Document xz08zz1kdnrwmbLEOV8v0r2NQ

AH 4v`t fov `tWi j ^ooIP- V\e (^ Geo-^e <'oAv\e^ *) (Tuk'W * fcl wYiev" V'is'/i-i" \ *- * --ThermJjTLo FR FLUID HEAT SYSTEMS ENGINEERING HEAT TRANSFER DATA A DosiQn Guido For Engineering Low-Cosi, Low-Pressure FIRE-RESISTANT HEAT TRANSFER SYSTEMS HONS 076587 ^j-o T^AI^LvmJ<-v\^J(^ / m # TABLE OP CONTENTS Pag* Introduction.......................................................................................... 1 Properties Important To Heat Transfer Design................................. Curves: Viscosity/Temperature; Density, Specific Gravity............. 4 Curves: Specific Heat; Thermal Conductivity................................... 6 Specific Heat of Therminot Fluids: Relationship To Density........... .0 b The Heater............................................................................................ .e Therminol System Components......................................................... Pumps, Piping, Valves, Rotary Joints, the Expansion Tank, etc. it Testing, Cleaning, Filtering................................................................. 14 Controls for the Therminol System.................................................... 10 Operation and Maintenance of the Therminol System..................... 10 Typical Therminol Systems................................................................ 10 Therminol Engineering Data............................................................... 22 Resistance ot Valves and Fittings To Flow of Fluids........................ 20 Pressure Drop; Heat Transfer Rate, Heat Exchangers...................... 30 Viscosity Conversion Chart................................................................ 30 Engineering Conversion Factors......................................................... 30 Typical Applications tor Therminol Systems.................................... 40 Safety ot Handling Therminol Fluids................................................. 40 Notes..................................................................................................... 47 M0N5 076588 ^..imnnsghs --thermXrix^JL FR FLUID HEAT SYSTEMS... Delivering High-Temperature Process Heat as a Liquid A rocently at 1941, process engineers were limited to two methods of delivering process heat: DIRECT FIRING or PRESSURIZED VAPOR. Each method had definite draw backs. Direct firing was often unsatisfactory becauso the heating was uneven, the tempera tures difficult to control, and the processing of combustible materials extremely hazardous. Prcasured-vapor, such as steam, required costly, high pressure piping, valves, and proc essing equipment--plus constant chemical "conditioning" of boiler water. Heat energy and temperature loas were common with pressured-vapor systems because of "blowdowns," condensation, and the inevitable pressure loss with long runs of piping. Today, non-pressurized, high-temperature, fire-resistant heat transfer systems based on Monsanto's TUERMINOL FR Heat Trans fer liquids overcome practically all the de ficiencies and drawbacks of direct firing and pressurized-vapor heating. THERMINOL FR--a series of high-boiling, heat-stable organic liquids, delivers processing heat to single or multi-users as a liquid without pres surizing. THERMINOL fluids are safe and fire resistant. Heating is uniform; and tem perature control is accurate within a range of plus-or-mmus 2F. Heat transfer systems now in use for several years have proved THERMINOL fluid heat successful in a wide variety of process healing operations... from food cooking to chemical processing, from distillations to drying ovens and in petroleum refining. Design engineers and manufacturers have developed a variety of THERMINOL FR Fluid Systems ranging from Bmall electrically heated units to giant gas or oil fired units-- all capable of delivering heat AS A LIQUID. HONS 076589 1 This manual explains and illustrates the fundamentals of THERMINOL fluid heat transfer systems design. It lists materials of construction and components for use with THERMINOL, and explains how each is "designed in'* to make the most efficient system for safe, economical and reliable opera tion. It shows how these systems can be adapted to a wide variety of heating and cooling processes. This engineering heat trans fer data has been compiled to aid the Process Engineer In designing a safe, minimum main tenance system for delivering heat to the points of use in practically any commercial or industrial process. PR HEAT TRANSFER LIQUIDS... Monsanto THERMINOL FR heat transfer liquids are chlorinated biphenyls, manufac tured under exacting process control to pro duce fluids consistent in ail properties impor tant to heat transfer. THERMINOL FR products are unique in that they are actually produced to rigid specifications for thermal stability, specific heat, thermal conductivity, vapor pressure, and viscosity. There are three THERMINOL FR products, with a range of low temperature fluidity and boiling poinU that allows the user to select the best balance of fluid properties for a specify use: THERMINOL. PR I with lowest temperature fluidity --excellent for processes requiring both heating and cooling THERMINOL FR 2 with optimum balftnce of properties for use in most common industrial heating applications THERMINOL PR 3 with highest boiling point for special proc essing equipment applications MOWS 076590 PROPERTIES IMPORTANT TO HEAT TRANSFER OE8ION 1: ' ' ," ' ; ' THRRMINOL FM-I >V v '' Ttmpiralun f. c. 074bo 10.0 100 100 W too OS too too 44to00o00 111107S44710 ut too too too too 000 t7o0o0 n0174o19 1Knlkalpy (pacific Has Thermal Conduct. BTU/lb. (TU/Lb.--*F. BTU/FE, Hr.,*F./FL 4.090 10.00 00.180788 ; 1111o404010709079000t.........o9009440M80o00070 010090..7100 ttt.tfe 000000000000............99408010000078040010089871008004970018409878090 00000000000000..............0000000000000098099659605906940830400780008080008708176010770099007000 < ' . > ^ Oanafty Lb./Qal. 11I111..H8415000 1111100000.....0075(0068016600 ' tw 000...801078108 . O8.t8o7e8 Vlacaally Lb./Hr.--Ft 78141o003801116885.....1.41..1.00747911803470004n104878887058058487o1391888800o11 Hg, Absolute 8188084189118670081.16 psla pda THIRMINOL PR -a Vv` Tampinlura F. c. 0 100 100 too ISO too 44to00o00 1110S0t471047000719..00 tst too too too too too t7o0o0 00n74o19 Knthalpy (pacific Heat Thermal Conduct. Oenelty BTU/lb. (TU/Lb.--*F. BTl)/Ft!, Hr.,*f./FL Lb./(aL 147..0010 0n4704t...o.411o140 11111070088740000......070001140090 810090..4090 0000000.......9088888009900700847840480 0o00000.......800998n408041o0978141o40007 0000000000000.............00000000000006556659886959489804708787898409804006804188710990508 aostn 111111111881......087800008808306098 . 111100f00000e........48016080040708000008700 Vlaeealty Vapor Free. mm. Lb./Hr.--Ft. Hg. Absolute 710818000061118141710.......111..819089888818700691979483101701108961906 091180471867406990.8 pale Tampiwliin F. c. 1t0o0 100 too too too t44o00o00 too too , too : t7o0o0 0170..00 t0o9 '8t11074t470l tat too tot n0074o19 THIRMINOL PR -* . Enthalpy (pacific Hast Thermal Conduct. Denalty BTU/Lb. (TU/Lb.-T. BTU/Ft!, Hrn F./Ft Lb./(al. 8410140..J.0000907 111004t081t0940M3J.....17471O070000 111007187...180148 00000000000000.............18098908088888140408089807790978008891889804489000409 00000000000000..............0000000000000096556659995599810504035415784081091080790017348860056000 111111111111100100101818988............1.00091840880570770000688930018617476008840 Vlaeealty Vapor Proa. mm. Lb./Hr.