Document xddBaqbdOojvbmMNN5X1mnjm0

1954 Guide Pipe Insulation 639 CHAPTER 28 638 example. In using the chart, start with the scale at the left bottom margin representing the given number of hours of operation per year; then proceed vertically to the line representing the given value of heat'; . thence horizontally to the right, to the line representing the given tem perature difference; thence vertically to the line representing the con ductivity of the given material; thence horizontally'to the left, to the line representing the given discount on that material; thence vertically to the curve representing the required percent return on the investment; thence horizontally to the right, to the curve representing the given pipe size; thence vertically to the scale at the top right margin where the eco nomical thickness may be read off directly. A rapid method for determining the economical thickness of insulation by use of tables has been published.2 UNDERGROUND PIPE INSULATION Underground steam distribution lines are carried in protective struc tures of various types, sizes and shapes (see Chapter 29). Detailed data Table 11. Thickness of Loose Insulation fob Use as Fill in -Underground Conduit Systems Steam Pressure . ^Psio Temperature Fahrenheit Minimum Thickness op Insulation in Inches Steam Lines Return Lines Hot Water, or 0 to 25 212 to 267 25 to 125 267 to 352 Above 125, or superheat 352 to 500 Pipes Less than 4 In. m 2 m. Pipes 4 In. Pipes Larger Pipes Less to 10 In. than 12 In.- than 4 In. 2 m iK 2A 3 IK 3 3K IK Pipes 4 In. and Larger m lA iA Minimum Distance Between Steam Return i IK IK on commonly used forms of tunnels and conduit systems, have been pub lished by the National District Heating Association.'- Pipes in tunnels are covered with sectional insulation to provide maxi mum thermal efficiency, and are also finished with good mechanical pro tection in the form of metal or waterproofing membrane outer jackets. In some instances, where actual submersion of hot lines may occur, it has been found good practice to firmly secure the covering with corrosion resistant wire, then sew on a wire-inserted asbestos fabric jacket with .wire. This jacket is porous. The principle of withstanding submersion is that water may enter as water, then actually boil at the pipe surfaces and escape as steam without rupturing the insulation or jacket. Conduit systems are in more general use than tunnels. Pipes carried in conduits may be insulated with sectional. insulation; however, the more usual practice is to fill the entire section of the conduit around the pipes with high quality, loose insulating material. The insulation must be kept dry at all times, and for this purpose effective waterproofing membranes enclose the insulation. A drainage system is also provided to divert water which may tend to enter the conduit. The economical thickness of insulation for underground work is difficult to determine accurately due to the many variables which have to be considered. As a result of theories4 previously developed, together with other experimental data which have been presented, the usual endeavor