Document xzQ2KQgNy0zNMK9Mok24GjRvy
VCM GAS MONITORING SYSTEM VCM TANK FARM AREA
ABERDEEN CHEMICAL PLANT MARCH 8, 1985
A
Work By
Lcrvtvo-
Frank G. Jeanson Process Engineer
1
Reviewed By:
L',vWUk
r
Vernon L. Thornhill
Senior Process Engineer
Approved By:
R. A. Frohreich Chief Process Engineer
\
VAB.0001106271
VCM GAS MONITORING SYSTEM
VCM TANK FARM AREA ABERDEEN CHEMICAL PLANT
Table of Contents I. Purpose of Design II. Process Description III. Equipment and Instrument Specifications IV. Process Piping Schedule V. Work List VI. P&I Diagram
mf
VAB.0001106272
i
4
-r
VCM GAS MONITORING SYSTEM
RAILCAR UNLOADING AREA
ABERDEEN CHEMICAL PLANT
I. Purpose of Design
The purpose of this design is to provide the VCM railcar unloading area with an additional gas monitoring system to detect serious VCM releases. Presently, there are six fixed point monitor locations that are tied into one of the plant's Honeywell GC's. These monitor locations are listed below:
1. Sphere (grade level). 2. Compressor shed (grade level). 3. Between railcar unloading stations number 1 and 6
(Top of railcar level). 4. Between railcar unloading stations number 2 and 7
(Top of railcar level). 5. Between railcar unloading stations number 3 and 8
(Top of railcar level). 6. Between railcar unloading stations number 4 and 9
(Top of railcar level).
These existing monitors do not provide immediate response and are not distributed throughout the entire VCM tank farm area. Also, since this area is not monitored by plant personnel the majority of the time and since it has the potential for a serious release, additional protec tion is needed.
In addition to the gas monitoring system, this design will provide a pressurization blower for the fire pump houses near the VCM tank farm. The purpose of this blower is to prevent VCM from entering the build ings in the event of a serious VCM leak.
This design will also provide for Item 84-6 of the Underwriter's In surance Company recommendations. This item recommended installing vapor detectors for the sphere's VCM transfer pumps to the old and new module.
mih mmm
VAB.0001106273
VCM GAS MONITORING SYSTEM VCM TANK FARM AREA
ABERDEEN CHEMICAL PLANT
A
II. Process Description
This design will provide for the installation of ten VCM gas sen sors, AT-101 through AT-110, in the VCM tank farm area (see P&I dia gram for locations). These sensors will be tied into dual channel combustible gas monitors, AI-121 through 125. Each monitor will accept signals from two sensors and display the higher of the two readings. The monitors will indicate the percent of the lower ex plosive limit (LEL) of VCM gas in the air. The monitors will be tied into alarms in the vinyl control room. The first alarm will be set at 25% LEL and the second alarm will be set at 45% LEL.
Should any of the monitors indicate a low level (25% LEL) of VCM gas in the air, the panel operator will notify the yard operator of the situation. If the monitors indicate a high level (45% LEL) of VCM gas in the air, the panel operator will then notify the yard operator to shut down any transfer or unloading equipment that is being used. When this equipment is off, the panel operator will isolate the sphere by pushing the sphere control valve override switch. This switch will close the following valves:
(1) The valve on the vapor line to/from the compressors.
(2) The valve on the liquid line from the compressors.
(3) The valve on the liquid line to the VCM transfer pumps.
(4) The valve on the liquid recirculation line from the VCM transfer pumps.
The monitors will be equipped with relay connections to tie into the existing sphere isolation control valve override switch. However, the relay connection will not be tied into this switch until the REMOTE OPERATING VALVES project is installed. When this project is installed, additional equipment and valves will be shut off by the sphere isolation control valve override switch. This includes:
(1) The valve on the liquid return line from the VCM vapor line knockout pot.
(2) The five VCM compressors in the VCM tank farm.
(3) The two VCM transfer pumps.
After installation of this project, the relay connections from the
gas monitors will be tred into the sphere control valve override
switch. Should the monitors Indicate a high level (45% LEL) of VCM
gas in the air, the sphere control valve override switch will
automatically shut off all the valves ahd equipment mentioned above.
When the isolation switch is used, it will override the motor con trols and shut down the units should they be in service.