--Ft. ___ Hg. Abaoluta 10180818048117111488............81463195910607017060360146819976890698591 487118881304439335 MOWS 076591 3 F VISCOSITY-TEMPERATURE CHART DENSITY AND SPECIFIC GRAVITY MOHS 076592 SPECIFIC S R A V ITY -em S /C C SPECIFIC HEAT THERMAL CONDUCTIVITY HONS 076593 BTU/HIL. FT.. F./FT. SPECIFIC HEAT S T U /IA , *F. ' nummrt* WTitfrtmai specific heat of--f h e r rrxJLrLaJL FR Its Relationship to Density Specific heat-- the quantity of heat required to rata the temperature of a material one degree, compared to the heat required to raise a like mass of water one degree--compares the material with water, pound for pound. When comparing specific heat values of THKKMINOL Fit liquids with correspond ing values of other heat transfer fluids, it is important to note that the density of THKKMINOL is much higher than the den sity of other fluids commonly used in heat transfer. In consequence, the heat capacity of THKKMINOL fluids is greater than imme diately apparent from the specific heat values. In transferring heat, a volume of fluid is circulated to give up or absorb heat and the heat capacity of that volume of fluid is the factor that determines the heat transfer ca pacity of the system. When s comparison is made on a volume basis (as illustrated below), THERM1NOL liquids are comparable to other organic liq uids and superior to some: SPECIFIC HEATS OF VARIOUS FLUIDS at ROOM TEMPERATURE Pound*/ Oal. Spocmc Hoat Haaf Capacity (BTU/lb./ (BTU/,.1./ eF.) r.) THERMINOL FR 2 Organic Fluid "A" Petroleum Oil 12.03 8.82 7.9 0.276 0.378 0.376 3.32 3.33 2.88 R;UJBXSL # THE FLUIDS the costly safety devices required in equip THKKMINOL FH liquids are unique. They permit installation of a non-pressurized Bys ment circulating a flammable fluid at or above its fire point. These economies show tem operating with a liquid which has no up both in the type of components needed fire point, and will not support combustion. and in the layout of the system. i THKKMINOL FK liquids are so fire-resist Still another unique property of THKKM ant they have been listed with Underwriters' INOL fluids is their unusual chemical inert laboratories! ness. They are among the moat oxidation- I ftecausc of this extreme fire resistance and its resistant compounds known. This inertness recognition by insurance companies, impor prevents the formation of oxidation sludges tant savings can be made in designing a if the hot fluid comes in contact with air. processheating system around THKKMINOL This extends the useful service life of the heat FK fluids. The savings include not only the transfer fluid; occasionally allows .economies lower capital cost of non-pressurized equip in design. However, THEKMINOL FK fluids ment, its simplified installation and lower are not intended for use in open vessels but maintenAnce; but also elimination of some of in properly vented, closed systems. MONS 076594 Chemically, THKRMINOL FR fluids are resistant to strong acids, mild alkalies, and dilute solutions of strong alkalies. THERMAL STABILITY THKHM1NOL Fit fluids are thermally stable. They are manufactured to meet strict thermal stability specifications. Each produc tion run is tested in Monsanto's laboratories with special equipment developed by Monsanto to assure that these fluids meet the high standards of thermal stability. Any material which docs not meet these standards is rejected. It is characteristic of almost all organic mate rial to undergo chemical change when ex posed to high temperatures for long periods of time. The type of chemical change depends upon the molecular structure of the fluid; the degree of change depends on the temperature, and the length of time of exposure. THKKMINOL Fit fluids resist chemical change up to temperatures of 600F. and show no measurable change after years of exposure to such temperatures. Exposure to tcm|>oraturc8 above 600F.-- even localized overheating will only cause some formation of "high boilers"; molecules of THKRMINOL FK will join together to form larger molecules quite similar to the original material, but higher in viscosity and in boiling point. These high boilers arc soluble in the fluid up to reasonable concentrations; so overheating only Increaaca the fluids' room temperature viacosity slightly. When a concentration of approximately 6-10 percent "high boilers" has boon formed, however, the viscosity begins to rise quite sharply. With this change, small but measurable amounts of dry hydrogen chloride gas are evolved. This should be removed from the system by appropriate venting. When THKKMINOL FR fluids operate at high bulk temperatures, or, where some local over heating may occur, the system should be designed to prevent moisture from condensing in the vapor spaces where this hydrogen chloride gas is being vented. When the hydrogen chloride is dry, it has little or no effect on metals in the system. However, if the hydrogen chloride dissolves in moisture, an acid corrosive to certain metals is formed. A properly designed heater and distri bution system operated at or below 600F., will allow use of the same fluid for many years. While THERMINOL FR fluids normally are operated to a maximum temperature of 600F. --systems specially designed for operation at higher temperatures have proved successful. At higher temperatures--"high boiler" forma tion with attendant viscosity increase is, of course, accelerated and a shorter service life must be expected. However, side stream dis tillation can be employed to constantly re move higher boiling materials while the sys tem is in operation. Periodic make-up is added to replace the quantity of the high boiler material removed. An alternate procedure for higher tempera ture operation, which is somelimeB more suitable for smaller installations, is periodic replacement of the THERMINOL charge, reclaiming the used fluid by straight take over distillation. (Monsanto Bhould be con tacted for details regarding this procedure.) On systems containing only 50-100 gallons of THKRMINOL, it is usually most economical to periodically discard the entire charge and replace it with new fluid. THERMINOL SYSTEM DESIGN When designing a THERMINOL FK syBlem it is important to remember this fact: THE FLUID CAN BE NO BETTER THAN THE SYSTEM! THERMINOL FR liquida are ideally suited for high temperature preci sion heating and temperature control applica tions, but only if the heater and distribution system are properly designed, constructed and operated. While there is nothing profoundly different or complicated about a THKRM INOL system, certain design parameters must be rigidly observed if the system is to operate trouble-free, efficiently, and with realization of the full benefits of heat de livered by a liquid. MGAS 076595 the heater The heater is the moat critical component in THERMINOL system. Accordingly, the heater should be elected with great caret Two basic healer designs for THERMINOL fluids are available: the liquid tube and fire tube types. In liquid tube heaters, the THERMINOL is pumped through the tubes at a definite flow rate as it is heated; in fire tube types, THERMINOL flows through the "shell** of the heater surrounding the fire tubes. When operating temperatures of 500F. (or higher) are required, a liquid tube type healer is to be preferred ... unless a specific design is devised to force a Bteady flow over the heat donor surfaces. Since THERMINOL fluids transfer heat in liquid form, they do not form vapor to ac celerate convection circulation. To avoid hot Bpola in a THERMINOL heater, the fluid should be pumped over the heating surfaces Av that no area of stagnant fluid occurs, v&uid velocities over the heat donor surfaces should be relatively high; generally 4 to 10 feci per second. This helps avoid both exces sive fluid film temperatures and also reduces the quantity of fluid in the high temperature film that is in direct contact with the heat donor surface. The illustration shows the effect of fluid velocity on film temperature and indicates the importance of this design requirement. EFFECT OF LIQUID VELOCITY ON FILM TEMPERATURE DURING HEATING High Liquid Velocity Lew Uquftf Velocity Importance of Fluid Velocity and Film Tem perature through Heater A bulk fluid temperature of 600F. and a maximum film temperature of 640F. ensures long service life of THERMINOL FR fluids. Note the significance of "maximum" film temperature: heating is not uniform in fired *0NS 076596 henter, and maximum conditions--not aver age--muet be used to determine the recom mended 640F. ceiling. Example: The film coefficient for THERMINOL in a given healer is 250 BTU/hr. eq. ft., F.