pyrocLor TRANSFORMER COOLANT BY monsanio pyrocLor FIRE-RESISTANT |fl . transformer coolant by monsanto The information contained in this publication is, to our best knowledge, accurate: but all recommendations or suggestions are made without guarantee, since the con* ditions of use are beyond our control. Monsanto Company, its subsidiaries, associates and affiliates disclaim any liability for loss or damage incurred in connection with the use of the following material. Moreover, nothing contained herein is to be construed as a recommendation to use any product in conflict with any patent. The information, recommendations and suggestions made herein are offered in the light of prevailing legislation and on the basis of present scientific information (1972) avail able to Monsanto. Monsanto Chemicals Limited 10-18 Victoria Street London SWIH ONQ Telephone: 01-222 5678 Telex: 916093 Monsanto Europe S.A. Place Madou, 1 B-1030. Brussels. Belgium Telephone: (02) 19.11.01 Telex: 22110 21986 HONS 0 7 * 9 8 8 1. INTRODUCTION--HISTORY OF PYROCLOR 2. I'SCS OF PYROCI.OR-FHJ.Fr> TRANSFORMERS Automotive Industry................................................... Aviation Industry......................................................... Chemical Industry ........................................................ Electricity Generating Boards.................................... Engineering Industry................................................... Exhibitions................................................................... Gas Boards................................................................... General Post Office..................................................... Glass Industry............................................................... Muhi-storey Buildings................................................. National Coal Board................................................... Oil Industry................................................................... Rubber Industry........................................................... Steel Industry............................................................... Television....................................................................... 7 10 12 14 |8 20 22 26 28 30 33 34 36 38 40 X ADVANTAGES OF PYROCI.OR-FIIJ.FD TRANSFORMERS Fire Resistance............................................................. No Fire Precautions..................................................... No Siting Limitations................................................. Freedom from Contamination.................................... Over-Voltages............................................................... Low Noise Levels......................................................... Low Power Loss........................................................... High Impulse Level..................................................... No Maintenance........................................................... Ideal for Package Substations.................................... Lower Insurance Premiums....................................... Summary of Main Benefits ....................................... 43 43 43 43 43 43 44 45 45 45 45 454 * * 4. COST SAV ING WITH PYROCI.OR-HU.FI) TRANSFORMERS Installation Cost Comparison .................................... Maintenance Cost Comparison.................................. Examples of Cost Savings: Example 1................................................................. Example 11............................................................... Example III............................................................. 47 47 48 52 56 5. TYPICAL PHYSICAL PROPERTIES OF PYROCLOR Viscosity......................... Density........................................................................- Solubility of Water........................................................ Vapour Pressure............................................................ Water Absorption ........................................................ Gas Absorption............................................................ Stability (Corrosion) Test............................................ CHEMICAL PROPERTIES Fire Resistance.............................................................. Thermal Stability.......................................................... Resistance to Oxidation.............................................. Stability to Hydrolysis.................................................. DIELECTRIC PROPERTIES Dielectric Strength........................................................ Permittivity.................................................................... Loss Tangent............................................. D.C. Resistivity............................................................ 6. PYROCLOR-FILLED TRANSFORMERS IN OPERATION Effect of Temperature.................................................. Fire Resistance.............................................................. Transient Arcing and Pressure Build-up.................... The Effect of Time........................................................ External Contamination.................. Weight of Pyroclor-Filled Transformers.................. Transformer Faults: Leaks.......................................................................... Major Faults............................................................ Regulations and Codes for Practice for Indoor Transformer Installations........................................ 7. Fi l l!) ( HECKS 1. Sealed Transformers... 2. Unsealed Transformers Sampling Procedure.......... 62 62 62 62 62 63 63 64 64 64 64 65 65 65 65 66 66 67 67 68 68 68 68 69 * 70 70 71 1. Appearance............................................................. 2. Dielectric Strength................................................. 3. Moisture Content................................................... 4. Loss Tangent........................................................... Reclamation................................................................. X. DESIGN OF PYROCLOR-FILLED TRANSFORMERS Compatibility of Construction Materials.................. Coolant Volume........................................................... Hermetically Sealed Units............................................ Tap Changers............................................................... Terminal Entry............................................................. 9. storage! handling and DISPOSAL OF PYROCLOR Drums ................................... Bulk ............................................................................. Handling Precautions................................................. Disposal ofempty drums and waste Pyroclor .......... 