VAB.0001106274
VCM GAS MONITORING SYSTEM
VCM TANK FARM AREA
ABERDEEN CHEMICAL PLANT
II. Process Description - Continued
In addition to the vapor monitors, a pressurization blower, F-150, will be Installed for the fire pump houses. This blower will pro vide air to pressurize fire pump houses #1, #2, #3, and #4. Pressurizing the fire pump houses will prevent any VCM from entering the buildings in the event of a serious VCM leak.
The blower*s controls will be tied into the 25% LEL alarm in the con trol room so that when this alarm goes off, the blower starts. The blower was sized to maintain a 0.25 inch of water pressure in the buildings while providing enough air to the diesel engines for combustion. This blower will be equipped with an extended inlet stack to provide VCM free air in the event of a serious release.
A
VAB.0001106275
VCM GAS MONITORING SYSTEM
VCM TANK FARM AREA ABERDEEN CHEMICAL PLANT
Instrument Specifications
Item No.
Description
AI-121 AI-122 AI-123 AI-124 AI-125
VCM transfer pumps gas monitor South unloading stations gas molntor Middle unloading stations gas monitor North unloading stations gas monitor Compressor shed gas monitor
AT-101 AT-102 AT-103 AT-104
AT-105
AT-106
AT-107
AT-108 AT-109 AT-110
Gas sensor north of VCM transfer pumps Gas sensor east of actuated valves Gas sensor south of unloading stations Gas sensor between #1 and #6 unloading
stations
Gas sensor between #2 and #7 unloading stations
Gas sensor between #3 and #8 unloading stations
Gas sensor between #4 and #9 unloading stations
Gas sensor north of unloading stations Gas sensor north of compressor shed Gas sensor north of VCM sphere
F-150
Fire pump house pressurization blower
HS-130
Handswltch for F-150
w
f
t
*
m- rar-fl
A
MONITORS, INC
3037 ENTERPRISE STREET COSTA MESA. CALIFORNIA 02626 PHONE: (714) 6404806 TWX 678 372
TO: Nr. Prank Jenson Vista Polymers Box 91 Aberdeen, MS
Your Reference: verbal request of 30 Janua:
ITEM
DESCRIPTION
1985
Date: 30 January 1985 GMI QUOTATION NO: 6150
QUANTITY
Please Reference GMI Quote No On All Correspondence.
UNIT PRICE
EXT. PRICE
Model 580 System to include one Dual Channel Monitor, 2 ea Sensor P/N 10001*1, 2 ea Sensor Bousing P/N 10007 and 1 ea Instruction Manual. Standard Relay Configuration. *Common Alarm Relays
Alternate System
Model 610 System to include one Four Channel Monitor, 4 ea Sensor P/N 10001-1, 4 ea Sensor Housing P/N 10007 and 1 ea Instruction Manual. Standard Relay Configuration. *Common alarm relays for all Four Channels. Common alarm set point adjustment.
Note: For a discrete set of alarm relays (Malfunction Low and High) for each channel plus discrete alarm set point adjustment add $470.00 to unit price of item #1A.
lb. Alternate System
Model 4800 system to include one 16 Channel Monitor, 1 ea Extender Card for Channel Card and one for relay card and one Instruction Manual. Blank Panels included at N/C for inactive channels. Each active channel to include one each channel control card. Relay
6 ea
X.
3 ea
$1,764.00 $10,584.00
$2,973.00 $ 8,919.00
Signature: Name/Title
Local Representative Address
Sheet No Phone
Sheets
var nnm 106778
^ J" T
' VI ;
' &" : rv"n
Tjwdfc . *
r1
b
v-
3037 ENTERPRISE STREET COSTA MESA. CALIFORNIA 82026 PHONE: 1714) S40-4EM TWX 878-372
INC
!>-
r -%pt . Ji,
*
'T l-A'VtaH- .
x. - >.. -i
L.
rr
*
f.^r" ""J*P
V 'i'-Jfl *yv-' l at"; :. .v h.J^' fc
4
TO: Mr. Frank Jenson Vista polymers Bock 91 Aberdeen, MS
Your Reference: Verbal reguest of 30 January 1985
ITEM
DESCRIPTION
Date 30 January 1985 GMI QUOTATION NO 6150
QUANTITY
Please Reference GMI Quote No On All Correspondence.
UNIT PRICE
EXT. PRICE
Card, Sensor P/N 10001-1 and Sensor Housing P/N 10007.
11 active channels
Standard Relay Configuration*
Mote: The Standard Relay Configuration is
Malfunction. SPDT, non-latching, energised
Low Alarm . DPDT, non-latching, de-energized.