( and the fluid temperature is 670F. 1'hc average radiant absorption rate is 9,000 RTU/sq. ft., hr. The maximum ra diant absorption rale is 17,000 BTU/aq. ft., hr. The average film temperature i 9.000 570 H 606F., 250 but the maxmium film temperature is 117 ,A0A0A0 670 H 630F. 250 Fast experience ehowe that when purchasing a healer, the buyer should insist that design and capacity provide optimum film tempera ture for the fluid. The method of I/obo and Evans5* is useful in calculating film temperatures in radiant heaters. When electric healers are used--heat flux is more even. However, it is important to re member that all of the heat from the electric element passes into the fluid. The watt-density on the surface of the healer tube and the fluid velocity past the tube should be in proper balance to avoid excessive THERMINOL film temperatures. Watt-densities in the range of 8 to 10 watts per square inch with a minimum velocity of 4 feet per second are suggested. However, watt-densities in the 18 to 22 watt per square inch range have proved satisfactory in properly designed installations. Heaters for THERMINOL Bhould meet local code requirements. However, the fire resist ance of THERMINOL FR fluids will often permit important economies in the design and placement of fired heater equipment. With gas-fired heaters, the THERMINOL unit need not be placed outside of the building or isolated in a fireproof structure unless the use process requires such precaution. Steam or inert gas smothering devices can generally be eliminated and a vapor tight firebox to retain smothering gases is not necessary. The fuel for THERMINOL heaters is purely optional. Gas- or oil-fired heaters, and elec tric resistance heating are all used with success. Coal-fired heaters are generally not recommended because of their slow response to change of load at the heat source. The over-all thermal efficiency of a fired heater will generally be comparable to steam boilers of similar size. Efficiencies of 75 to 80 percent can be expected when convection sections are added. Efficiencies of 60 to 70 percent are achieved with only a radiant section. (!) Lobo, W. E.. and J. E. Evan*, Tran*. AlChE, 35. 743 (1939) HONS 076597 10 PUMPS FOR THE fhefl FLUID HEAT SYSTEM... In selecting pumps for a THERM1NOL system, it is important that the pump ca pacity and pressure head be sufficient to circulate the fluid at the rate demanded by the particular installation. For large flow rates, the fluid circulating pump should gen erally bo the centrifugal type and any one of a number of brands of standard high tem perature centrifugal pumps designed for hot liquid service is suitable. Dean Brothers, Worthington, IngorsolMiand and Chempump for example, are all used satisfactorily. For most THERM1NOL systems, cast steel pumps are best. Pump manufacturers usually specify that above 450*F. fluid temperatures, a water jacketed, deep stuffing box or me chanical seal and water-cooled bearings be used. Mechanical seals are used widely today. It is suggested that with a stuffing box, eight rings of packing be provided. Durametallic No. D-110, Garlock No. 736 and equivalent packings are satisfactory for the pump, and an open, non-overloading impeller is desirable to handle the cool, relatively viscous liquid at start up. When a new system is first put into operation, a alight leakage may be noticed at the pump packing. It is not advisable to tighten the pump gland, however, until the system has heated up close to the temperature of operation. Canned pumps such as Chempump Series T require no ecal and have proved very service able in T1JERM1NOL systems. Small gear pumps are also used successfully in THERM* 1NOL FR service because the fluids have good high temperature lubricating properties. However, gear pumps characteristically de crease in pumping capacity after extended use. When gear pumps are used, care should be taken in selecting the capacity so there is a margin that will assure adequate flow through the heater. Regardless of the type of pump selected, the flow rate should be checked regularly against its performance when new. To avoid shaft trouble and leakage at the seals, it is important to provide adequate expansion joints and to support the piping in a way that avoids stresses on the body of the pump. Direct-connection pumps driven by 1,750 rpm. motors are most commonly used. Each pump should be fitted with a control to switch off the burner in case of pump failure. If expansion loops are used in the pump suction piping, they should be horizontal or vertically downward. They should not be vertically upward, for in such a position they form a trap which can collect air and non condensibles, and seriously hamper the pump's performance. PIPING... The most important factors in the piping layout for a THERMINOL FR system are: (A) Proper sizing for the required flow rate and (B) minimizing pressure drop. Because the system will undergo temperature changes, HONS 076599 adequate expansion joints and loops to relieve expansion and contraction stress are essential. Generally, Schedule 40 seamless steel pipe is used with THERMINOL FH systems, It is characteristic of most organic fluids (includ ing THEKMINOL) to have a tendency to leak through joints and fittings at high tem peratures unless these fittings are very tight. Therefore, flanged joints should be used sparingly to minimize potential leak points. Threaded connections are used with THEKMINOL FK up to a one-inch maxi mum size. Care is required in cutting the threads to assure a proper fit; a clean, new die is recommended. Careful attention to threading procedure should provide a good threaded connection. It is not wise to rely upon the use of pipe dope to eliminate leak age. However, pipe dope should be used. Q-scal (Quigley Company, Inc.); Plastiseal (Johns Manville); and Crane's No. 425 are all used auccessfully in THERMINOL FH systems. I n larger size pipes, welded connections should be used wherever practical. Careful layout and use of curved sections of pipe can mini mize the welded or flanged connections re quired. When a flanged connection is made, 150 pound raised face flanges are recom mended. The flange should be backwclded to the pipe and proper gasketing used. Spiral wound (Spiratalic or Flexitallic) asbestos and stainless steel gaskets are good. Small lip spiral wound gaskets are preferred over the wide lip type, because they allow bet ter compression with the 160 pound flange. Oarlock short fiber, pre-cut and cured as bestos gaskets have also proved satisfactory. It is recommended that high temperature bolts, such as Crane Triplex steel bolts, which do not stretch, be used. All high points in the piping system should be provided with vent valve connections. VALVES... One hundred and fifty pound cast steel valves with deep slutting boxes are satisfactory for THEKMINOL systems. Cast steel ball valves designed for high temperature (such as offered by Hills McCanna have also proved very effec tive, particularly where quick open-and-close action is desired. ROTARY JOINTS... It is wise to take particular care in the in stallation and maintenance of rotary joints in order to assure long service life