1932American Society of Heating and Ventilating Engineers Guide,
Table 4. Conductivities (&) and Conductances (C) of Building Materials and Insulations
Tests Conducted at the U. S. Bureau of Standards.p Insulation Tests Based on Samples Submitted by Manufacturers
Note.--The coefficients in Tables 4^-8, incl., are expressed in Btu per hour per square foot,
PER 1 DEG F, PER 1 IN. THICKNESS UNLESS OTHERWISE INDICATED BY NOTE b._______ ____________ _
Material
Description
Density (Lb. per Cu. Ft.)
Mean
Temp. (Deg.
Fahr.)
CONDUC-*
TIVITY (k) OR
Conduc tance (O
Asbestos Wood______ Asbestos Mill Board. Balsam Woolb............
Cabots Quiltb_______ Cabots Quiltb._........ Celotex........ ..... _.........
Corkboard....... ............. Corkboard......... ........... Cdrkboard....... ....... Corkboard (Eureka). Dry Zeroh__......... Fibrofeltb................ Flaxlinumb............. ' Gyplap.....................
Hairinsulb................... . Hairinsulb......... .......... Hair Feltfa......... ..... Hair Feltb________ Insulex or Pyrocell__ Insulex or Pyrocell-- Insulex or Pyrocell..: Insulex or Pyrocell... Insulite________ _____ Linofelth..................... Lith___ ______ _______
Magnesia' (Rigid)-- Plaster.____...------ ----Regranulated cork-- Rock cork....... ...... -- Rock wool__________ Rock wool---------------Rock wool....... ............ Rock wool____ :-------Sawdust............. .......... Shavings________ ___ Sheetrock..........--.--
Sprayo-Flake.......... Thermofeltb-............. Thermofelth_............. Thermofill__ ^............ Thermofill................... Thermofillb__ 1......... Torfoleum._................
Asbestos and cement compressed--.......
Pressed asbestos......................:.................... Chemically treated wood fiber be
tween layers of paper...... ...... :.............. Eel grass between Kraft paper-------Eel grass between Kraft paper............... Rigid insulation made from sugar
cane fiber....... -.......................................... Pure; no added binder............................... Pure; no added binder............................... Pure; no added binder...........................--
Asphaltic binder............ -.......................-- Kapok between burlap or paper--.....-
Flax and rye fiber......... .............................. Flax fiber...................... --............................ Gypsum between layers of heavy
paper (H in. thick)............--................ 75% hair; 25% jute.................................... 50% hair; 50% jute.................................... Felted cattle hair......................................... Felted cattle hair.-------- '...............:............. Cellular gypsum--dry........................... . Cellular gypsum--dry--...............-......... Cellular gypsum--dry_............................. Cellular gypsum--dry................................ Rigid insulation made from wood pulp..
Flax fibers between paper....................... Rock wool, flax and straw pulp with
binder............................... --..................... 85% magnesia, 15% asbestos................. Gypsum..................._........... ......................... About %> in. particles.....------ t................. Rock wool block with binders...... .......... Fibrous material, made from rock........ Fibrous material, made from rock........ Fibrous material, made from rock........ Fibrous material, made from rock........ Ordinary--........................ ....................... ...... Ordinary--........................................ .............. Gypsum mixed with sawdust between
layers of heavy paper (0.39 in. thick)
Shredded paper with silica binder......... Jute and asbestos fibers, felted ....... -- Hair and asbestos fibers, felted--------- 1 Dry, fluffy, flaked gypsum.__... ............ . Dry, fluffy, flaked gypsum....................... Dry, fluffy, flaked gypsum....................... Peat moss compressed into sheet form
123.0 60.5
2.2 4.6 3.4
13.2 14.0 10.6
7.0 14.5
1.0 13.6 13.0'
53.5 6.3 6.1
13.0 11.0 30.0 24.0 18.0 12.0 16.9
4.9
14.3 19.3 46.2
8.1 16.7 10.0 14.0 18.0 21.0
--
60.7 4.2
10.0 7.8
34.0.. 26.0 19.8 10.2
86 86
90 90 90
90 90 90 ,90 90 90 90 90
90 90 90 90 90 . 90' 90 90 90 90 90
90 86 86 90 86 90 . 90 90 90 86 86
90 . 94 90 90 90 90 90 91.5
2.70 0.84
0.27 0.26 0.25
0.34
0.34 .0.30
0.27 0.32 0.24 0.32
0.31
2.60b
0.27 0.26 0.26 0.26 1.00 0.77 ' 0.59 0.44 0.34
0.28
0.40 0.51 2.32*
0.31 0.37 0.27 0.28 0.29 0.30 1.04
0.71
3.60b
0.28 0.37 0.28 0.60 0.52 0.35 0.29
.
Woods: Balsa wood--.........