High Alarm. DPDT, latching, de-energized.
other relay options (Latching and energized) are available.**
**Model 4800 Low & High alarm Relays are SPDT, add $22.00 for each active channel in Item #lb.
DPDT
$11,784.00 $11,784.00 $12,597.00 $12,597.00 $13,410.00 $13,410.00 $14,223.00 $14,223.00 $15,036.00 $15,036.00 $15,849.00 $15,849.00
Signature: Name/Title
Ken Kaub
Local Representative
Address
Phone
Sheets
VAB.0001106279
%
Description
General Monitors' Model 580 is a compact highly-versatile system for contin uously monitoring combustible gas concen trations in two locations. The system consists of two remote sensing assemblies and a solid-state controller.
For safety, reliability, and ease of calibration, sensor outputs are not summed. Each channel is completely independent and has its own constant current sensor drive circuit. Sensors are available to meet various service requirements for most gases.
The Model 580 independently moni tors two locations. The controller automati cally displays the higher reading channel on an analog meter, scaled from 0-100% LEL (Lower Explosive Limit). Manual over ride switching permits readout of the low channel at any time. Low and high alarm set-points are common to both channels. Calibration of each channel is done inde pendently, and an alarm override switch disables the alarms during the calibration mode. A 45 second time delay also disables the alarms on start-up.
Customers may select from a wide variety of relay options, such as normally energized or de-energized high and low alarms, and latching or non-latching high and low alarms. The malfunction relay circuitry is normally energized and monitors both channels.
Features
"Peak Picking" Circuitry Automatically displays highest reading channel
Compact Packaging Dimensions: 2WW x7"H x11.5wD (51 mm W x178 mm H x 292 mm D)
Low Power Consumption Analog Meter Standard
Independent 3 AMP/117 VAC DPDT High and Low Alarm Relays 3 AMP/T17 VAC SPDT Malfunction Alarm Relay
Variety of Relay Options Normally energized or de-energized high and low alarm Latching or non-latching high and low alarm
Remote Reset
Superior Reliability Two week factory burn-in of system Single PC. board Solid-state circuitry Proven catalytic sensor Malfunction alarm circuitry Positive contact field terminals Time delay Constant current supply to sensor
U Safe, Easy Calibration Fully accessible calibration adjustments Alarm relays automatically disabled while in calibration mode
Low Cable Costs 40 ohm loop resistance, e g. 3000 ft. (910 meters) one way of #18 AWG cable 7600 ft. (2320 meters) one way of #14 AWG cable
User Protection Two year warranty CSA approved
Applications -- Protection from
hazardous combustible gases in:
Fuel Loading Facilities Compressor Stations LNG Processing and Storage Oil Well Logging L_i Sewage Plants _ Gas Turbine Enclosures
Drilling and Production Platforms Solvent Vapors
Sensor E lements
General Monitors' sensors are designed for reliable performance and long life. Each sensor must undergo extensive burn-in and rigid quality control procedures before shipment.
The sensors consist of two catalytic bead elements in a balanced Wheatstone bridge circuit (See Principle of Operation). These low temperature catalytic bead sensing elements require minimal sensor excitation current, greatly increasing sensor life.
Principle of Operation
A cataiytically treated ceramic active bead and a passivated ceramic reference bead form two legs of a Wheatstone bridge circuit Combustible gases diffuse through a flame arrestor and oxidize on the cataiyti cally treated active bead, causing an increase in its temperature and electrical resistance. This results in an unbalancing of
the Wheatstone bridge circuit. The reference bead, inert to combustible gases, compen sates for ambient temperature, humidity and pressure changes. The difference in resistance of the active and reference beads is converted into a sensor signal which is amplified in the controller, sent to the indicator and alarm circuits, and displayed on an analog meter. The meter is scaled in percent of the Lower Explosive Limit (% LEL). In the Model 580 the two sensor inputs are continuously compared, the higher signal being displayed on the meter.
Two adjustable electronic alarm circuits may be field-set for any alarm level up to 100% LEL. The low alarm signal
indicates potentially hazardous gas accumu
lations at low concentrations, allowing
time for corrective action. The high alarm
signal indicates immediate danger A flashing
malfunction LED will indicate low input
power, sensor removal or damage, "CAL''
mode, severed cable or current failure.