and mini mum leakage. Install such joints with proper flexible connections to assure alignment at all times. Rotary joints should not be operated in a new system until the system hfts been thoroughly cleaned of abrasive particles which could score the sealing faces and cause leak age. Rotary joints such as those manufac tured by the Johnson Corp. and Perfecting Service Co. are satisfactory with THERMINOL FR. THE EXPANSION TANK... Proper design of the expansion Unk for the THEKMINOL system is quite simple, but is also very important to proper system operation. Characteristic of most organic liquids, THERMINOL expands in volume about 4 percent for every 100F. temperature rise. In heating THERMINOL from room tem perature (70F). to 600F., the fluid in the system expands about 20 percent. Therefore, the expansion tank should be large enough to accommodate about 20 percent of the total volume of the entire system, including the fluid content of the heater, piping and all heat users. The tank should be sized so it is about one quarter full when the system is cooled to 70*F. and three quarters full when the system is at a maximum operating temperature. The expansion tank should be fitted with a sight glass at the "full" range and with a float operated, low-level switch to shut off the burner in case of accidental fluid loss in the system. Place the expansion tank in the circuit on the pump's suction side --above the highest point in the system. The expansion tank also serves as the major venting point of most THEKMINOL sys- HQhS 0766G0 Umm. Tho temperature of the fluid in the expansion tank ia much lower than the bulk fluid temperature in the system. Connect the expansion tank to the system with a small diameter line to avoid thermal recirculation. However, make this line large enough to readily pass the flow caused by expansion and contraction in the system and to permit recirculation of fluid for moisture removal as explained below. Hcoause THKHMINOL Fit fluids are fire resistant, the vent need not be isolated from potential sources of ignition. However, the vent should be out of doors, particularly away from working areas, to eliminate pro longed or repeated contact with the vapors. Care should be taken to prevent the entry of atmospheric moisture into the system as the expansion tank `breaths' air. The vent can be equip)>cd with an air dryer, such as a calcium chloride pot or other desiccant. An alternate procedure would be to blanket the expansion tank with nitrogen. However, if this is done, the THKHMINOL system should be dried thoroughly before the system is sealed with nitrogen. In systems using THKHMINOL above 600F. (or in systems whore accidental high film temperatures may occur in the heater) some provision must be made for venting any hydrogen chloride gas formed in the system and to assure that the system remains dry. Gas or water vapor will not escape readily through the "cold seal" connecting the ex pansion tank to the THKHMINOL system. It is advisable to provide a pipe to feed a small side stream of hot THKHMINOL through the expansion tank as illustrated at right to allow hydrogen chloride and water vapor to flash from the fluid. A small stream of hot THKHMINOL from near the pump discharge should be piped directly into the vented expansion tank, so it enters the tank abovo the highest liquid level. A globe valve should be installed in the line to permit throttling the flow to the desired rate. Kx)>erioncc shows this simple procedure to be extremely effective and completely satisfac tory for removing hydrogen chloride and moisture from the THKHMINOL system. Analysis of samples drawn from systems operating with such a device show that the THKHMINOL fluid maintains minimum acidity and holds moisture at the low levels equivalent to newly manufactured fluid, even after prolonged periods of operation. Provision should be made to prevent moisture from condensing in the vapor space above the liquid level in the expansion tank and in the vent. It is advisable to trace and insulate the expansion tank and the vent so that any moisture accidentally entering the system will remain as a vapor and will not condense. This will prevent corrosion of steol and elimi nate the need for higher cost alloys. The use of non-metallic vent pipe is also recom mended. Polyester piping (available from Fibercast), resin lined steel piping or other non-metallic8 resistant to THKHMINOL vapors and to hydrogen chloride are com mercially available and have been used with great success. NOTES... The expansion tank and vent should be traced and insulated. If steam is not available at the site, hot THERMINOl fluid can be passed through sleet tracing tube. HONS 076601 TESTING FOR LEAKAGE... When a new system has been installed, it is important to test for leaks. Probably the most widely used technique is to check for leaks with ammonia gas.. In this method, the system must be relatively dry and sealed. Ail vent valves should be closed and a tem porary pipe cap or slip blank installed at the expansion tank vent and at other points where there Is no valve. Ammonia gas is fed into the sealed system followed by air under pressures up to ten pounds per square inch. Any leakage areas can be readily detected by the escape of ammonia. Tiny amounts of ammonia vapors can be made visible as white smoke by directing a small stream of hydrogen chloride gas over each joint or fitting, and around each welded connection. Any leakage points can be marked, tightened, and then the system purged free of ammonia with plenty of air. A satisfactory alternate procedure ia Halogen Testing: in this procedure, introduce one pound of Freon F-12 or Freon F-22 for each fifty cubic feet of volume of the system. Carefully introduce air not exceeding 10 psig of pressure. At this sir pressure, the con centration of Freon will be auflicient to give a sensitive test. Attach a halide torch to an acetylene tank and light it. Using the H inch flame as a probe, explore for leaks by passing the end of the flame along seams and joints. If a leak is present, the escaping Freon will be drawn into the acetylene flame turning it green. A large leak will produce a violet color. Leak testing with water is not recommended. Though effective, it creates a problem of introducing a large amount of water into the THEKMINOL system which will be hard to remove. CLEANING THE SYSTEM... After testing for leaks and making any re quired adjustments, the system must be thoroughly cleaned. A new system will contain dirt, weld and mill scale and other foreign particles. Unless re moved, these particles will be carried in sus pension by the circulating THEKMINOL. They may "lodge" in valves, controls, mechancial seals, rotary joints and other mechan ical equipment, causing faulty operation or component failure. When purchasing the heating equipment, the supplier should be requested to clean the equipment as thoroughly as possible using brushes, wiping rags and suitable solvents, such as tri- or perchlorethylene. When completed, fill the system with the operating charge of THEKMINOL. Hring the system up slowly to approximately 200F. At this temperature, the viscosity of THEKMINOL will be very low. The turbu lence from this low viscosity, plus the excel lent solvent action of THEKMINOL fluid, will further clean the system. Circulate the warm THEKMINOL through the system without operating rotary joints (if they are installed in the system). FILTERING... Install a strainer, made of ordinary fine mesh screen backed up with H* screen, in the pump suction of the new system. As foreign material collects, this screen should be peri odically removed and cleaned. When, after several days during which the strainer col lects no material, remove it permanently from the