Document xO4ZzMKnmGxE3EzDb9r90vBJ
EDC UNIT SOP MANUAL Section: Reactors
Page 1 of 1
Description: Normal Plant Vent Operation
EFFECTIVE DATE:. Revision #:
_______
APPROVED BY:
THE NORMAL FLOW OF THE REACTOR VENT STREAMS IS TO THE
INCINERATORS AT WTU. WTU VALVES OUR VENTS TO ONE OR MORE
I NCINERATORS.
THE VENTS MUST GO TO THE INCINERATOR DURING STARTUP AND
SHUT DOWNS. THIS IS REQUIRED BY OUR ENVIRONMENTAL
REGULATIONS. BUT IT IS DIFFICULT BECAUSE EXCESS ETHYLENE
CAUSES THE INCINERATOR TO HEAT UP AND IT MAY SHUT DOWN.
CLOSE COMMUNICATION WITH THE OPERATORS AT WTU IS REQUIRED.
IF THE VENTS TRIP - THEY SHOULD BE RESET AS SOON AS POSSIBLE.
THE RECOVERY STILL VENTS ARE TIED INTO THE SAME LINE
WITH #1 PLANT VENT. THE #1 AND #2 PLANT VENTS TIE TOGETHER AT
THE SOUTH END OF #2 PLANT. EACH PLANT CAN BE INDEPENDENTLY
ROUTED TO EITHER THE INCINERATOR AND SCRUBBER.
AT THE SOUTH END OF #2 PLANT, AFTER THE TIE IN BETWEEN
#1 AND #2, THERE IS A DRAIN OFF THE BOTTOM OF THE LINE THAT
GOES INTO A KNOCK OUT POT. THIS POT PREVENTS LIQUID FROM
GOING TO INCINERATORS. YOU SHOULD CHECK THIS POT ON YOUR
ROUNDS AND EMPTY IT AS REQUIRED. INVESTIGATE AND REPORT TO
SUPERVISION IF THE KNOCK OUT POT FILLS RAPIDLY WITH LIQUID.
A RATE CUT MAY BE REQUIRED IF EXCHANGERS ARE TOO FOULED TO
WORK EFFICIENTLY.
THE SCRUBBERS ARE SET UP SUCH THAT WHEN THE VENTS ARE
TRIPPED, A WATER VALVE AUTOMATICALLY OPENS TO THE SCRUBBER.
WHEN THE VENTS ARE SWITCHED BACK TO THE INCINERATOR, THIS
VALVE SHUTS.
THE EFFLUENT FROM THE SCRUBBERS GOES TO THE LIFT STATION
SUMP. IN ORDER NOT TO OVERLOAD THE STEAM STRIPPER, IT WAS
DECIDED THAT NO WATER FLOW WOULD GO TO THE SCRUBBERS WHILE
THE VENTS IN THE INCINERATOR.
IN ORDER TO RESTORE VENTS TO THE INCINERATOR, THE EDC/
VDCM OPERATOR MUST HAVE PERMISSION FROM THE INCINERATOR
OPERATOR. THE VENT SWITCHES WILL BE RESET BY WTU ONCE THE
VENTS CAN BE PUT BACK IN. THE EDC TANK FARM VENTS TIE INTO
THE #1 PLANT VENT LINE AND GO TO THE INCINERATOR OR SCRUBBER
ALSO.
ON DECEMBER 19, 1990 WE HAD A ORC MEETING TO ALLOW US TO
TAKE THE VENT TRIP FEATURE OUT OF THE REACTOR SHUTDOWN
SYSTEM. THIS MEANS THAT WHEN WE HAVE A MOD I CON TRIP ON EITHER
REACTOR THE VENTS WILL CONTINUE TO THE INCINERATOR UNLESS THE
OPERATOR MANUALLY TRIPS THEM TO THE SCRUBBER. REMEMBER, YOU
SHOULD ALWAYS LEAVE THE VENTS IN THE INCINERATOR UNLESS
INSTRUCTED TO TAKE THEM OUT BY WTU.
, CONFIDENTIAL:
Subject to Protective order
of 14th Judicial District Court
No. 91-11 4*>
SL 010471