10. GLOSSARY OF TERMS 71 71 71 72 72 ?4 75 75 75 75 76 ?6 77 77 3 S 6 9 0 SNOW MONS 0 7 6 9 9 0 1 Introduction History of Pyroclor Over forty years ago electrical engineers expressed the need for a synthetic electrical insubting fluid to replace mineral oil for transformer instalfifcons where fire was a particular hazard. The new fluid had to be as good as mineral oil in every respect, in ten6 of electrical insulation properties and performance under working conditions. But it had to be fire-resistant. This new synthetic transfoimer fluid was termed an "askareP and like all chemical innovations underwent an initial period of acceptance. But gradually the askare! proved itself and its use is now widespread. In Europe askare! transformers form a large percentage of the distribution transformers installed today. In France, one-third of the distribution transformers brought into service each year are of the askarel type. The first askarel fluid was produced by Monsanto in ,.,1932 and was the ideal solution to many engineering r problems. It meant that transformers could be placed indoors exactly where the electrical engineer wanted in his distribution system, at the load centre. Askarei- 4 filled transformers could be sited in confined spaces and no maintenance would be required. Askarel is a generic term for a group of fire-resistant products used as electrical insulating media. Monsanto manufactures transformer askarel at their Newport, Monmouthshire, plant and the fluid is known as Pyroclor. The purpose of this book is to enable both transformer manufacturers and transformer users to better under stand the many benefits of Pyroclor in modem industry and fo answer many of the questions which are still asked about transformer askarel. An international specification for transformer askarels has been drafted and is being reviewed by the competent authorities of the various countries involved. It is intended that this international specification will form the basis of a British Standard. Manufacturers are assured that Pyroclor will meet or exceed this British Standard specification. Pyroclor contains Polychlorinated Biphenyls (PCB's) which some studies have shown may be persistent, an environmental contaminant and. possibly, injurious to certain forms of bird, aquatic and animal life. However, the need for the safety and reliability pro vided by askarel-filled transformers, coupled with the fact that they are designed to be leakproof has enabled the continued use of PCB's in this application.. . . Two organisations in the electrical industry:--American National Standards Institute (Committee C-107) and C.l.G.R.E. (Study Committee No. 15 working group 02) are working to produce documents setting out guidelines/codes of good practice for the use of PCB askarels in electrical equipment. A typical 1250 kVa 3300 433 Volts sealed Pyroclor-filled transformer. A0s 07699 MQNS 0 7 6 9 9 2 2 Uses of Pyroclor-filled Transformers Pyroclor-filled transformers have been used in a very wide range of applications including installations in steel works, glass factories, airports, public buildings, offices and shops. In high rise buildings. Pyroclor-filled transformers have been installed several stories up or even on the roof, thereby saving valuable architectural space in overcrowded conurbations. In railways, ships. 6 coal mines, oil refineries and chemical plants Pyroclorfilled transformers have provided fire safe installations, protecting both personnel and property. Here, together with photographs, are a number of cases where Pyroclor-filled transformers are used by well known companies in many different industries. Automotive ' Industry *' Fifty-three Pyroclor-filled Transformers on Motor Company Rooftops Pyroclor-filled transformers solved a factory planning problem for the Ford Motor Co. Ltd. new tractor produc tion plant at Basildon. Essex. Although the plant covers 800,000 square feet the planners ruled that, in order to permit maximum flexibility in pro duction layout,there should be no permanent obstructions in the floor area. This meant that the many transformers required to supply the manufacturing and assembly oper ations could not be placed inside the building at floor level. Owing to the immense size of the building, transformers sited externally would have meant long runs of expensive low-voltage cables to connect with the many load centres required. The obvious place was the roof. But conventional transformers in this location would have meant an unacceptable fire risk--not so much from the possibility of a transformer itself starting a fire, but from the likelihood of it becoming involved in an extraneous blaze and its fluid carrying the fire to other parts of the building. Modem single-storey open-plan factories in fact constitute a major fire hazard since there are no solid walls to prevent the lateral spread of flames and smoke. Nevertheless, the roof had undeniable attractions and Ford decided to carry on with the scheme using II Pyroclorfilled fire-resistant transformers. In addition, 18 Pyroclor-filled transformers are sited at the Ford Motor Co. Ltd.. Dagenham, works and 14 at the new car assembly plant at Halewcod. All transformers are on the roof, so too are the 10 units at the Caterpillar Tractor Co. plant at Glasgow. 7 Roof insta/lation--Tmo Pyroclor-filled fire-resistant trans formers are installed on the fiat roof of the Ford Motor Co. Ltd.. Basildon Works. with a light enclosure around them. In the event of a fire in the factory below there is no risk of the transformer cooling fluid spreading the blaze. VSS940 SNOW t I: i.c' i- 8 HONS 0 7 6 9 9 5 Pvrtulor-fif/ed transformers we \npftlving till /vn< cr requirements at I'auxhafl Motors' rum 700 acre vehicle proving gntutui near l.ii/liw'tmi. Heilfnrihhuc. Aviation Industry Britain's First Jumbo Jet Hangar Powered by Transformers Two 1.5 MVA transformers filled with Pyroclor are sup* plying all power requirements to Britain's first Boeing 747 hangar at Heathrow Airport. London. " Among unique features powered from the transformers are six sliding glass doors each 75 square feet and weighing 45 tons and an air conditioning system that blasts down an invisible curtain of hot air to bring the hangar temperature up to a comfortable 20* C (65~ F) within 15 minutes of the doors closing, even in the coldest weather. Besides natural light from a glass roof, a blended installation of 283 mercury and sodium lamps will provide pleasant working light for technicians maintaining the giant iets. 10 For servicing, aircraft will be towed into the hangar nose first and manoeuvred into a specially contoured steel mezzanine floor 16 feet above ground. This will allow access to wings, engines and forward fuselage. (In conventional hangars, movable steps and gantries are used.) Another innovation powered via the transformers is the system for maintaining undercarriages. Normally, an aircraft has to be lifted up with jacks before the wheels can be moved, but in the new Hangar 01 the aircraft will remain on its normal level while the floor beneath the wheels is lowered to make inspection pits. The periphery of the hangar, housing all ancillary buildings within 4-storey structures, will also receive all power require ments from the two transformers. 07*99} And whilst performing these many tasks, the Pyroclorfilfed transformers will not require maintenance for at least 25 years. They were chosen because of safety, space and cost factors. Several hundreds of pounds a year will be saved because fire precautions are unnecessary and the transformers are load-centred, bringing further economies in installation layout. The units are sited in a small transformer house in a comer of the Hangar and breakers of 800 amps feed into a bus bar circling the hangar's mezzanine floor with tap off points every two feet. Right.--A 1000 k VA Pyroclor-ftlled transformer is installed at the Westland Aircraft Ltd factory in Yeovil. Somerset. To save space the transformer is located in the roof over a busy machine shop. Below.