line. The system should be heated and cooled for a minimum of two cycles with the suction screen in place, since the resultant expansion and contraction will loosen mil) I MONS 076602 U l*f:- n .iiifiifiair'Mftiiirir]> fitaftifliMBaiailMMiaMM scale. The screen may be placed in the main stream line, gasketed between two flanges. It is advisable, when operating where solids and contaminants might enter the system, to permanently install a high temperature filter on a by pass line that can be isolated with valves for periodic cleaning. CONTROLS... Controls for heating systems using THERM1NOL should be installed both on the heater itself and on the heat-using units. A wide variety of thermal-operating controls are available, and any reliable standard equip ment is satisfactory. Install heater controls to regulate the firing mechanism in direct proportion to the re quired output. These controls should increase or decrease the heat in-put to maintain the THKHMINOL at the operating temperature required by the heat-demand of the user. Small units may be operated satisfactorily by relatively simple "on-off" or "high-low" con trollers; larger unite will operate more uni formly if equipped with modulating tem perature controls. Install user controls to regulate the flow of the heat transfer fluid in proportion to the heat-consumption of the heat-using equip ment. In a multiple-user system, separate controls should be installed on each consum ing unit, to assure the proper heat-delivery. Safety Controls. In addition to activating controls, the heater muat also be fitted with the proper safety controls to meet the local code requirements. Safely controls should Include: . High temperature cutoff at the heater outlet... to shut off the burner in the event of an excessive temperature rise, b. High tube wall temperature cutoff. A thermocouple sensing element should be installed in contact with the radiant heated surface at the highest temperature point in the healer and protected as much as possible from direct or reflected radiation. Such a controller is usually of the on-off type with the switch wired into the flame safety circuit so that the burner is shut down when the switch opens. Aside from protecting the tube bundle, this safely con trol protects the THERM1NOI-. fluid from overheating. c. Low flow cutoff. This control will shut down the burner should flow rate drop below design rates, or if a loss of flow occurs due to pump mat-function or failure. Equip burners with regular automatic ignition controls and flame failure controls. In wide range firing operations, an over-fire draft con trol will increase the economy of the opera tion. Electric power failure and instrument air failure safety controls are also desirable. In general, the practice of "fail-safe" instru mentation and control is essential: use good quality indicating and recording gauges, with scales calibrated for the particular limits of operation for best reading accuracy. MGNS 076603 OPERATION AND MAINTENANCE OF THE THERMINOL SYSTEM.. The following recommendations are intended only as guides. These suggestions are sup plemental to the equipment manufacturer's recommendations as they relate to the par ticular heater or the user equipment in the installation. The following comments on start-up, shut-down, power failure precau tions, and periodic fluid check-ups apply generally to all sizes and types of equipment. NEW SYSTEM START-UP... For a new installation, or an existing system that has been drained and is idle: 1. Check the safety and control devices. Check the safety and control devices for proper installation, proper range settings for the operation, and actual operation (by manually activating the instrument). For protection of the over-all system and for predictable long fluid life, it is vital that all instruments and controls perform properly. 2. Check for leaks (eee section on leak tasting, page 14.) 3. Pull Vacuum on System. a. The vacuum should be pulled from a point of high elevation in the Bystem; usually at a point just below the expansion tank. Prior to drawing a vacuum, close all valves to the expansion tank; close all valves and vent connections to the atmos phere; close all valves to non-pressure equipment in the system (such vessels may collapse under vacuum) and open all valves in the interconnecting piping of the system. b. Turn on vacuum equipment and evacu ate the entire system (including the "users") to 26-27 inches of mercury vacuum (if possible), or until the absolute pressure of the system has reached the limit of the available vacuum equipment. c. Shut off vacuum equipment. 4. Charge the System with THERMINOL. a. Fill the expansion tank with THERM INOL, and introduce the fluid slowly into the system through the expansion tank valve until the tank is almost empty. Close the valve and again fill the tank. Open the valve allowing the fluid to enter the system and repeat until it no longer flows by gravity. b. Open all valves then start the main circulating pump in accordance with the manufacturer's recommendations. Observe the liquid level in the expansion tank re peating "a" above until the system has been filled. The thermal expansion of THERMINOL must be allowed for in determining the cold charge level. (A 20% expansion can be expected when heated to 600F.--as a guide, the expansion tank should be 70-75% full at the hot operating condition.) c. Circulate the THERMINOL fluid through the system for about 3 to 4 hours to eliminate air pockets and to assure com plete fill of the system. BEFORE FIRING HEATER, BE SURE THAT THERMINOL IS CIRCULATING FREELY. 5. Fire Heater. a. On new installation start-up, or after prolonged shut-down, bring the system up to temperature slowly--about 100F. per hour. This will prevent thermal shock to heater tubes, tube/header joints, refrac tory materials, etc., and allow operators to check the functioning of instruments and controls and become familiar with the equipment's operation. The slow heat-up will also allow any moisture trapped in the system to escape as a vapor. b. Bring system to operating temperature and put "users" on the line. DAILY START-UP ... when equipment has been shut down overnight or for week ends, follow this procedure: 1. Start the circulating pump and check the expansion tank level to see that the HONS 076*0* THKKM1N0L is at the proper cold-start level (H-full). 2. Start burner at the "low" flame setting and continue full circulation until the T1IKHMINOL bulk temj>erature reaches 1B0*F. 3. Turn heater up to full heat. . SHUT-DOWN . . . should be performed as follows to avoid overheating: 1. Shut off burner completely with circulating pump still operating. Continue to run the pump at full capacity for at least 30 minutes to dissipate residual heat in the combustion chamber of the burner. 2. Shut ofT circulating pump after H hour, and switch off all heater electrical controls. COLD WEATHER PRECAUTIONS... When the THKRMINOL system is exposed to low ambient temperatures, it is often most practical to leave the system "idling." Turn the burner to "low" position, and allow the fluid to circulate continuously at about 200F. The unit will then be "at. ready" for imme diate high-tcm)>erafure operation, and the viscosity of the fluid will remain low and workable. IN CASE OP POWER FAILURE... The burner circuit should be shut down by the heater controls. When the power comcR on, run the circulating pump for a few moments to eliminate any vapor pockets that might, have been formed by the fluid remain ing static in the hot combustion chamber. If there is no knocking in the piping system, full-fire may be resumed immediately if the fluid temperature is above 180P. PERIODIC CHECK-UPS... The regular maintenance inspection schedule should include the manufacturer's recom mendations, as well as inspection of the THEHMINOL. Following is a listing of in spection check-points: 1. Lubrication of moving parts. 