CHAPTER 23
1957 Guide' 'Wff
Panel Heating
607
The combined heat transfer for ceiling panels and floor panels in rooms
in which the air temperature is 70 to 76 F can be read directly from Figs. : 15 and 16, respectively. These two diagrams apply to rooms in which the AUST does not differ greatly from room air temperatures. Tests6 7 showed that the two temperatures are normally nearly equal.
Panel Heat Losses
Heat transferred from the upper surface of ceiling panels, the back sur face of wall panels, the underside of floor panels, or the edges of any panel
SURFACE OR MEAN WATER TEMPERATURE - F
Fig. 15. Ceiling Panel Design Graph Showing Panel Subpace Temperature and Mean Water Temperature vs. Output Downward
calculating AUST, the surface temperature of inside walls is assumed to be the same as the inside air temperature. The surface temperatures of out side walls And exposed floors or ceilings can be obtained from Figs. 13 for a 70 F room air temperature. Corrections for other temperatures may be obtained from Fig. 14.
SURFACE OR MEAN WATER TEMPERATURE-F
Fig. 16. Floor Panel Design Graph Showing Panel Surface Temperature and Mean Water Temperature vs. Output Upward
BTU PER IHR) BO FT) IF DEO)
Fig. 17. Downward and Edgewise Heat Loss Coefpicent for Concrete Floor Slabs on Grade
is considered a panel heat loss. Panel heat losses are part' of the building heat loss if the heat is transferred outside of the building. If the heat is transferred to another heated space, the panel loss is a source of heat for the space and is not a part of the building heat loss. In either case, the magnitude of the panel loss should be determined.
Panel heat loss to the outside should be kept to a reasonable amount by insulation. Panel heat loss to heated spaces may require reduction, by msulation if the amount of heat transferred is excessive or if objectionable temperatures will be developed. For example, a floor panel may overheat the basement below and a ceiling panel may cause the temperature of a floor surface above it to be too high for comfort.
The heat loss from most panels can be calculated by using the coefficients gjven in Chapter 9 Heat Transmission Coefficients of Building Materials, these coefficients should not be used to determine the downward heat mss from panels built on grade because the heat flow from them is not uniform.10-11 -12 The heat loss from panels built on grade can be esti mated from Fig. 17.