--The new Jumbo Jet Hangor at Heathrow Airport, London. {Photo: courtesy Holland &. Hannen dt Cubitts (Southern) Ltd., and B.O.A.C.) U Chemical Industry Low-Voltage Power Supply at Chemical Processing Plants Some chemical processes involve the use of highly inflam* mable base materials. Large amounts of electric power may also be required, and the provision of suitable low voltage supplies under flameproof conditions can present problems. At the Coleraine works of Monsanto Textiles Ltd., where Acrilan fibre is made, the nccessarv power is obtained from 8 x IOOOkVA<U kV/415 V) and 6x500 kVA (11 kV/415 V) transformers. Four of the main distribution sub-stations are located in the main factory building. This location was made possible by the choice of Pyroclor-filled transformers which have reduced both installation and running costs. At Bagtan Bay, where Forth Chemicals Ltd. manufacture styrene monomer, the whole factory compound has been declared a flameproof area: consequently the 4 x 500 kVA transformers which supply the works are Pyroclor-filled even though thev are sited out of doors. Similarlv three 800 kVA and one 1500 kVA (I l kV'3.3 kV) and two 100 kVA (11 kV 415 V) transformers for the Monsanto poly ethylene plant at Fawlev have been located adjacent to the buildings involving ethylene processing. In neither of these cases would it have been economical to use dry transformers, since these would have required protection from wind-blown dust and driving rain. Pvrochr-fiHed transformers have reduced installation and maintenance costs at Monsanto Textiles Ltd . plant. Coleraine. ,V. Ireland. Electricity Generating Boards o o 1 s Is?' 2 Almost Twenty-Five Years Service in Electricity Generating Stations The ^Idest transformers in Britain using Pyroclor are at Trafford, Manchester, power station of the Central Electri city Generating Board. Installed in a basement there as long aeo as 1941. thev are still in service. The units are of 500 and 800 kVA. More recently. Pyroclor-filled transformers have gone into the San Esteban and Mallorca power stations in Spain, and in India, transformers of this type form part of the huge Damador Valley development in West Bengal, at the Bokara and Durgapur steam power stations. 14 15 *ONS 077001 Pyroclor in "Excellent" Condition after 30 Years Service ! For 30 years two 1000 kVA transformers have been working in the sab-basement of the Birmingham Civic Centre, built before the war as the Town Hall. One ofthe transformers was taken out of service, because of re-development and re distribution of load and it became possible to do a thorough examination of the Pyroclor fluid. Samples of Pyroclor were taken from the top and bottom of the transformer and tested at Monsanto Technical Service Laboratories for electrical, physical and chemical properties. Results prove that Pyroclor is still in excellent condition and there is no evidence of decomposition after three decades of service. Dielectric tests in accordance with BS 148:1959 (4 mm gap) showed that there was no breakdown of the fluid up to 90 kV. Modem transformers, unlike the one tested, are often hermetically sealed to prevent contamination by water. But tests on this unsealed transformer showed that the water content was only 52 ppm. substantially below the maximum level when drying out of Pyroclor is recomm ended. Low acidity, low inorganic chloride content and the absence of carbon particles indicated the lack of decom position over the years. Age had contributed to a slight increase in the boiling range of the Pyroclor, although not enough to affect the insulating properties. Throughout their service fife, these transformers (built to a specification dating back to 1936), have required no maintenance other than routine visual inspection. Nor have they required any topping up. - "Since the transformers were installed, records have either been lost or destroyed, but it is safe to assume that the Pyroclor was selected because of its fire resistant properties.'" said Mr. C. Claridge of the Birmingham Area M.E.B. who supervised the removal and examination of the pre-war transformer. 16 The fop removed to sho the dean condition of the interior. And now, the 1000 kVA transformer will simply require topping up before it goes back into service at a suitable indoor location. Two more transformers of similar age are installed at Marshall and Sneigrove. the busy Birmingham store. This is a remarkable example of the reliability of Pyroclor. What other insulating material would withstand 30 years of fluctuating load and still be in first-class dielectric condition' Or consider how many times a conventional transformer would have to be cleaned out and refilled over that period. HONS 0 7 7 0 0 2 The 1000 A YA. 30-year-ofJ Pyroclor-fillcd transformer at ilte Birmingham Civic Centre. O o * 0 0 1 1 0 SHOW Engineering Industry Analysing the Advantages of PyroclorfHied Transformers in Package Sub stations When the choice has to be made between various types of transformers for a distribution system, the best analysis is to compare relative advantages. This was the procedure adopted by Giddings & Lewis-Fraser Ltd. one of the world's leading manufacturers ofnumerically controlled machine tools. The total existing transformer capacity for the works was approximately 2,500 kVA installed in units of500kVA. and all transformers were of the oil-filled type having voltage ratios of 11.000/415. Giddines & Lewis-Fraser Limited proposed installing an is additional 750 kVA inside the factory to cater for the numerically controlled machine tools they manufacture, which are equipped with motors rated from 20-40 HP direct-on-line. It was decided that a package substation would show considerable cost and space savings compared with a conventional brick-built substation having a separate transformer connected by cable to the medium voltage switchgear. Only two types of transformer were considered: either PyTOcIor-filled or Class "C" dry type. This was because of possible fire risk associated with oil filled transformers inside the factory and because of recommen dations by the insurance company concerning fire risk. And here are the various factors which were considered by Giddings & Lewis-Fraser Limited and which influenced their ultimate decision. Pyroclor Filled Transformer 750 kVA AJiHiys 1. Fire-resistant insulant, consequently low fire risk. 2. No special buildings required for installation. 3. Compact and therefore suited to integrated transformer switchgear layout. 4. Can be placed at load centre resulting in large savings in cable costs which outweigh the additional cost of a Pyroclor-fiHed transformer. 5. Transformer hermetically sealed thereby preventing harmful ingress of dirt from a dust-laden atmosphere. 6. No fluid maintenance required. 7. Lower fire insurance rates. Disadvantages 1. Possible long term efficiency of hermetic sealing unless a welded construction is used. 750 kVA Transformer Class "C" insulated Advantages 1. Air-cooled, consequently low fire risk. 2. No special buildings required for installation. 3. Compact and therefore suited to integrated transformer/ switchgear layout. 4. Can be placed at load centre but savings in cable costs would not outweigh additional cost of the air-cooled transformers. 5. Lower fire insurance rates. Disadvantages 1. High cost: approximately 80% more than an equivalent rated oil filled unit. 2. High risk of winding failure due to deposits of coolant vapour and cast-iron dust associated with machine shop atmosphere. 3. Maintenance cleaning problems associated with removing above deposits. Pyroclor was the final choice and the finished package substation is a neat, compact arrangement. The medium voltage switch panels are fitted with 8 fuse switches TP A N. rated from 150 Amp. to 300 Amp. Future extensions can easilv be accommodated on the switchboard together with cabling. 19 HONS 0 7 7 0 0 5 Exhibitions and World Fairs >0 o o tz/ X EXPO 67 No less than % of the 100 electrical transformers used at Expo 67--Montreal's World Fair--were Pyroclor-filled. This architectural extravaganza with its 62 national paw ilions created a high demand for electrical power to supply exterior illuminations, monorail systems and escalators, the Expo Express train service and for the massive displays designed around such themes as Man and his World and Man the Creator. Consumption of electricity during the exhibition period was rated as equivalent to a city with a population of 50.000 and the estimated cost including installations was 10.000.000. Five single circuits at 25,000 volts nominal came from a substation on the south shore of the St. Lawrence river. Three of these circuits were transformed down from 25.000 to a 12.500 volt distribution network and the other two circuits were transformed down from 25.000 to a 600vclts network for the various buildings and amusements. Three double circuits at 12.500 volts from the north shore of the St. Lawrence river served directly electrical installations on Mackay Pier and the five rectifier stations of the mass transit system (Expo Express). These five stations were equipped with Pyroclor-frllctf transformers and rectifiers. 