2. 0|>orating fidelity and accuracy of readings * of safety controls and temperature limit controls. 3. Inspection of heater tubes, burner, refrac tory linings. 4. Periodic inspection of heater surfaces. 5. Inspection of water cooling at the circu lating pump. 6. Repacking of stuffing boxes (according to manufacturer's specifications). 7. Semi-annual or annual sampling and anal ysis of THEHMINOL. Under normal operating conditions, it should not be necessary to check on the condition of the fluid more than once or twice annually. The analysis for fluid condition is a simple test of fluid viscosity. The exact viscosity limits will be affected by the specific mode of operation and esn vary somewhat from sys tem to system. Monsanto should be contacted to determine specific values for the intended operation. Most users do their own testing; some have the viscosity determination made by an outside laboratory. A simple test kit for in-plant testing of THERM1NOL is available at a low cost. Customers can have their fluid tested by Monsanto free of charge. For sampling con tainer and application data form, write to: MONSANTO COMPANY FUNCTIONAL FLUIDS MARKETING ORGANIC CHEMICALS DIVISION ST. LOUIS, MISSOURI 63166 Analysis results will be returned to the cus tomer with complete recommendations for improving or continuing the performance of THEHMINOL heat transfer liquid. I I r i 1* \ ' f lL f u MGNS 07660S 17 TYPICAL fhf^rmJLiihiiri U* SYSTEMS FR THE HEATING PLANT Figure 1 ebovo illustrates a typical basic heating `'plant" for a THCRMINOL FR system. Note the use of instruments to control THERMINOL temperature leaving the heater and by-pass how control to assure adequate flow through the heater regardless of "user*' demands. MGftS 076606 18 KEATING A tlNOLt USER; rra 2 frc=flow recorder controller WITH LOW LIMIT CUTOFF TO BURNER ' : Not* that the ur t*mpr*tur can be controlled by either <> rate of flow ol THERMINOL to the uaer, or (b) temperature of THERMINOL, varied by fuel Input to the heater. HBATING MULTIPLE USERS: I FIQ. % PUMP FRCsFLOW RECORDER CONTROLLER WITH LOW LIMIT CUTOFF TO BURNER Note that each uaer can be controlled at a different temperature by control of the flow of THERMINOL and therefore the rate of flow of heat offered. MGNS 07660? HEATINO OR COOLINO SEVERAL USERS SIMULTANEOUSLY MONS C76608 TEMPERATURE CONTROL BY BLENDINO FLOW RECORDER CONTROLLER WITH LOW LIMIT CUTOFF TO BURNER Single healer system provides varying THERMINOL temperatures 1o users ... finds application for processing heat-sensitive materials. MONS 076609 v. S. V .IS ... v 99 hftrnrtXrtaJL FR ENGINEERING DATA The design and installation of THEKMINOL indirect heating systems requires a heat balance between the user(s) and the heater. The amount of heat which will be absorbed by the user in a given time depends upon the over-all heat transfer coefficient, the heat transfer area of the user, and the mean temperature difference between THERMINOL and the process or area being heated. In processing most organic chemicals, oils, food cooking --the rate of heat transfer is usually dictated by the process and not by the heating medium. However, in designing a system--it is important to know the heat transfer coefficient of THEKMINOL. This is affected by a number of variables, probably the most important of which is flow rate. The following curves provide engineering data on THEKMINOL heat transfer coefficients as a function of flow rate... and pressure drop as a function of flow rate ... in various common sizes of pipes and tubes. NOTE: The following charts depicting heat transfer coefficients and pressure drops for various sizes of pipes and tubes are available In full page reproduction for greater accuracy in Inter pretation. Write to: Monsanto Company Organic Chemicals Div. 800 N. Lindbergh Blvd. St. Louis. Mo. 63166 MONS 076610 0 HEAT TRANSFER COEFFICIENT BTU/HIL, FT.*. F.--INTERNAL THERMINOL FR-1 HEAT TRANSFER COEFFICIENTS INSIDE SCHEDULE 40 PIPE Id to >0 40 SO 70 100 too 900 too 1000 2000 4000 0000 FLOW--S.P.M. HEAT TRANSFER COEFFICIENTS INSIDE TUBES MGNS 076611 HEAT TRANSFER COEFFICIENT BTU/HR^ FT.*, *F.--INTERNAL : :<ut. !iaaaifcr8~ mt THERMINOL FR-2 HEAT TRANSFER COEFFICIENTS INSIDE SCHEDULE 40 PIPE HBAT TRANSFER COEFFICIENTS INSIDE TUBES MCKS G 76612 0 THERMINOL FR-3 HIAT TRANSFER COEFFICIENTS INSIDE SCHEDULE 40 PIPE HEAT TRANSFER COEFFICIENTS INSIDE TUBES HONS 076613 -sfSrfeSiatwiij&a; THERMINOL FR-1 PRESSURE DROP IN SCHEDULE SO PIPE PRESSURE OROP-PS.U PER 100 FEET o-> i 1 t.6 t 9 49 7 10 IS SO FLOW--G.P.M. 80 40 60 80 1Q0 MONS 07661* c Cm THERMINOL FR-2 PRIMURI DROP IN SCHIDULR 40 PIP* PRESSURE DROR-P.SJ. PER * 0 FEET MONS 076615 27 THERMINOL FR-3 PRESSURE DROP IN SCHEDULE 40 PIPE PRESSURE DROP--P.S.I. PER 100 FEET i)) I 1.6 I a 4 6 ? 10 IS 90 FLOW--G>.M. ao 40 60 80 100 HQhS 076616 JH rtmirmt --iffurrtirtN RESISTANCE OF VALVES AND FITTINOS TO FLOW OF FLUIDS A simple way to account for the resistance offered to flow by valves and fittings is to add to the length of pipe In the line a length which will give a pressure drop equal to that which occurs in the valves and fittings In the line. Example: The dolled line shows that 3000 the resistance of a 6-inch Standard Elbow is equivalent to approximately 16 feet of k 2000 6-Inch Standard Steel Pipe. 300 200 90 H "l 20 p [Sudden EnlargementI----- dID-'A Ordinary Entrance 2< > - -4 ISudden Contraction V V-- d/D->4 y--d/D-x '--<>1-'/. H Long Sweep Elbow or--J run of Standard Tee t Lo HONS 076617 PRESSURE DROP AND HEAT TRANSFER RATE FOR HEAT EXCHANGERS - .-x^-.x^rar avcys.-v.^Bwu-. .. .. =.... v.; ;-, yV'y': . ' y Pam *.' ' ; : '1 PROCEDURE TO OBTAIN PRESSURE DROP SHELL SIDE OF TUBULAR EXCHANGERS WITH THERMINOL FR-2 1. Enter Chari No. i with GPM & average flow* Ing temperature--read avaraga ahall alda valocity. E. Multiply avaraga ahall alda valocity with baffle correction (Be--Chart No. 9) to obtain cor rected valocity. 9. Enter Chart No. 9 with corrected velocity-- read uncorrected preeaure drop. 4. Correct preeaure drop-9 above-tor temper ature* tube diameter and tube length. Example: THERMINOL FR-2 400F. 400 6PM 80" Shell W Tubea on 19/ir Bafllea 12" Pitch Tubea 14' Long 1. Chart No. 1 400 GPM--20" ahall--2.7 ft/eec. avaraga velocity. 2. Chart No. I 12" Baffle Pitch--0.9 correction 2.7 ft/eec. x 0.4 - 1.62 ft/aec. corrected ve locity 3.1.42 ft/eec. In 20" Shell -4.1 P$l uncorrected preeaure drop. 4. Correct for temperature, tube size and length. Preeaure Drop -- 4.1 x 1.2 x 1.0 x 1.93 * 9.44 Ane. Part II PROCEDURE TO OBTAIN HEAT TRANSFER RATE SHELL SIDE OF TUBULAR EXCHAN6ER8 WITH THERMINOL FR-t 1. Enter Chert No. 1 with 6PM at average flow ing temperature-read avaraga thell alda velocity. 2. Multiply average shell aide velocity with baffle correction (Bet, Chart No. 2) to obtain cor rected velocity. 9. Enter Chart No. 2 with corrected velocityreed uncorrected h. 4. Correct h--(9 above)-for temperature and tube diameter. Example: THERMINOL FR-2 900s 20" Shell TonlX' Bafllea 10" Pitch 950 6PM 1. Chart No. 1 9S0 6PM--20" Shell -2.35 ft/aec. average velocity. 2. Chart No. 2 10" Baffle Pilch--0.876 correction 2.35 ft./eec. x 0.875 --2.04 ft/aec. corrected velocity 9. 2.04 ft./aec. Chart No. 2 - 225 uncorrected h. 4. Correct h for temperature and tuba diameter. 