Two LED channel indicators are provided to
indicate the higher channel
A variety of alarm relay options
provides contacts for high, lowland,
. n.oon
malfunction alarms to be wi>eotc?MiQI?Q?y^^^^
lamps, horns, fans or shut-down eouioment.
\\ : >
i-
lftMi*
Analog output meter with linear seal*
calibrated in tha percent oi tower Explosive Limit (% LEU
Used (or normal operation or ciMbration When in the "CAL" mode high and low alarms are disabled.
Status Indicators
HIGH alarm -- flashing red LED LOW alarm -- flashing amber LED READY (power on)--steady green LED MALE (malfunction)--flashing amber LED *High channel indicators--green LED's Channel select switch--blade button
HIGH and LOW alarms--set point adjustments located on circuit board
SPAN and ZERO adjustments for each channel accessible through front panel
RmaHultari Used for manual reset of latching high and low alarm circuits.
Height 7* (178 mm)
5S0
4
-Jr
mu i
Width 7 (51 mm)
Depth tl .5* (292 mm)
Calibration
By placing the recessed toggle switch on the front panel to the calibration mode, the high and low alarm relays are held in standby condition and the "MALF" LED flashes. Zero and span pots are accessible from the front panel Calibration is accom plished by adjusting the meter to zero and exposing one of the two sensors to a known concentration calibration gas and adjusting the meter with the span pot to indicate the concentration The alarm adjustments are located on the side of the controller to prevent tampering.
Relay Options
The versatility of the Model 580 is enhanced bv the availability of different relay operat ing modes for specific user requirements. These relay options include normally energized or de-energized high and low alarms, latching or non-latching high and low alarms and sealed relays
CSA performance certified to C22.2 No. 152-1976
Controller Specifications
Mounting Options:
Rack, panel and wall
Dimensions:
2"W x 7"H x 11 5"D (51 mm W x 178 mm H x 292 mm D(
Weight:
4 lbs (180 kg)
Temperature Range:
0F to 150F(--18C to +bbC)
PoWf*
117 VAC 15% (220 VAC 15% optional), 50-60 Hz. 22-30 VDC, 8 watts nominal
Meter Range:
0-100% Lower Explosive Limit (% LEL)
Repeatability:
2% full scale
Linearity:
5% full scale
Alarm Circuits:
High, low and malfunction: Standard high and low DPDT 3 AMP' 117 VAC resistive, malfunction SPDT 3 AMP/117 VAC resistive, high and low normally de-energized, malfunction normally energized
LED Status Indicators:
Flashing red for high alarm, flashing amber for low alarm, green for ready (power on), flashing amber for malfunction, flashing amber for calibration mode, steady green for each channel indicator
Electrical Classification:
General purpose for mounting in nonhazardous area
Warranty:
Two years
Sensor Specifications
Type:
Continuous diffusion, low temperature catalytic bead. Standard Industrial
Hydrocarbon Sensor, High Temperature Standard Industrial Hydrocarbon Sensor.
Temperature Range:
-65F to 200PF(-55C to +93*0; High Temperature Sensor to 400PF (200PC)
Response Time:
Typically 6-second time constant when exposed to 50% LEL of methane gas
Zero Drift:
Less than 5% per year
Life:
3 to 4 years, normal service
Electrical C lassification:
NEC and CSA, Class I, Division 1. Croup B. C and D: VDE 0171 (Ex) sd 3n G5
Warranty:
Two years
Cable Length:
Maximum 3 wire cable length allow
able between controller and sensor
assembly with one way resistance of
20 ohms (total 40 ohms loop)
AWG
20 18 16 14
FEET
1900 3000 4800 7600
METERS
580 910 1460 2320
Represented by:
3037 Enleronse Street Costa Mesa. CA 92626 Tel (714) 540-4895 Telex 678-372 FAX
106281
VAB.OOOl tee 282
i t1
t
p*w
VCtA feAll-C-ML
nbl^a
VAB.0001106284
J
ui
t:
J.
I;
i;
ru
W" i
y. ::;if ijir
c 1
Vr*
1 !] <
h
C4
I r
j ..
r
.i
;ii
ij i i i r i n, ij "<
1i
%
4i
r^?t
xj\*
u-. iUur>i
f^-6?
%noiCIA38
ki 4< i * rrxi
TM
3SV3ir
*-frD6
1t 1*
4
1
VAB.0001106285
m
I
^w
r f
VAB.0001106286
*
n\
-frD6