3 I Illustrated here arc the Pyroclnr-filfed transformers used for the British Pavilion and for the Expo Express rapid transit m stem. Gas Boards CO o or% r% o The New Generation of Gas Works The latest methods of town gas production are presenting plant designers with a number of new and interesting prob lems. derived from the inflammable nature of raw materials and from the large amounts of electric power required for the reforming process. A modern reforming plant may need up to 10 MW to drive motors for fans, feed pumps, hydro gen compressors, cooling tower pumps and other machinery. A further problem is space limitation. Most of the new plants must be erected on sites already occupied by coal-fed stations, and the latter cannot be removed until the new equipment is in full production. Both must operate together at first. w Finally, there is the question of reliability. The new install ations usually comprise a number of separate gas-roakine units built into a common process. An electric power failure would halt the whole complex, and it might take several hours to bring a 120 million cu. ft.'day output back on stream. The North Thames Gas Board's new plant at Slough, built by Woodai! Duckham Ltd. on the site formerly occupied by a coal carbonising plant win have an output of 90 minion cubic feet of gas a day. Space was a critical factor, and the only way to lit three transformers into an area set aside for two was to specify 3 x 1500kVA Pyroclor-filled units to avoid the need for fire walls between and around them. They will work in parallel with automatic protection equipment; and should any of the three units fail the load will be automatically transferred to the other two. All are hermetically sealed and although their initial cost will be higher than equivalent oil-filled units, it is anticipated that maintenance costs will be lower. On the same West London site, there is a 15-million cubicfeet-per-dav peak load reforming plant which is fed with 1000 BTU methane gas. This plant is supplied with electri city from two 500kVA transformers which again are Pyroclor-filled. chiefly because a gas main runs across the only site available for the unit. Pyrodor has the advantage of being chemically inert: it does not deteriorate in any way with time, consequently no maintenance is required and the initial charge of fluid should last for at least thirty years without replenishment or attention. This was a factor in the choice of Pyroclor-filled trans formers for the Slough Works and also for the new 120million cubic-feet-per-day Town Gas Plant. Romford Works of the North Thames Gas Board. This is the largest capacity gas producing unit yet ordered by the British Gas Industry. Here there will be one group of 3 x lOOOkVA and one group of 3 x 1500kVA Pyroclor-filled transformers on a site which may also have to be occupied by tanks containing light distillate spirit. The reformers in this plant are fully instrumentated and will be operated by a very small staff. It is therefore important that maintenance requirements should be kept to a minimum. Other Gas Boards who have specified Pyroclor-filled transformers for reasons of space limitation and reduced maintenance are The North Western Gas Board at Preston where four 1500kVA units are in service whilst plant reconstruction is underway. At the North Thames Gas Board. Southall. Europe's largest gas plant, two 600kVA Pyroclor-filled transformers have been operating since 1958. Pyroclor-filled transformers were chosen because of possible fire hazard and drainage pit considerations if conventional oil-filled units had been used. Furthermore, problems of space and cost precluded the use of air-cooled transformers. Pyroclor-filled transformers at the North Thames Gas Board, Southall, have operated successfully since 1958. 23 HONS 0 7 7 0 0 9 MOMS 0 7 7 0 1 0 One of the four 7J0 k VA hermetically sealed Pyroclor.flled transformers installed in a flame-proof area at the North Thames Gas Board Canxev Island Methane Terminal, in dose proximity to the liquid methane tanks. These trans formers are manufactured to B.S.! 71 and operate at 3300 415 solts. The low tension cable box is pressurised with nitrogen and there is aflame-proof cable box on the high tension side. The transformers are fitted with temperature gauges and bursting discs. Pyroclor-filled transformers located at North Thames Gas Board. Slough. a Pyrocbr-fiUed trans formers associated w ith the power supply to the large-scale prod uction plant of the North Thames Gas Board. Romford. They are installed in close proximity to highly inffammahle spirit tanks. HONS 0 7 7 0 1 1 i i General Post Office s I X Compact. Dust Free, Pyroclor-filled Units Below Ground for Railway Power Recent modernisation on the British Post Office's private underground railways, which link eight postal depots in the busiest parts of London, included the installation of Pyroclor-filled fire-resistant transformers. In the event of the transformers becoming heated due to a fire in the vicinity there is no risk of burning fluid spreading the conflagration through the underground tunnel systems. For static rectification of alternating current, the combin ation of Pyroclor-filled transformers and mercury-arc rectifiers has proved extremely reliable and economic. At Mount Pleasant the sub-station is below the platform on which the mail-bags are handled. Pyroclor-filled trans formers were chosen because no enclosures or COj equip ment were required. They were preferred to air-cooled units because they are more compact, an important consideration below ground. In Lisbon. Portugal, the Metro has installed seven Pyroclor-filled transformers fora sunken rectifier sub station and The Pennsylvania Railroad Co. has now used Pyroclor-filled units for 25 years. Every one of the company's 215 electric locomotives is now equipped with this type of transformer. A Pvroclor-fi/led transformer of the type used hv the British Post Office at its Mount Pleasant. London, sorting office. At the Post Office private underground railway, power for traction, signalling and lighting comes from transformers filled with Pvroelor fire-resistant cooling fiuid. n Glass Industry * ro* rv O O Where large numbers of transformers are required for diff erent duties as. for example, in a modern glass works with electric furnaces and electrically driven machinery. L.T. cable costs can become astronomical unless the transform ers can be sited close to the equipment they are to serve. This often means that only Pyroclor-filled fire-resistant transformers can be considered for most duties, and at Chance-Pifkington Optical Works. St. Asaph. N. Wales, a total of 19 such units have been installed. Four 750 kVA transformers are the main source of power, with 15 special transformers and reactors, to supply the various furnaces. The latter include I x 200 kVA. 5 x J50 kVA. 1 x 100 kVA. 6 x 50 kVA and 2 x 37.5 kVA units. AH are located at load centres inside the factory itself and the use of Pyroclor has saved fire protection costs, reduced maintenance and by far the greatest saving has come from the reduced lengths of L.T. distribution cable required. HONS 0 7 7 0 1 5 Larfe numbers of Pyrocfnr-fifled transformers performing various duties at the Chance-Pilkington Optical Works. St. Asaph. \. H ales. 29 Multi-Storey Buildings 'O o r* o a * Q X Freedom from Fire Risk in High-Rise Structures Pyroclor-filled