Balsa wood............ Balsa wood............
Cypress--.--........ Maple________ ^...... Mahogany_______
Virginia Pine-----White Pine--........
.. Across grain........... .. Across grain... .......
.. Across grain .. Across grain..........
.. Across grain .. Across grain...........
.. Across grain.......... .. Across grain..........
20.0 8.8 7.3
28.7 44.3
34.3 34.3 31.2
90 90 90 86 86 86 86
86
0.58
0.38 0.33 0.67 1.10
0.90 0.96 0.78
;
aln addition to the conductivity values for the authorities listed, considerable work of importance per taining to the heat transmission of various types of construction and materials has been done by the late Prof. John R. Allen and the late Prof. A. J. Wood of the Engineering Experiment Station of Pennsylvania
' State College.
,...
bFor thickness stated or used in construction, not per 1 in. thickness.
iThcftSidurtivity of plaster varies with the composition. Note range of-values from 2.32 to 8.0. The
average value for plaster is probably about 5.0. On account of the comparatively high conductivity of plaster and the fact that it is seldom applied more than X in. thick, thismaterial does not appreciably effect the over-all transmission of a construction, excepting in the case of thin uninsulated walls. r;
: pSee Chapter LX, by Chas. H. Herter of the Report of the Insulation Committee. A. S. R. b... Annual Meeting 1922, Revised'to 1924, entitled. Heat Transmission of Insulating Materials for a more compre
hensive collection of heat transmission data relating to building and insulating materials.
32
Chapter 3--Heat Transfer Through Materials and Constructions
Material
Brickwork. ...................... Cement Mortar.................... Hollow Clay Tile................. Plaster (gypsum)..............
Total resistance (R)......
Thickness Inches
12
A
2
A
Internal Conductivity
or
Conductance
Surface Coefficients
h r V
5.0 (i) 8.0 (*) 1.18 (C)
2.32 (k)
4.02 (/,,) 1.34 (/!)
Internal Resistance .
Subface Resistance
2.400 0.063 0.847 0.215
3.525
0.249
0.746 0.995 3.525 4.520
U =. = 4520 = 0-^21 Btu per hour per square foot per degree
difference in temperature between the air oh the two sides of the wall. In computing heat transmission coefficients of floors laid directly on
the ground (Table 28), only one surface coefficient (/i) is used. For
Table 5.
Conductivities (k) and Conductances (C) of Building
Materials and Insulations
Based on Tests Conducted at. the University of Illinois, By A. C. Willard, L. C. Lichty and L. A. Harding p
Material
Description
Density (Lb. per Cu. Ft.)
Mean
Temp. (Deg. Fahr.)
CONDUC-" TIVITY (k)
OR Conduc tance (O
Asbestos Asbestos Board .......................
Brickwork.________ . .
Corkboard 2 in. hollow clay tile, M in.
4 in. hollow clay tile, H in.
6 in. hollow clay tile, X in.
Plaster Ronfinch
Roofinph
Stucco Wood (Fir. one-
surface finished)...... ..........
Built-up bitumen and felt, gravel or Built-up bitumen and felt, gravel or
slau surfaced
Across grain.................................................
48.3 20.4 132.0
140.0 9.7
120.0 127.0 124.3
13.5
............
33.4
110 100 110 110 100 lid
--
0.29 0.48 4.00 5.00J 8.001 8.30 0.32
1.00b
0.60b
0.47b 0.51 8.00*
5.30d-b 8.001
1.00
_.*In addition to the-conductivity values for the authorities listed, considerable work of importance per taining to the heat transmission of various types of construction and materials has been done by the late Prof. John R. Allen and the late Prof. A. J. Wood of the Engineering Experiment Station of Pennsylvania State College.
bFor thickness stated or used in construction, not per 1 in. thickness. ^Calculated from 2 in. tile tests. , ^Cement mortar and stucco assumed same as cement plaster. bRoofing, 0.15 in. thick (1.34 lb per sq ft), covered with gravel (0.83 lb per sq ft), combined thickness assumed 0.25. `The conductivity of plaster varies with the composition. Note range of values from 2.32^to 8.0. The average value for plaster is probably about 5.0. On account of the comparatively .high conductivity of plaster and the fact that it is seldom applied, more than X in. thick, this material does not appreciably effect the over-all transmission of a construction, excepting in the case of thin uninsulated walls. iRecommended value. See Mechanical Equipment of Buildings, by Harding and Willard, Vol. I, second edition, 1929, p. 182.
pSee Chapter LX, by Chas. H. Herter of the Report of the Insulation Committee, A. S. R. E,, Annual Meeting, 1922, Revised to 1924, entitled. Heat Transmission of Insulating Materials for a more compre hensive collection of heat transmission data relating to building and insulating materials.
33