Document xz90a157Nrz07XGq99ryqymrQ

1932American Society of Heating and Ventilating Engineers Guide, Table 4. Conductivities (&) and Conductances (C) of Building Materials and Insulations Tests Conducted at the U. S. Bureau of Standards.p Insulation Tests Based on Samples Submitted by Manufacturers Note.--The coefficients in Tables 4^-8, incl., are expressed in Btu per hour per square foot, PER 1 DEG F, PER 1 IN. THICKNESS UNLESS OTHERWISE INDICATED BY NOTE b._______ ____________ _ Material Description Density (Lb. per Cu. Ft.) Mean Temp. (Deg. Fahr.) CONDUC-* TIVITY (k) OR Conduc tance (O Asbestos Wood______ Asbestos Mill Board. Balsam Woolb............ Cabots Quiltb_______ Cabots Quiltb._........ Celotex........ ..... _......... Corkboard....... ............. Corkboard......... ........... Cdrkboard....... ....... Corkboard (Eureka). Dry Zeroh__......... Fibrofeltb................ Flaxlinumb............. ' Gyplap..................... Hairinsulb................... . Hairinsulb......... .......... Hair Feltfa......... ..... Hair Feltb________ Insulex or Pyrocell__ Insulex or Pyrocell-- Insulex or Pyrocell..: Insulex or Pyrocell... Insulite________ _____ Linofelth..................... Lith___ ______ _______ Magnesia' (Rigid)-- Plaster.____...------ ----Regranulated cork-- Rock cork....... ...... -- Rock wool__________ Rock wool---------------Rock wool....... ............ Rock wool____ :-------Sawdust............. .......... Shavings________ ___ Sheetrock..........--.-- Sprayo-Flake.......... Thermofeltb-............. Thermofelth_............. Thermofill__ ^............ Thermofill................... Thermofillb__ 1......... Torfoleum._................ Asbestos and cement compressed--....... Pressed asbestos......................:.................... Chemically treated wood fiber be tween layers of paper...... ...... :.............. Eel grass between Kraft paper-------Eel grass between Kraft paper............... Rigid insulation made from sugar cane fiber....... -.......................................... Pure; no added binder............................... Pure; no added binder............................... Pure; no added binder...........................-- Asphaltic binder............ -.......................-- Kapok between burlap or paper--.....- Flax and rye fiber......... .............................. Flax fiber...................... --............................ Gypsum between layers of heavy paper (H in. thick)............--................ 75% hair; 25% jute.................................... 50% hair; 50% jute.................................... Felted cattle hair......................................... Felted cattle hair.-------- '...............:............. Cellular gypsum--dry........................... . Cellular gypsum--dry--...............-......... Cellular gypsum--dry_............................. Cellular gypsum--dry................................ Rigid insulation made from wood pulp.. Flax fibers between paper....................... Rock wool, flax and straw pulp with binder............................... --..................... 85% magnesia, 15% asbestos................. Gypsum..................._........... ......................... About %> in. particles.....------ t................. Rock wool block with binders...... .......... Fibrous material, made from rock........ Fibrous material, made from rock........ Fibrous material, made from rock........ Fibrous material, made from rock........ Ordinary--........................ ....................... ...... Ordinary--........................................ .............. Gypsum mixed with sawdust between layers of heavy paper (0.39 in. thick) Shredded paper with silica binder......... Jute and asbestos fibers, felted ....... -- Hair and asbestos fibers, felted--------- 1 Dry, fluffy, flaked gypsum.__... ............ . Dry, fluffy, flaked gypsum....................... Dry, fluffy, flaked gypsum....................... Peat moss compressed into sheet form 123.0 60.5 2.2 4.6 3.4 13.2 14.0 10.6 7.0 14.5 1.0 13.6 13.0' 53.5 6.3 6.1 13.0 11.0 30.0 24.0 18.0 12.0 16.9 4.9 14.3 19.3 46.2 8.1 16.7 10.0 14.0 18.0 21.0 -- 60.7 4.2 10.0 7.8 34.0.. 26.0 19.8 10.2 86 86 90 90 90 90 90 90 ,90 90 90 90 90 90 90 90 90 90 . 90' 90 90 90 90 90 90 86 86 90 86 90 . 90 90 90 86 86 90 . 94 90 90 90 90 90 91.5 2.70 0.84 0.27 0.26 0.25 0.34 0.34 .0.30 0.27 0.32 0.24 0.32 0.31 2.60b 0.27 0.26 0.26 0.26 1.00 0.77 ' 0.59 0.44 0.34 0.28 0.40 0.51 2.32* 0.31 0.37 0.27 0.28 0.29 0.30 1.04 0.71 3.60b 0.28 0.37 0.28 0.60 0.52 0.35 0.29 . Woods: Balsa wood--......... Balsa wood............ Balsa wood............ Cypress--.--........ Maple________ ^...... Mahogany_______ Virginia Pine-----White Pine--........ .. Across grain........... .. Across grain... ....... .. Across grain .. Across grain.......... .. Across grain .. Across grain........... .. Across grain.......... .. Across grain.......... 20.0 8.8 7.3 28.7 44.3 34.3 34.3 31.2 90 90 90 86 86 86 86 86 0.58 0.38 0.33 0.67 1.10 0.90 0.96 0.78 ; aln addition to the conductivity values for the authorities listed, considerable work of importance per taining to the heat transmission of various types of construction and materials has been done by the late Prof. John R. Allen and the late Prof. A. J. Wood of the Engineering Experiment Station of Pennsylvania ' State College. ,... bFor thickness stated or used in construction, not per 1 in. thickness. iThcftSidurtivity of plaster varies with the composition. Note range of-values from 2.32 to 8.0. The average value for plaster is probably about 5.0. On account of the comparatively high conductivity of plaster and the fact that it is seldom applied more than X in. thick, thismaterial does not appreciably effect the over-all transmission of a construction, excepting in the case of thin uninsulated walls. r; : pSee Chapter LX, by Chas. H. Herter of the Report of the Insulation Committee. A. S. R. b... Annual Meeting 1922, Revised'to 1924, entitled. Heat Transmission of Insulating Materials for a more compre hensive collection of heat transmission data relating to building and insulating materials. 32 Chapter 3--Heat Transfer Through Materials and Constructions Material Brickwork. ...................... Cement Mortar.................... Hollow Clay Tile................. Plaster (gypsum).............. Total resistance (R)...... Thickness Inches 12 A 2 A Internal Conductivity or Conductance Surface Coefficients h r V 5.0 (i) 8.0 (*) 1.18 (C) 2.32 (k) 4.02 (/,,) 1.34 (/!) Internal Resistance . Subface Resistance 2.400 0.063 0.847 0.215 3.525 0.249 0.746 0.995 3.525 4.520 U =. = 4520 = 0-^21 Btu per hour per square foot per degree difference in temperature between the air oh the two sides of the wall. In computing heat transmission coefficients of floors laid directly on the ground (Table 28), only one surface coefficient (/i) is used. For Table 5. Conductivities (k) and Conductances (C) of Building Materials and Insulations Based on Tests Conducted at. the University of Illinois, By A. C. Willard, L. C. Lichty and L. A. Harding p Material Description Density (Lb. per Cu. Ft.) Mean Temp. (Deg. Fahr.) CONDUC-" TIVITY (k) OR Conduc tance (O Asbestos Asbestos Board ....................... Brickwork.________ . . Corkboard 2 in. hollow clay tile, M in. 4 in. hollow clay tile, H in. 6 in. hollow clay tile, X in. Plaster Ronfinch Roofinph Stucco Wood (Fir. one- surface finished)...... .......... Built-up bitumen and felt, gravel or Built-up bitumen and felt, gravel or slau surfaced Across grain................................................. 48.3 20.4 132.0 140.0 9.7 120.0 127.0 124.3 13.5 ............ 33.4 110 100 110 110 100 lid -- 0.29 0.48 4.00 5.00J 8.001 8.30 0.32 1.00b 0.60b 0.47b 0.51 8.00* 5.30d-b 8.001 1.00 _.*In addition to the-conductivity values for the authorities listed, considerable work of importance per taining to the heat transmission of various types of construction and materials has been done by the late Prof. John R. Allen and the late Prof. A. J. Wood of the Engineering Experiment Station of Pennsylvania State College. bFor thickness stated or used in construction, not per 1 in. thickness. ^Calculated from 2 in. tile tests. , ^Cement mortar and stucco assumed same as cement plaster. bRoofing, 0.15 in. thick (1.34 lb per sq ft), covered with gravel (0.83 lb per sq ft), combined thickness assumed 0.25. `The conductivity of plaster varies with the composition. Note range of values from 2.32^to 8.0. The average value for plaster is probably about 5.0. On account of the comparatively .high conductivity of plaster and the fact that it is seldom applied, more than X in. thick, this material does not appreciably effect the over-all transmission of a construction, excepting in the case of thin uninsulated walls. iRecommended value. See Mechanical Equipment of Buildings, by Harding and Willard, Vol. I, second edition, 1929, p. 182. pSee Chapter LX, by Chas. H. Herter of the Report of the Insulation Committee, A. S. R. E,, Annual Meeting, 1922, Revised to 1924, entitled. Heat Transmission of Insulating Materials for a more compre hensive collection of heat transmission data relating to building and insulating materials. 33