oil Solenoid Valve 7. Modulating Oil Metering Valve
Air Purge Relay and Valve 9. Oil Strainer (Not Mounted)
GAS UNITS
1. Forced Draft Radial-Jet Flame Retention Type Gas Burner 2. UL Gas Control Group Including' Automatic Motorized Gas Valve,
Automatic Solenoid Safety Gas Valve, Gas Pressure Regulator,
Modulating Gas Volume Control Valve, Gas Pressure Gauge, Gas Cock
1. Gas Controls for Other than Standard Pressures 2. Gas Controls for FM 3. Gas Controls for FIA 4. Gas Controls for Local Utility Requirements.
1. Manual Fuel Changeover Switch
COMBINATION GAS-OIL UNITS
+ 1. Automatic Fuel Changeover Switch
* On Special Application Only.
5- -
28539
Kewanee Square-Heat Generator
TYPICAL SQUARE-HEAT GENERATOR SPECIFICATIONS
FOR UNITS M-335, M-425, M-505
The contractor shall furnish and install . . . Model No................. SquareHeat Generator(s) for (No. (2)(4)(5) oil), (gas), or (combination gas--No. (2)(4)(5) oil) firing. The unit(s) shall be of 3-pass firebox design with arched upright crown sheet and two passes of firetubes, and constructed in accordance with the ASME Code for (15 lbs. steam) (30 lbs water).
The unit(s) shall contain not less than . . . cubic feet of furnace volume and shall have a gross output rating of not less than .... MBh. Heat release shall not exceed 61,000 Btu per cubic foot of furnace volume.
Normal water line of unit(s) shall not exceed .... inches. A pyrex observation port shall be provided at the rear of the firebox. Front flue access cover, with refractory securely keyed in place and of a size permitting easy access to all fire tubes, shall be mounted on a gastight, insulated front smokebox. Gas-tight rear smokebox shall be pro vided with a (rear) (top) outlet.
Unit(s) shall be provided with a wrap-around steel jacket with 2" min eral fiber insulation and smooth enamel finish.
All tubes shall be set with a roller expander at each end. No welding of tubes to the tube sheets nor use of refractory baffling to provide the second or third pass will be permitted.
Unit(s) shall be assembled and wired, with burner, controls, trim, in sulated steel jacket and refractory filled skid type base installed at the factory.
Fuel burning equipment shall be forced draft type; Factory assembled, wired, mounted, and tested. The entire unit shall bear the Underwriters' Laboratories label and shall be ready for field connection to power and fuel supply. Equipment shall include forced draft fan with air damper; dual high limit controls; modulating operating control; flame sensing device; and control cabinet containing Fireye FP-2 electronic flame safeguard and programmer, burner on-off switch, necessary switching relays, two indicating lights for major operations, numbered terminal strips, color-coded wiring and engraved nameplates.
All motors shall be for .... volts, .... cycle, .... phase operation. Controls shall be 115 volt, 60 cycle, single phase. Magnetic motor starters with thermal over-load protection and a step-down control cir cuit transformer shall be provided in the control cabinet when other than 115 volt motors are specified.
Fuel burning equipment shall be set and adjusted by a factory-author ized representative to bum .... G.P.H. of No. (2)(4)(5) oil (and)(or) ............C.F.H. of..............Btu cu. ft. (natural)(manufactured) (L.P.) gas having a . . . . sp. gr. with .... inches W.C. pressure at inlet of burner manual gas cock. Unit efficiency, based on flue gas analysis, shall be not less than 80%. Note: Specify job altitude if over 2,500 ft. above sea level.
FOR PRESSURE ATOMIZING OIL UNITS
Oil burner shall be of the pressure atomizing type for No. 2 oil with a two-stage oil pump assembly with internal relief valve mounted on the boiler skid. Burner shall include variable-flow oil atomizing nozzle; oil solenoid valve; oil metering valve; gas-electric ignition assembly with ring-type pilot burner, 6000 volt ignition transformer, automatic gas valve, gas pressure regulator and gas cock; air flow safety switch; lead sulphide flame detector; low fire interlock; and all necessary con trols and linkage for modulated firing with proved low fire start. Fuelair control shall provide modulated regulation of the air damper and the oil metering valve by means of a motor operator.