225 x 0.61 x 0.44" - 121 Ane. Part III NOTES: a. Tubes to be on triangular pitch K" on 'Mr"; H" on '*'\ 1" on IK** b. All bafflee cut 1 row of tubes poet horizontal cantarline. e. Charts have base condition--on 'ft*"; Bafllea at 6" pitch. THERMINOL FR-2 at 660F. Data on ahall side preeaure drop end coefficients Courtesy of Struthere Welte Corporetlon. t MOMS 076618 ) &> I 80 +mt MONS 076619 CHART NO. 1 AVKRAOI SHLL SIDS VELOCITY > < > < G.P.M. A V B IA 6 E FLOWING TtJUPERATURt9 t)> MONS 076620 32 mr i A I i CHART No. 2 HEAT TRANSFER SHELL SIDE BAFFLE PITCH--INCHES ED SHELL SIDE VSLOCITY-FT./SEC. TEMPERATURE CORRECTION Tci MONS 076621 33 CHART No. 9 ,T,srrg:.,^:grggg>rr;v:: jr.r ~:vj: :\vrr^.':y~::.' * . - \*. PRESSURE DROP SHELL. SIDS CORRECTION FACTOR HONS 076622 #I r '''l'.a.-. v.^v., *. c.._ . .. ,;., '.*>.. ... .;v VISCOSITY CONVERSION CHART % (Converting kinematic and Saybolt Vlecoelty to Absolute Viscosity) i-10.000 i.MO 4: |- t.ooo GRAVITY, IN OEGREES A.P.I. .1,000 -100 >000 - 800 - 400 - 000 I- 100 :F8 i u 1-4 14IJ- w-3 o 1.0 10 ^*0 > . 2 ^ 80 U) : f. U 0.8 - k E : " oj : k" $ i* e.r - -io 0.8 4 0.0 - MCNS 076623 ENGINEERING CONVERSION FACTORS 6. *>.*.-i T^"* ''T4 * .'I*if*M* r^**r^**~>"' `..litfrjrh.j ,,-.* *v i. TO OBTAIN i 31 ATMOSPHERES ATMOSPHERES ATMOSPHERES ATMOSPHERES ATMOSPHERES ATMOSPHERES British thermal unite British thermal unfts British thermal units British thermal units British thermal units British thermal units British thermal units Btu/cu. ft. Btu/hr. 8tu/hr, sq. ft. Btu/(hr. sq. ft. 0 F.) Btu/(hr. sq. ft. 0 F.) Btu/(hr. sq. ft. F.) Btu/|hr. sq. ft. F.) 6tu/(hr. sq. ft. F.) (Btu/hr. sq. ft.)/( F./in.) (Btu/hr. sq. ft.)/( F./in*) (Btu/hr. sq. ft.)/( F./ft.) (Btu/hr. iq. ft.)/(0 F./ft.) (Btu/hr. sq. ft.)/( F./ft.) Btu/min. Btu/min. Btu/min. Btu/lb. Bfu/lb. mol. Btu/lb. 0 F. 14.70 2116.8 760 29.92 33.90 1.033 x 10* 778.2 107.6 1055 0.2520 3.930 x I0-* 2.930 x 10-' 0.5556 8.90 3.927 x I0-* 2.712 4.882 1.0 1.356 x 10-* 5.66 x 10-4 2.035 x 10-' 12.4 3.445 x 10-' 4.13 x 10-' 0.0173 14.88 12.97 0.02358 0.01758 0.556 0.556 1.0 Ib./sq. in. Ib./sq. ft. mm. Hg. in. Hg. ft. of water Vg./sq. meter ft. lb. fcg.-mefers joules kg.-cal. hp. hr. Iiw. hr. P.C.U.* kg.-cal./cu. meter hp. kg.-cal./hr. sq. meter kg,-cal./(hr, sq. meter 0 C.) t P.C.ll.*/(hr. sq. ft. 0 C.) gram-eal./see. cm.' 0 C. watts/cm.' 0 C. watts/sq. in. F. (kg.-cal./hr. sq. meter)/( C./cm.) (gram-cat./sec. cm.')/( C./cm.) (gram-eal./sac. cm.*)/( C./cm.) (wtti/cm.*)/( C./cm.) (gram-cal./hr. cm.')/)0 C./em.) ft. Ib./sec. hp. kw. gram-cal./gram gram-cal./gram mol. gram-cal./gram C. *feund-C*nfierd Unit MONS 076624 #> . | MULTIPLY Bfu/tec. Btu/sec. Btu/sec. Btu/sec. Btu/sq. ft. Btu/sq. ft. CALORIES CENTIMETERS CENTIMETERS em. Hg. cm. H9. cm. Hg. cm. Hg. cm. Hg. cm. Hg. cm./0 C. cm./tec. cm./see. cm./sec. em./iac. cm./tec. CENTIPOISES CENTIPOISES CENTIPOISES CENTIPOISES cubic centimeters cubic centimeters cubic centimeters cm.*/sec. cm.'/sec. cm.*/sec. cnv'/iec. cm.*/grem cm.Vgrem mol. CUBIC FEET CUBIC FEET ENGINEERING CONVERSION FACTORS JTaisM& Y 778.2 1,4147 1.0549 107.6 0.2712 2.712 See gram-eel. 0.3937 0.0328 0.01316 0.1934 27.85 136.0 5.353 0.4461 0.2 IB7 1.969 0.03281 0.036 0.60 0.02237 0.01 2.42 6.72 103.60 0.06102 3.531 > 102.642 x I0-* 2.119 x 100.0864 0.01585 3.6 0.01602 0.01602 0.02832 7.481 n.i>Av y TO OBTAIN ft. Ib./sec. hp. kw. kg.-meter/sec. gram-cal./cm.* kg.-cal./sq. meter in. . etm. Ib./sq. in. Ib./sq. ft. kg./sq. meter in. of weter ft. of water in./0 F. ft./min. ft./sec. km. /hr. meters/mSn. mph poises lb./. hr. Ib./ft. sec. kg./meter hr. cu. in. cu. ft. gel. cu. ft./mtn. cu. meter/dey gal./min. liter/hr. cu. ft./lb. cu. ft./lb. mol. cu. meters gal. aj__ HONS 076625 A' ) ENGINEERING CONVERSION FACTORS multiply IY CUBIC FEET CUBIC FEET cu. ft. ga$ |60 F. at 1 atm) cu. ft./lb. cu. ft./mln. cu. ft./mln. cu. ft./tac. cu. ft./tac. tq. ft. CUBIC INCHES CUBIC INCHES CUBIC INCHES CUBIC INCHES CUBIC METERS CUBIC METERS cu. matart/day dagraat/tac. dagraat/tac. ERGS FEET FEET ft. of wafar ft. of watar ft. of watar ft. of watar ft. of watar ft. of watar ft./mln. ft./mln. ft./mln. ft./mln. ft./sac. ft./tac. ft./iac. FOOT POUNDS FOOT POUNDS FOOT POUNDS FOOT POUNDS 28.32 62.43 2.636 i 10- 62.43 472.0 0.1247 448.6 0.0305 16.39 5.717 x I0-* 0.01639 4.329 > 10-' 35.31 264.2 11.57 2.776 I0-* 0.1667 1.0 10-' 30.48 0.3048 0.0295 2.242 0.8626 304.8 62.43 0.4335 0.508 0.01667 0.01829 0.01136 1.097 16.29 0.6818 1.285 i I0-* 3.239 10" 3.766 > 10-' 5.05 i 10 TO OBTAIN IHart lb. of witir lb. mol. cm.'/gram cm.'/iac. gal./tac. gal./mln. lifars/sac. cm.1 cm.* cu. ft. Ilfon 90I. cu. ft. gal. cm.*/wc. rav./iac. rpm joule* cm. mafart atm. cm. Hg. In. Hg. kg./sq. matar fb./tq. ft. lb. /sq. In. cm./sac. ft./tac. km. /hr. mph km./hr. matari/min. mph Btu kg.-cal. kw. hr. hp. hr. +Poutid-Contlgrd* Unll HONS 076626 * 6 "3T1 1 ENGINEERING CONVERSION FACTORS MULTIPLY IY ft. Ib./mln. ft. Ib./mln. ft. Ib./tac. ft. Ib./tOC. ft. Ib./stc. ft. lb./MC. GALLONS (tmporiol) .L (U S.) |US) .L (U.S.) ,.L (U.S.) 9*l./hr. gal./min. gal./mln. gal./mln. gal./mln. of water GRAMS GRAMS gram molt gai gram-eel. grenvcel./grem grem-eal./grem mol. gram-cet./gram C. grem-eal./em.* (grem-cel./cm.,)/cm. grem-cel./(tec. cm.* C.) (grenveal./tec. em.'l/l0 C./cm.) gram-cm. gram-cm. gram-cm. gram-cm. gramt/cm. gramt/cm.* gramt/cm.* grami/cm.* gramt/cm.* gramt/cm.1 gramt/cm.* 3.03 I0-* 2.26 x I0-* 0.0771 1.8II x I0-' 0.01943 1.3SO i I0-* 1.201 231 0.1337 370S 3.78$ 3.71 x I0-* 2.228 i I0-* 0.227 0.06309 500.8 980.7 2.20S < IO-> 2.24 x 10* 3.9*8 i I0-* 1.8 1.8 1.0 3.687 1.452 7.373 > 10* 2.903 x 10* 9.294 i 10- 980.* 7.233 i 10- 2.342 i 10'* S.60 x I0-* 1.0 *2.43 0.07355 10 0.394 0.03281 TO OITAIN hp. Iiw. Btu/min. hp. kg.-cal./mln. kw. ,.l. (U.S.J cu. in. eu. ft. cm.* Rtan cu. ft./tac. cu. ft./tac. cu. matars/hr. Iifart/tac. Ib./hr. of w.I.r dynet ib. cm.* gat (0 C. and 760 mm.) Btu Bfu/lb. Btu/lb. mol. Bfu/lb. F. Btu/tq. ft. (Btu/tq. ft.)/ln. Btu/(hr. tq. ft. 0 F.) (Bfu/br. .9. ft.)/| F./ln.) Btu argt ft. lb. kg.-cel. Ib./in. tpacific gravity at 4 C. Ib./cu. ft. cm. Hg. kg./tq. matar In. of water ft. of w.t.r tv - r*", E-- ' I I MGNS 07662? 39 ENGINEERING CONVERSION FACTORS Miti!:."',.!?.,' <_.. ',.... L'l.0 . 1 iktini MULTIFLY IY ,JL SkTSW^j.'V TO OITAIN grams/cm.1 grams/cm.' grams/cm.* HORSEPOWER HORSEPOWER HORSEPOWER HORSEPOWER HORSEPOWER hp. (boilar) hp. (boUar) hp. hr. hp. hr. hp. hr. hp. hr. hp. hr. hp. hr. hp, hr. INCHES In. Hg. In. Hg. In. Hg. In. Hg. In. Hg. in. of watar In. of watar In. of watar in. of watar In. of watar In. of watar In./0 F. KILOGRAMS KILOGRAMS KILOGRAMS KILOGRAMS lig.-matan kg.nmotar* kg.-matan 9.678 i 10- 0.01422 2.046 42.41 3.3 > 10SSO 10.7 0.7457 3.3479 > 10* 9.604 2.S4S 10* 1.98 x 10* 2.664 10* 641.2 2.737 i 10* 0.7457 1.414 i 10* 2.54 0.03342 1.133 0.4912 70.73 345.3 2.456 > I0-* 0,07355 0.1869 25.40 0.03613 5.202 4.672 9.607 10* 70.93 2.205 1.102 i 10-* 9.302 10 - 7.233 2.344 10- 2.724 I0-* atm. Ib./iq. In. Ib./iq. ft. Btu/min. ft. Ib./mln. ft. lb./we. kg.-cal./min. kw. Btu/hr. kw. Btu ft. lb. jeulai kg.>cal. kg.-mafar* kw. hr. P.C.U.* cm. atm. ft. of watar Ib./sq, in. Ib./sq. ft. kg./tq. nriatar atm. ln. Hg. cm. Hg. kg./sq. matar Ib./iq. in. Ib./sq. ft, cm./ C. dynas poundak lb. ton* (short) Btu ft. lb. kg.-cal. kw. hr. *Fwiirf>CMtl9rd UnH HONS 076628 MULTIPLY kg.-mcf#ri kg./cu. motor kg./cu. motor kg./motor kg./tq. motor kg./iq. motor kg./sq. motor kg./tq. motor kg./q. motor kg./tq. motor KILOMETERS KILOMETERS km./hr. km./hr. km./hr. km./hr. KILOWAHS KILOWATTS KILOWATTS KILOWATTS KILOWAnS KILOWAnS kw. hr. kw. hr. kw. hr. kw. hr. kw. hr. kw. hr. LITERS LITERS LITERS LITERS LITERS lifori/grom mol. Iifer/hr. IStor/kg. litort/min. lilort/min. . w ................. .................. ENGINEERING CONVERSION FACTORS IY 5.165 x 10 * 1.0 io-< 0.06243 0.6720 9.678 i I0-* 7.355 x I0-* 3.281 > I0 > 2.896 x 10-' 0.2048 1.422 i 10-' 3.281 x 10* 0.6214 27.78 84.68 0.9113 16.67 56.92 4.425 x 10* 737.6 1.341 14.34 1 10' 3.413 i 10* 2.6SS > 10* 1.341 3.6 x 10* 860.5 1.895 > 10* 1 X 10' 0.0353 61.02 0.2642 1.057 16.02 0.2778 0.01602 6.0 x 10* 5.885 x 10 * TO OBTAIN P.C.U.