transformers are ideal for supply services in tall buildings. Freedom from fire risk is important in overcrowded areas and these transformers can be sited anywhere, in the basement or at the bottom of a lift shaft for example, without special fire protection. Costly runs of L.V. cable are avoided by using Pyroclorfilled transformers in the sub-stations on several levels of a tall office block. The clean lines and modern appearance of present-day architecture are not marred by obtrusive out buildings or cages. Pyroclor transformers can be installed indoors, out of the way, and assist improved architectural planning. The Canadian Imperial Bank of Commerce. Montreal, installed Pyroclor-filled transformers on the 42nd floor, further proof that these units can be safely installed anyvkhere--even at the top of the Commonwealth's tallest skyscraper! M> 1 </> g 3E 9* a* o o SO zo X National Coal Board Several modern colliery winding installations in Britain have been equipped with Pyroclor-fillcd fire-resistant trans formers. In the event of the transformers becoming heated due to a fire in the vicinity there is no risk of burning oil pouring down the mine shaft to spread the conflagration. The North Western Division of the National Coal Board, for example, has installed 14 Pyroclor-filled transformers for rectifier duties at collieries in the Lancashire area. These arc installed in the winding towers immediately above the pit shafts and. according to an NCB official, "the fire hazard associated with the difficulty of containing such a large volume of oil from reachingthe shaft, made it essential to use a non-flammable fluid if the transformers were to be mounted in this position and avoid lone and cosily copper connections". Very similar installations have been com pleted at two collieries in the Durham Division of the National Coal Board. 53 Industry In Oil Pipeline Systems With completion of a new 500-mile pipeline by Con structors John Brown Ltd., over the Atlas mountains, from the Sahara Desert to the Mediterranean coast, a further 10 million tons of crude oil a year will flow from the Algerian oilfields of Sodetd National de Transport etdeComraercialisation des Hydrocarbures (S.O.N.A.T.R.A.C.H.). At the Arzew terminal on the Mediterranean, where light crude oil is stored ready for loading into sea-going tankers, a 500 kVA Pyroclor-filled transformer has been placed beside the main switchroom. Two more, one of 150 kVA and one of 200 kVA. have been installed at a nearby tanker deballasting station and in the maintenance workshop. The advantage gained by installing Pyroclor-filled trans formers was the freedom from fire risk when pumping a (light crude oil at ambient temperatures which may vary between--2'C and J-50'C. By minimising this risk it was possible to obtain better insurance rates and to conform with the practice in Algeria, where all existing oil plants have transformers with fire-resistant filling. All units supplied for the S.O.N.A.T.R.A.C.H. project are hermetically sealed and will require little maintenance--a factor of some importance where unskilled staff are being trained to take over. And because the transformers were sited close to the plant lone cable runs have been avoided k Rubber Industry r* o r* rv o c-1 Q % In Motor Tyre Factories As in many other modern factories it is important to locate distribution transformers close to the plant they serve and to eliminate the expense of low-tension cable mns. But if the factory has a fire hazard, as in a large motor tyre plant, such economies are impossible to achieve unless Pyroclorfilled transformers are specified. At the Goodyear Tyre & Rubber Company's works in Glasgow, electric power and lighting demands are met by one 1250 kVA and four smaller transformers, all sited inside the factory buildings. Three have been installed in major control rooms and the other two on platforms high above the production shops. The aim in choosing these sites was to place transformers as close as possible to the various load centres without encroaching on valuable production space at floor level. This was made possible by using Pvroclor-filled transformers. The main transformer installation at the Belfast factory of Michelin (Belfast) Ltd., is oil filled. Even so, the six 40 kVA transformer/transductors, six 50 kVA transformers and four 100 kVA transformers on the shop floor, where the fire hazard is greater, are filled with Pyroclor. Pyroclor-filfed transformers are also used at the Firestone Tyre factory. South Africa. In countries where higher ambient temperatures are experienced, the high thermal stability of Pyroclor is an added advantage which has con tributed to its general use in such areas. Saving space on the factory floor with Pyrodor-fiiled transformers mounted in the roofgirders at Goodyear Tyre A Rubber Co. Ltd. Steel Industry Basement Locations in Steelworks Eliminate Fire Hazard At the world's most advanced steelworks, the Spencer Works of Richard Thomas & Baldwins in South Wales, Pyroclor-filled transformers are installed in the basement of one of the rolling mills to eliminate fire hazard. The basement houses part of the main power distribution and control systems and even minor damage there could result in complete plant stoppage. Two Pyroclor-filled transformers supply rectifiers providinf direct current for the main drive motors of the two 60-inch temper mills which give the final finish to the cold-rolled wide strip. These 11 kV transformers are rated at 2625/4280 kVA. This installation is only one of several completed in recent years in British steelworks. The Steel Company of Wales, at its Port Talbot Works, uses three Pyroclor-filled trans formers for the 56-inch high-speed temper mill, and the Appleby-Frodingham Steel Company, at Scunthorpe, has 11 units, supplying mercury-arc rectifiers. In all these three installations, in basement location*, air cooled transformers with the British Class H insulation (180' C.) were considered but Pyroclor was preferred on cost grounds and because of the dusty environments. The modern steelworks depends on an unfailing supply of electricity. Even if a minor fire damaged the power distri bution system this could ha\e far-rcachine reporcusMonv ?x MONS 0 7 7 0 2 5 * t Television 'Q O rw o Pyroclor-filled Transformers inhigh ambient Temperatures Pyroclor-filled transformers are now In service at !h- new national television station for Malaysia. They are rated at 3.750 kV A, H <3.3 kVA. and connect with a series of smaller Pyroclor-filled transformers--2 x 1.000 kVA. 1 x 750 kVA and I x 500 kVA at 415 volts. Package sub-stations arc used for these smaller units, built in the form of control panel consoles. f \ * f k i | { : Despite their size, these 3.750 kVA Pyroclor-filled units form a neat indoor installation with control gear alongside. as illustrated. The Pyroclor fluid is unaffected by high ambient temperatures associated with tropical areas and the transformers are sealed, as recommended when using Pyroclor. so that maintenance is eliminated completely. Hence, there is always trouble-free transformer activity, an important consideration for ensuringcontinuity oftele* vision programmes. j : . . ? ; 40 T 41 MOWS 0 7 7 0 2 7 ots 0 7 7 0 ia 3 Advantages of Pyroclor-filled Transformers Pyroclor-filled transformers are intended primarily for medium voltage distribution systems from 50 kVA to 2.000 kVA. The electrical engineer has a choice when designing such systems between three types of trans former unit: Oil-cooled Air-cooled (Class C) Pyroclor Following are some of the reasons why Pyroclorfilled transformers are often considered in preference to the conventional oil-filled or "Class C" dry-type transformer. Figure 2 flame lest for Pyroclor-- the oil-soaked material on the right burns rapidly *hile the material soaked in Pyroclor