FOR AIR ATOMIZING OIL UNITS
Oil burner shall be of the air atomizing type for No. 5 or lighter oil with an air-oil unit consisting of air compressor, motor, air pressure regulator, air metering valve, inlet air filter, check valve, air pressure safety switch, air gauge, oil pump assembly and relief valve mounted on the boiler skid. Burner shall include air-oil atomizing nozzle; oil sole noid valve; oil metering valve; air purge relay and valve; thermosta tically controlled electric oil heater (omit for No. 2 oil)t gas-electric ignition assembly consisting of a ring-type pilot burner, 6000 volt igni tion transformer, automatic gas valve, gas pressure regulator and gas cock; air flow safety switch; lead sulphide flame detector; low fire in terlock; and all necessary controls and linkages for modulated firing with proved low fire start. Fuel-air control shall provide modulated regulation of the air damper and the oil metering valve by means of a motor operator.
FOR COMBINATION GAS-PRESSURE ATOMIZING OIL UNITS
Gas-oil burner shall consist of a combination radial-jet flame retention type gas burner and pressure atomizing oil burner for No. 2 oil in cluding all necessary controls for modulated type of operation with proved low fire start. Gas controls shall include a main gas control group consisting of an automatic motorized gas valve, an automatic so lenoid safety gas valve, gas volume control valve, gas pressure regula tor, gas gauge, and gas cock. Oil controls shall include a two-stage oil pump assembly with internal relief valve; variable-flow oil atomizing nozzle; oil solenoid valve; oil metering valve. Controls for both fuels shall include a lead sulphide flame detector; air flow safety switch; low fire interlock; and gas-electric ignition assembly consisting of a ringtype pilot burner, 6000 volt ignition transformer, automatic gas valve, gas pressure regulator and gas cock. Fuel-Hir control shall provide modulated regulation of the air damper, the gas volume control valve, and the oil metering valve by means of a motor operator. Changeover from one fuel to the other shall be accomplished by means of a manual fuel selector swatch in the control cabinet. No changes in linkage, burner position, or mechanical adjustment shall be necessary when changing fuels. The fuel selector switch shall provide, through the com bustion control relay, proper ignition timing for the fuel being burned.
Owner's representative shall be present to receive instructions in care and maintenance of the unit at the time it is started up by the service representative. Contractor shall provide a free service period of 90 days after startup.
NOTE: Select applicable paragraphs below according to fuel and unit size. The following equipment conforms to UL requirements. Specify additional controls if FM or FIA insured, or subject to special local utility requirements.
FOR GAS UNITS
Gas burner shall be of the radial-jet flame retention type including a main gas control group consisting of an automatic motorized gas valve, automatic solenoid safety gas valve, gas volume control valve, gas pressure regulator, gas gauge, and gas cock; gas-electric ignition as sembly consisting of a ring-type pilot burner. 6000 volt ignition trans former, automatic gas valve, gas pressure regulator, and gas cock; air flow safety switch; lead sulphide flame detector; low fire interlock; and all necessary controls and linkage for full modulation type of operation with proved low fire start. Fuel-air control shall provide full modula ting regulation of the air damper and the gas volume control valve by means of a motor operator.
FOR COMBINATION GAS-AIR ATOMIZING OIL UNITS
Gas-oil burner shall consist of a combination radial-jet flame retention type gas burner and air atomizing oil burner for No. 5 or lighter oil with all necessary controls for modulated type of operation with proved low fire start. Gas controls shall include a main gas control group con sisting of an automatic motorized gas valve, automatic solenoid safety gas valve, gas volume control valve, gas pressure regulator, gas gauge and gas cock. Oil controls shall include an air-oil unit consisting of an air compressor, motor, air pressure regulator, air metering valve, in let air filter, check valve, air pressure safety switch, air gauge, oil pump assembly and relief valve; air-oil atomizing nozzle; oil solenoid valve; oil metering valve; air purge relay and valve; thermostatically controlled electric oil heater (omit for No. 2 oil). Controls for both fuels shall include lead sulphide flame detector; air flow safety switch; low fire interlock; and gas-electric ignition assembly consisting of a ring-type pilot burner, 6000 volt ignition transformer, automatic gas valve, gas pressure regulator and gas cock. Fuel-air control shall pro vide modulated regulation of the air damper, the gas volume control valve, and the oil metering valve by means of a motor operator. Changeover from one fuel to the other shall be accomplished by means of a manual fuel selector switch in the control cabinet. No changes in linkage, burner position, or mechanical adjustment shall be necessary when changing fuels. The fuel selector switch shall provide, through the combustion control relay, proper ignition timing for the fuel being burned.
6- -
28540