* grom/cm.' Ib./cu. ft. Ib./ft. otm. cm. Hg. ft. of water in. Hg. Ib./tq. ft. Ib./iq. In. . ml. cm./ioe. ft./min. ft./toc. motort/mln. Bfg/mln. ft. Ib./min. ft. Ib./soc. hp. kg.-eol./mln. wotts 8tu ft. n>. hp. hr. {oulcs kg.-col. P.C.U.* cm.' cu. ft. cu. In. 9al. (U.S.) qt.(llq.| cu. ft./lb. mol. cm.yee. cu. ft./lb. cm.'/hr. cu. ft/soc. HONS 076629 !Ptnd-CiMI|rWt Unit ENGINEERING CONVERSION FACTORS MULTIPLY Iftart/min. Mart/mln. fffart/sac. cm.* METERS METERS malar*/ C. mtfr/min. malart/mln. matars/min. malart/mln. matart/iac. maltf*/iac. malari/tac. OUNCES OUNCES OUNCES (fluid) OUNCES (fluid) oi./sq. in. POISES POUNDS POUNDS POUNDS lb. mob gat lb. of wafar lb. of wa+ar lb. of watar/hr. lb. of watar/hr. Ib./ct>. ft. Ib./cu. ft. Ib./ro. In. lb./ft. fc./. hr. Ib./ft. hr. Ib./9al. Ib./ln. Ib./q. ft. lb./(. ft. IY IS.ISI 4.403 x 10-' 32.8 3.211 39.37 1.124 1.667 0.06466 0.06 0.03728 176.1 3.6 2.237 28.36 0.0625 1.805 0.02767 (.732 i 4.448 x 10* 453.6 32.17 379.4 0.01602 0.1178 2.868 x 10- 1.777 I0-* 0.01602 16.02 27.68 1.488 4.13 > I0-* 0.413 0.1178 178.6 0.01602 4.882 TO OBTAIN gal/hr. gal./tae. cu. ft./iac. iq. ft. it. In. ft./ F. em./tac. ft./iac. km./hr. mph ft./mln. km./hr. mph grams lb. cu. in. litart in. of wafar gram/cm. tac. dynat grams poundab eu. ft. gat (60 P. at 1 atm.) cu. ft. gal. cu. ft./mln. gal./mln. gramt/cm.* kg./cu. malar grami/cm.1 kg./matar gramt/cm. tac. cantipoiias gramt/cm.1 grami/cm. ft. of watar kg./tq. malar I A * i >1111111 i 11 | II i| 1 11 ~ 1 1 |l " l| m~Tfl TTT1 n1 fcrI*TO^ftVfhrliK<rtfl*,','- illNfTrtf&ifii^ ^^?;F*vrJgMrF^W4. * > ..- ' ?" TT~'? *,, RONS 076630 t> ENGINEERING CONVERSION FACTORS MULTIPLY Y Ib./tq. ft. Ib./tq. In. N>./*q. In. Ib./tq. in. Ib./tq. In. Ib./tq. In. Ib./tq. In. REFRIGERATION--STD. TON SQUARE CENTIMETERS SQUARE CENTIMETERS SQUARE FEET SQUARE FEET SQUARE FEET SQUARE INCHES SQUARE INCHES SQUARE INCHES SQUARE KILOMETERS SQUARE KILOMETERS SQUARE METERS temperature C. 273 temperature C. 17.8 temperature F. 460 temperature F. --32 TONS (long) TONS (long) ton* (metric) font (metrle) tent (short) font (thert) tons (short)/sq. ft. tons jshort)/tq. ft. tom (shortj/tq. In. tom (thorfj/tq. in. tom of refrigeration WATTS WATTS WATTS 6.944 x I0' 0.06804 2.307 2.036 61.7 703.1 144 200 1.076 x I0-" 0.1660 929 144 0.0929 6.452 6.944 x 10-' 6.452 x I0"J 1.076 x 10' 0.3661 10.76 1.0 1.8 t.0 0.5556 1.016 x 10" 2.24 x 10" 1 x 10* 2.205 x 10" 907.2 2 x 10" 9.765 x 10* 13.89 1.406 x 10* 2 x 10" Soo refrigeration 0.05692 I x 10' 44.26 TO OBTAIN Ib./tq. in. etm. ft. of water in. Hg. mm. Hg. kg./sq. meter lb./*q. ft. Btu/mln. sq. ft. tq. In. tq. cm. tq. in. tq. meters cm.* sq. ft. sq. meters tq. ft. sq. mi. sq. ft. abs. temp. 0 K. temp. F. abs. temp. R. temp. C. kg. lb. kg. fc. Vg. lb. kg./sq. meter Ib./sq. in. kg./sq. meter Ib./sq. in. Btu/min. ergs/tec. ft. Ib./min. HONS 076631 ENGINEERING CONVERSION FACTORS MUlTIfLY WATTS WATTS WATTS WATTS WATT HOURS WATT HOURS WATT HOURS WATT HOURS WATT HOURS WEEK WEEK WEEK YEARS (common) IY 0.7376 1.341 i 10 * 0.0H34 1.0 10 -' 3.413 2.655 i 10* 1.341 i I0-* 0.9605 367.1 169 1.009 x 10* 6.049 i 10* 1.76 i 10' ................................... TO OBTAIN ft. Ib./sec. hp. kg.-cal./mln. kw. Btu H. lb. hp. hr. Itg.-cal. kg.-matar hr. min. tac. hr. t .a STEEL PIPE DIMENSIONS--OAPAOITIE0 AND WEIOHTS* NomtMt Ortttot WoH O.Hn.Pto. toon., ScMOala (Mehto. No. NM, to. K owe 40 H 0.375 40 toM CJ40 40 l.0 40 1 1.3)9 40 IU tat* 40 m I.M0 40 t nn 40 2H 7.079 40 1 3.300 40 3V5 im 40 4 UN 40 1 IHl 40 .m 40 1 I4 40 M ion 40 If 13.79 40 .000 til .100 .113 .It) .100 .143 .134 JU no M JS7 ISO .too J93 400 at*4 M A. $. A. Stiltfw* tn.ll. Into Atom.. to. .944 .40) .on 474 1.040 I.NO 1410 7.407 1400 3000 3.341 4.020 3 047 0.063 7001 10.070 11030 Crotlmttoful MM natal, 10. to. Into* Mtttoful IIM, to. n. .171 .107 .730 4)) .404 MO .701 1.079 1.704 3.321 2400 317) 4.304 9.304 l.C 11.00 13.77 .00077 .0013) .00311 .00371 .40000 .01040 .01414 .03330 .03333 .03130 .10070 40040 .1300 .toot .3474 3475 .777) Cfcnn4ww, II.. Of turfaca ao.kaorft.oi ton|tk Oatotoo tattoo .141 .0034 .177 .1703 in .1330 .373 .2190 J44 .3743 .401 442 400 .427 .337 .343 .733 .347 .017 004 1.047 IN 1.170 1039 1.430 1.32? 1.734 1.500 7.390 3.000 3.014 3.970 33)0 3.13 CMHlIr il 1 It. p*> tac. nJedti U.. 19 pt> to. 1*1 0M water n4. .37) 141 5 .306 200.0 045 473.5 1.035 1375 7309 1.345.0 4.S7 2,m. 3.34 3.170.0 10.43 3.375.0 1407 7.430 0 73 00 11,500.0 3000 IS.4M.0 301 13.000.0 32.3 31.1900 000 45,000.0 1397 77,150.0 243.0 173.000.0 3400 174,500.0 Wafftit afaba Ml ft. 19. .97 JS 111 190 2.24 377 3.99 5.99 750 0.11 101 14.7 100 209 403 53.9 MOhS C76632 --thermJUrioIL TYPICAL. APPLICATIONS FOR LIQUID HEATING SYSTEMS... Indirect liquid heating with Til HUM INOI. Fit systems is recommended wherever lowpressure, high-temperature proc essing-requiring safe, uniform dolivery of heal--is needed. Here are a few typical applications. . I .* .r. ^S # CHEMICAL PROCESSING ... especially where flammable materials are handled. VARNISHES AND RESINS PROCESSING ... where a single "circuit" with multiple users and varying temperatures is desirable. PLASTICS AND RUBBER MOLDING ... where uniform heating, rapid temperature flux, and pin-point control is essential. BITUMINOUS MATERIALS HEATING ... for maximum safety where explosive gases and volatile fumes occur. FOOD PROCESSING ... for controlled, quality "cooking" of potato chips, pre-cooked soups, other foodstuffs. MATERIALS CONVERSION ... to heat corrugating rolls, crimping presses, calenders. METALS TREATING OVENS ... for heat-treating metals such as titanium and vanadium; for "seasoning" weldments, castings and forgings. MALT COOKING AND LIQUID DISTILLATION ... for efficient indirect heating of distillation equipment. HONS 076633 .1 fhorm Nm ill* FR SAFETY OF HANDLING On the basis of animal toxicity studies, THEKMINOL FR may be considered only slightly toxic from the standpoint of acci dental massive skin exposure or accidental ingestion. Similarly, single exposures to high concentrations of vapors (when heated suffi ciently to volatilise) or high concentrations of decomposition products (if the fluid is accidentally discharged into the fire chamber) are not serious hazards because the irritating character of such concentrations preclude vol untary exposure. Repeated or prolonged skin exposure should be avoided since THEKMINOL FK acts as a solvent for fata and oils of the skin. Re moval of these natural, protective barriers can lead to drying and chapping such as occurs with exposures to paint thinnere. More important, THEKMINOL FR may be ab sorbed if it is allowed to remain on the unbroken ekin. For these reasons, we recom mend that the skin be washed with soap and water if there is contact. A skin burn resulting from accidental contact with hot fluid should be treated in the normal manner for any thermal burn due to hot oils. Because of its low vapor pressure, there is no significant vapor inhalation hazard when THERM1NOL FK is at room temperature. For example, there is no vapor exposure prob lem while transferring the fluid from its ship ping container to the heat transfer system. On the other hand, the vapors emitted by THEKMINOL FK heated to elevated tem peratures are injurious on prolonged exposure. It is indicated that the "threshold limit value" or atmospheric vapor concentration which cannot be safely exceeded (on a daily basis) is 0.6--1.0 milligrams of THEKMINOL FR vapor per cubic meter of air in the workroom. In heat transfer installations, the fluid must be used in a closed system free from leaks with the expansion tank vented to the out doors. Accordingly, there should be little or no opportunity for workers to come in con tact with vapors. MONS 076634 I 1 HONS 076635 1 t HONS 076636