on the left will not ignite under a bunsen burner. HONS 0 7 7 0 2 9 Fire resistance Pyrocler is very fire-resist2nt- It cannot be ignited by internal transformer arcing or by surrounding flames and therefore provides maximum transformer safety. Over-voltages Pyroclor-filled transformers can be used in installations where over-voltages due to lightning or switching surges are prevalent. No Fire Precautions Pyroclor-filled transformers eliminate the need for fire walls, pebble drains and fire fighting equipment. No siting limitations Pyroclor-fiiJed transformers are particularly suitable in many applications where fire risk is great and space is limited. They can be located indoors, close to working areas or at the load centre. Increasing population, higher density of building and proliferation of industrial plants, high rise offices and apartments have put a high cost on space. The electrical engineer faces problems of reduced architectural space. Tight cost control has set a premium value on construction economies and reduced operational costs. These limitations present a number of difficult problems in system design for the electrical engineer. "Load centring" has emerged as a means of solving them. In load centring. Pyroclor-filled transformers, long-established and thoroughly service-proved can provide new solutions-- reducing expensive low voltage cable runs and improving voltage regulation. Low noise levels A comparison of various noise levels is tabled for Oil-filled. Air-cooled and Pyroclor-filled transformers. Pyroclor-filled transformers are the quietest in operation across the complete kVA range and for guidance 50-60 decibels repre sent the noise of suppressed conversation in a business office whereas 60-70 decibels is equivalent to a radio at high volume. The decibel range of noise measurement is an exponential progression. Hence a "7" decibel noise increase represents a noise seven times as loud. Comparison of Noise Level Size kVA 500 750 1.000 1.500 Oil-Filled Decibels 54 56 57 59 Air-Cooied Pyroclor-filled Decibels Decibels 58 53 60 54 62 55 64 57 Freedom from contamination This is particularly important when transformers are being installed while building construction is in progress. Sealed Pyroclor-filled transformers are unaffected by dirty or dusty atmospheres. Low Power Loss Loss levels are another important consideration. In the graph below, the losses of Oil-filled and Pyroclor-filled transformers ate identical whereas the toss level of Air cooled transformers is consistently higher. MQNS 0 7 7 0 3 0 Iron core and copper core losses for the three alternative types of transformer are given in detail in this table: Comparison of Power Losses Size kVA 300 500 750 1,000 1.250 1.500 2.000 Iron Coro Loss (Watts) Dry-typo (Class "C") Oil-Filled or Pyroclor-filled 1.200 1.480 1.900 2.400 2.950 3.480 4.375 673 1.030 1.420 1.770 2.150 2,400 3.000 Copper Core Loss (Watts) Dry-Type (Class "C") Oil-Filled or Pyroclor-filled 6,250 8.050 10.400 12.800 15.500 18.500 25.000 4,600 6.860 9.500 11.820 14,000 16.000 20000 0 High impulse level Pyroclor-filled transformers (built to BS.I71) have high impulse strength and offer a greater margin of safety against surging and overload thanla$s *C transformers. . No maintenance Because Pyroclor is blended to provide maximum thermal and chemical stability, a properly sealed Pyroclor-filled transformer requires no maintenance. No fluid checks, fluid filtration or fluid change should be needed for the entire life of the Pyroclor-filled transformer, see page 70. Maximum reliability Pyroclor-filled transformers are as sturdy and reliable as oilcooled units. A statement of their reliability by a large network user is given as follows: "Properly designed and installed askarel-filled transformers will give trouble-free service for over 30 years. Since their introduction in 1932. the overall failure rate has been less than 0.5 ,, for all units under test and service conditions.1' Ideal for Package Substations The fire-resistance and elimination of fluid maintenance benefits make Pyroclor-filled transformers particularly suit- able for package substations where connections between transformer and switchgear may be solid busbar, thus eliminating the need for M.V. cable. Overall cable costs, site labour charges for interconnecting and time for installation are also greatly reduced. Busbar interconnections also lower the chances of a fault. Floor-space is saved, and the package Load Centre can be neat and uniform. o iw o on z o * Lower Insurance Premiums Although there is no standard reduction of premiums by insurance companies for Pyroclor-filled transformer users, many companies have been able to negotiate lower insur ance premiums. Summary of Main Benefits of Pyroclor-filled Transformers No pebble brains & fire eq. No maintenance No siting limitations Low noise levels Low loss levels High impulse levels No fire risk OIL air PYROCLOR V V V" 45 *4 rn rQs r* Q </> Cost saving with 1 Pyroclor-fiiled Transformers Typical installed costs of Pyroclor-fiiled, mineral oilfilled and Class kC' transformers, based on equivalent rated transformers have been calculated. While the initial cost of a mineral oil-filled transformer is lowest, once provision has been made for maintenance, re filling and the fire precautions almost certainly necessary with a flammable liquid, the installed cost can well be even higher than that of a Class `C* dry-type. The Pyroclor-fiiled transformer, whose initial cost is be tween that of the other two. can prove to be the least expensive. 46 HONS 0 7 7 0 3 3 In a well constructed transformer, the initial Pyroclor charge can be expected to last the life of the transformer. Thus a Pyrodor-filled transformer is maintenance free under normal operating conditions. Maintenance must be carried out on both oil and dry-type transformers. The following table gives details of typical maintenance require ments and costs. Source of Cost* OIL 1 AIR ipYROCLOR ! CLASS C' FILLED Transformer lOOOkVA 58 110 82 1 Fire-protection 32 - - equipment Civil Work TOTAL 10 8 100 : ns 14 86 Type Work j Required Frequency OIL-FILLED Cyclic loading ! Oil Filtration ; Oil Change Sample Check Every 7 years Every 14 years Every year Continuous Load . Oil Filtration Oil Change Sample Check Every 4 years Every 8 years Every year OPEN DRY-TYPE (Class "C") Regular cleaning of air gaps and air ways Depending upon environment but at least once annually PYROCLOR-FILLED NONE - 47 Examples of Cost Savings s with s Pyroclor-filled Transformers The most impressive savings that Pyroclor-filled trans formers can make are in the total solution of the power distribution design problem. The following are two typical problems with their alternate solutions com pared. EXAMPLE 1 (Theoretical) Small factory. 200' x 400'. requiring installed capacity of 1.000 kVA. supplied at 11 kV. and distributed at 415 V. 48 HONS 0 7 7 0 3 5 R -0 Two 500 kVA transformers m oatside sob-station, feeding two indoor dSstribotion and starter boards inside. Cable Costs MV Cable: 0.6 sq. in. Copper (P.I.l.C.W.P.V.C.) (singles) 0.8 sq. in Aluminium (singles) (P.V.C.) (Assume 4-core M.V. cable required) f 2.227 1.000 yds 888 1.000 yds Solution A Requires: 200 ft. MV cable between each transformer and distribution board. 2 x 200 x 4 (cores) ^5? x 2.227/1,000 (Copper) -- 1,600 ft. 1,190 pp X 888/1.000 (Alum.) = <74 Note: All pricings quoted are based on costs prevailing 3rd quarter 1967. 49 HONS 0 7 7 0 3 6 Site two 500 kVA transformers inside boBding with distribution boards. Cable Costs E.H.V. Cable: 0.06 sq. in. Copper (P.I.L.C.S.W.A.) 0.10 sq. in. Copper (P.I.L.C.S.W.A.) 0.15 sq. in. Aluminium (Sat. polythene S.W.A. A P.V.C.) (Prices are for 3-core cable) 1,342/1.000 yds. 1.837/1.000 yds. 1,838/1.000 yds. 50 Solution B requires two 200 ft. E.H.V. cable runs to connect source of supply to the indoor transformers. 200 x 2 = 400 ft E.H.V. 400 x (Costs cited) - 179 (0.06 Copper) 1" 245 (0.10 Copper) 245 (0.15 Alum.) HONS 0 7 7 0 3 7 Operating Costs Assume the two transformers are 75% loaded. 50% of the time, operating 4.400 hrs annum, with power costs at ip.'unit. (Solution A) Power Loss in MV Cable 6.100 watts (Copper) 7.750 watts (Ahim.) The minimum improvement in conductor Joss by using the E.H.V. cable to a load centre is 6.03 kW or an annual minimum saving of 110 Cost Comparison Summary 1,600' MV Cable (Solution 8) Power Lots in E.H.V. Cable 56 watts (0.06 Copper) 40 watts (0.10 Copper) 44 watts (0.15 Alum.} 40<r E.H.V. Cable Cable Cost: Minimum Saving 229 Operating Cost: Minimum Saving 110 per annum Si EXAMPLE II (Actual case history detailed cost analysis of instal lation and operation*). 1 o n* r* O c/> Z X Factory with fire risk. Transformer size l.OOOkVA: maxi mum demand. 700 kVA; load factor, 0.35. Three alternative solutions of the problem of supplying this can be considered: 1 Substation to be installed outside factory with MV feed to load centre--a distance of 200 yds. (Cost: 6,688) 2 Substation to be installed inside factory at the load centre containing a standard oil-filled transformer and MV switchgear. Fire protection equipment to be installed inside the substation. The 11 kV metering O.C.B. to be installed outside the factorv a distance of 200 yards awav. * (Cost: 2.891) 3 Same as 2 but utilising a Pyroclor-filled transformer: no fire protection needed. (Cost: 2.623) The costs that would be common to all solutions can be omitted. The electrical characteristics of Pyrodor and oil-filled transformers are similar, therefore the cost of transformer losses can be ignored Basic Pricing Data Cable Losses: Based upon C.E.G.B. bulk tarifiT Day rate units (adjusted for 100 - per ton of coal) 0.6873 d/unit Peak units (adjusted for 100/- per ton of coal) 1.0873 d/unit 90% of the losses occur at the Day Rate 10% of the losses occur at the Peak Rate Therefore, cost per unit (plus 5% to cover losses in the system) is: 0.6783 x 0.90 - 1.0873 x 0.10 x 1.05 d/unit = 0.7688 d/unit Demand Costs: (including 8% to cover losses in the system) = 7.11/kW Loss Load Factor: 0.3F - 0.7F2 = (where F = load factor (0.35) 0.191 * Giste'u* ecfcnowledgemant is mad* to t*a Birmingham Electrical Engmeannq 0Ot-. Mrtflaod Eiaeincitv Board 'or than assistance in calculating this case ""Story 52 Q r* r* o System Conditions: Cables installed in conduits: 700 kVA = 970A (Rating of 3 x 4C .5 Al. cables installed in a 3-way conduit is 370 A--in accordance with ERA Report Reference F/T.183). Voltage Conditions at Load Centre: Assumed temperature of cables: 50C Resistance of 4C .5 Al. cables at 50C = 0.084 x 1.12! -- 0.094 ohms/1000 yds Load on each cable 970 = 323A ~T Volt Drop along 200 yd. length: 323 x 200 x 0.094 = Tooo 6.1V (2.5%) Capital Costs: Additional cost over alternatives to house switchgear and transformer 100 Oil-Filled Transformer 1.100 3 X 200 yds, 4C .5 Al. cable supplied, delivered and installed (including cost of conduits) and terminated 2,700 On cost 8% 3,900 310 Total: 4,220 Cost of Operating Losses: I*R per cable 323* X 0.094 x 200 x 3kW 1000* -- 5.9 kW per cable Annual unit losses in one cable: 5.9 x 8760 x 0.191 x 0.7688 = 240 Demand Losses per cable: 7.11 x 5.9 -- Total annual fosses per cable: Total losses per 3 cables: Loss over 25 vears at interest of 7.1 %: 220.5 x 11.147 ' " 31.5 42 73.5 220.5 2,478 53 MQftS 0 7 7 0 4 0 System Conditions: Load: Current: Size of Cable: Resistance of Cable at 20eC: 700 kVA at II KV 37A 3-core 0.015 sq. in (A!) 0.282 ohms/1.000 yds Capital Costs: Building to house transformer 1000 kVA oil-filled transformer Fire protection in substation 200 yds. 3C. .15 sq. in A1. cable supplied delivered, installed (including cost of conduits) and terminated 500 1.100 300 750 On cost 9% 2.650 210 Total:2.860 54 Cost of Operating Losses: l*R per cable = 37* x 0.282 x 200 x 3kW - 0.22kW 1000 Annual unit Losses: 0.22 v 8760 x 0.191 V .7688 1.2 240 Demand Losses: 0.22 x 7.11 = 1.6 Total Annual Losses: 2.8 Loss over 25 years at 7|. interest (2.8 1 1.147) 31 MONS 0 7 7 0 4 1 Capital Cost: Proportion of cost of Load Centre Housing for Transformer 1.000 kVA Pyroclor-filled Transformer 200 yds. 3C. .15 sq. in Al. cable supplied delivered installed (including cost of conduits)and terminated 200 1.450 750 On cost 8% 2,400 192 Total: 192 Cost of Operating Losses: The cost of operating losses for this solution will be identi cal to that of Solution B. Annual Losses: 2.8. Loss over 25 vears at 7h% interest: 31 Comparison of Costs Capital Cost Cost of Operating Losses. C Towi (t) Solution A (MV) 4.210 Z478 6.688 Solution B Oil Filled Transformer 2.860 31 2.891 Solution C Pyroclor Filled Transformer 2.592 31 2.623 55 EXAMPLE III Multi-Storey Buildings Supply to 32 Storey Blocks of Flats. Details of Load: No. of consumers .. ADMD per consumer Total load of building Load Factor .. 248 8 kW 1984 kW 0.32 Two alternative schemes of supplying this load are considered: 1. One 4 MVA capacity substation on ground floor. 2. One 2 MVA capacity substation on ground floor and one 2 MVA capacity substation on 16th floor. Cost of Copper Losses: Based upon latest C.E.G.B. bulk tariff. Day rate units (adjusted for 100/- per ton of coal) 0.6873d./unit Night rate units (adjusted for 100/- per ton of coal) 0.5573d./unit Peak Units (adjusted for 100/- per ton of coal) 1.0873d./unit 82% of losses occur between 07.00 hrs and 23-00 hrs. 9% .. 23.00 hrs. and 07.00 hrs. 9%.................... during peak periods. Therefore cost per unit (0.6873 x 0.82 x 0.5573 x 0.09-^ 1.0873 x0.09)d./unit Plus 5% to cover losses in the svstem. (0.6873 x 0.82 ^0.5573 x 0.09 -1.0873 x 0.09) 1.05 =0.7463d./'uniL Demand Costs, including 8% to cover losses in the System 7.11/kW 56 T m o r* rw o co X O v Load Loss Factor: Loss Load Factor = 0.3F -- 0.7F2 where F = load factor (0.32) = 0.168 Capital Cost: Contribution to Corporation foT Substation Chamber 2 x 1000 kVA oil-filled Transformers at 1100 each MV Cables between substation and distribution board on 16th floor (53yds/cable) On cost 8% 1200 2200 300 3700 296 3996 57 Assumption: Lift for hoisting equipment to 16th floor available. Contribution to Corporation 976 per substation. Transformer in ground floor substation oil-filled Transformer in 16th floor substation Pyroclor-filled HV switchgear installed in ground floorsubstation--isolation of Pyroclor-filled transformer by means of remote tripping. Cost of Losses: Assumed temperature of cable 50C Resistance of 4C .15 Al. cable at 50C - 0.316 ohm''1000 yds. 5* Current/Conductor/Cable -- 345 A Distance of feed 53 yds. = 0.0168 ohms. I*R per cable -- 345* x 0.0168 x 3 x 10~l kw = 6.00 kW per cable Annual unit losses in one cable 6.00 x 8760 x 0.168 x 0.7463 27.5 240 Demand losses per cable 7.1! x 6.00 42.7 Total Annual losses per cable 70.2 Total Annual losses for 4 cables 280.8 MOMS 0 7 7 0 4 4 *O NS 0 7 7 0 4 5 Annua! maintenance cost of 2-1000 kVA oil filled transformers = 2 Present value of above charges over 25 vears at interest of 7i% ' (280.8 - 2) x i 1.147 3140 Capital Costs: Contribution to Corporation for Substations at 976 each I x 1000 kVA oil filled Transformer at 1100 I x lOOOkVA Pyroclor-filledTransformeratI450 53 yds. 3C .15 sq. ins. (Al.) cable supplied, delivered, installed and terminated 53 yds. 4C 0.3 sq. in. (Al.) cable as above (30% Interconnection between substations) Fencing off transformer, interlocking compound with 11 kV OCB and remote tripping 1953 1100 1450 124 150 200 On Cost 8% 4976 398 5374 Cost of Losses: Resistance of 3C 0.15 Al. cable 0.172 ohmsTOOO yds. Current/Conductor'Cable 50A at 11 kV Distance of feed 53 yds. = 0.0092 ohms. l*R per cable 50* x 0.0092 x 3 x 10~-? kW 0.068 kW Annual unit losses 0.068 x 8760 x 0.168 x 0,7463 240 0.3 Demand Losses 0.068 x 7.11 0.48 Total Losses 0.78 Annual maintenance cost of 1000 kVA oil filled transformer 1. Annual maintenance cost of 1000 kVA Pyroclorfilled transformer NIL Present value of above charges over 25 vears at interest of 7i% ~' (0.78 -i- 1.0) x 11.147 20 Summary of Costs Capital Cost P V of Running Costs Total Solution 8 i$ 24 5% cheaper than Solution A. Solution A 4 MVA $.S. on Ground Floor 3996 3140 7136 Solution B 2x2 MVA s.s. 5374 20 5394 59 Typical properties of Pyroclor There are two grades of Pyroclor available: PYROCLOR 5 the recommended fluid for all Pyroclor-filled transformers operating at normal ambient temperature conditions. PYROCLOR 1 for cases where transformers are required to operate at unusually low temperatures. Pyroclor 1 and Pyroclor 5 have similar properties but Pyroclor 5 has the additional advantages of lower density and higher relative permittivity. 60 The following table shows typical values for several properties of Pyroclor 5 and Pyroclor 1. Typical Properties of Pyroclor 1 and Pyroclor 5 MONS 0 7 7 0 4 7 Property Appearance Colour Density at 20"C Refractive Index at 20'C Kinematic Viscosity at 20CC Fire Point Pour Point Neutralisation Number Inorganic Chlorides Scavenger Content (PPO) Water Content Electric Strength at 25'C, 50 Hz Resistivity at 10Q"C, 500V, after t minute Dissipation Factor (tan $) at 100'C. 50 Hz Relative Permittivity at 100 C, 50 Hz Test Method ASTM D1702 ASTM D1702 ASTM D1810 and ISO/R 649 ASTM D1807 ASTM D445 ASTM D92 ASTM D97 Monsanto ASTM D1821 Monsanto ISO/R760 ICC 156 Monsanto Monsanto Monsanto Unit APHA g/cm* Pyroclor 1 Pyroclor 5 Clear liquid free frorr suspended matter and sed ment 150 max. 150 max. 1.555 to 1.565 1.502 to 1.524 cSt C CC mg KOH/g ppm Cl % ppm kV T Q cm % - 1.6160 to 1.6180 24 max. None to BP -33 max. 0.01 max. 0.1 max. ca. 0 2 30 max. 46 min. 1 min. 5 max. 3.8 to 4 0 1.6173 to 1.6193 32 max. None to 8P --30 max. 0.01 max. 0.1 max. ca. 0.2 30 max. 45 min. 1 mm. 5 max 4.2 to 4.5 61 Viscosity Table 1 shows that the viscosity temperature characteristics of Pyroclor 5 closely resemble mineral oil. Pyrodor ! is suitable for very low temperature operation. TABLE 1 Temperature (C) -30 -20 -10 0 + 10 20 30 40 50 60 70 80 90 100 Kinematic viscosity (cSt) Pyroclor 1 Pyroclor 5 Typical mineral oil ca. 16 000 1 800 350 100 42 21 12 3 78 5.4 39 30 2.4 1.98 1.70 ca. 50 000 4 524 655 162 57 26 15 9.4 6.4 46 3.4 2.7 2.2 1.86 2 500 750 270 118 62 33 21 14 9.7 7.2 5.5 4.3 3.4 2.8 Density Table 2 shows that Pyroclor has approximately twice the density of mineral oil (15.2 lb. U-K. gallon for Pyroclor 5). TABLE 2 (C) 0 10 20 30 40 50 60 70 80 90 100 Density (kg/m3) Pyroclor 1 Pyroclor 5 1.578 1.567 1.560 1.545 1.534 1 533 1.512 1.501 1 490 1.479 1 468 1.541 1.530 1.520 1.510 1.499 1 488 1 478 1 468 1.457 1.446 1.436 Therefore the Pyroclor-filled transformer is heavier and this raises certain questions regarding the location of Pvrodor transformers, particularly in high-rise buildings. T>* subject is fully discussed in the section "Pyroclor-filled" transformers in operation'*. . . page 66. Solubility of Water Water is slightly more soluble in clean Pyroclor than in mineral oil, but there is very little change in the solubility between new and used Pyroclor. Vapour Pressure The variation of the vapour pressure of Pyroclor with temperature is shown in Table 3. Temperature <C) 40 60 80 100 120 140 160 180 200 220 TABLE 3 Vapour Pressure (torr) Pyroclor 1 Pyroclor 5 <1 2 5 12 27 55 105 188 322 527 <1 1 4 9 20 41 79 141 242 397 In the above table the values at the lower temperatures have been obtained by extrapolation. This procedure was adopted to overcome inherent difficulties in the measurements of low vapour pressures of mixtures of liquids. Water Absorption Figure 4 shows the absorption of water from humid air by transformer askarel and mineral oil. o r* rs* O (4 X Gas Absorption The solubility of carbon dioxide, air, nitrogen, and hydrogen chloride is shown in this table. SOLUBILITY OF GAS IN PYROCLOR Percent Gas by Volume Corrected to: 25C--750mm 0*0--760mm Carbon dioxide Air Nitrogen Hydrogen Chloride* 25C 71 5.7 6.0 37.8 100*0 47 4.9 4.8 50.9 In the absence of gas scavenger 25*C 100C 58 5.0 --5.5 4.4 Stability (Corrosion) Test Description A sample of the Pyroclor is heated in darkness for 6 hours at a temperature of 210?C with a prepared piece of alumin- ium foil. At the end of this period, the appearance, colour, inorganic chlorides and neutralization number of the sample of Pyroclor are determined. The piece of aluminium foil is examined for changes in appearance and its weight loss is determined. Results: The values in the following table must not be exceeded for the sample of Pyroclor to pass this test. Property Aluminium foil Weight loss (g) Change in apoearance Pyroclor sample Colour (APHA) Inorganic chlorides (ppm) Neutralization number (mg KOH/g) Test method Value -- Visual 0.0 None ASTM 01702 A STM D1821 Monsanto 200 (max) 5.0 (max) 0.01 (max) 63 Chemical Properties O o o on z Q X Fire Resistance Although Pyroclor can be shown to have a flash point when examined by the usual laboratory tests, no fire is carried back to the liquid phase, therefore there is no corresponding fire point. The autogenous ignition temperature of Pyroclor can be measured by dropping small quantities of the liquid on the floor of a ceramic lined muffle furnace. The liquid does not take fire until the surface glows with a dull red heat, approximately 700CC. However, once the liquid leaves the hot surface it ceases to burn and does not convey fire by means of a moving stream of liquid. The laboratory of the National Board of Underwriters (U.S.A.) have carried out stringent tests on the fire resistance of this type of liquid and have concluded that it is essentially non-flammable. Thermal Stability Pyroclor undergoes no thermal decomposition whatsoever at temperatures below 175"C. If Pyroclor is heated above this temperature by local over-heating or transient arcing, small quantities of hydrogen chloride gas are produced. The gas scavenger additive in Pyroclor absorbs this hydrogen chloride and prevents attack on the iron core or the cellulosic insulation. If a major internal fault occurs in a Pyroclor-filled trans- 64 former which results in a sustained arc below the Pyroclor surface, the extremely high temperature of the arc will decompose the Pyroclor. Major faults are discussed in the section "Pvroclor-filled transformers in operation" ... page 66. * Resistance to Oxidation Pyroclor has exceptional resistance to attack by oxygen. When subjected to a bomb test at 140"C in oxygen at a pressure of 250 psig. (17 kg/cm2) there is no evidence of oxidation as judged by development of acidity or the formation of sludge. Hot mineral oil in the presence of oxygen undergoes a series of complex chemical reactions, producing by stages, peroxides, acids, water and other condensation products which eventually form a sludge. Stability to Hydrolysis Whilst Pyroclor is resistant to attack by water, water will dissolve in Pyroclor and will deteriorate the electrical properties. Pyroclor has been tested by refluxing with water whilst oxygen was passed through the mixture. No free chlorides were generated during this test. In another test Pyroclor was sealed in a glass capsule with water and heated for six hours at 150 C. and again no chloride forma tion was detected. Dielectric Properties (A Q Z Although a transformer liquid is principally a coolant, it must also act as an insulation in and between the windings of the transformer. Good dielectric properties are therefore an important characteristic of the fluid. Loss Tangent Satisfactory Pyroclor in a transformer may be expected to have considerably higher loss tangent than new material, in the range 0.2 to 6.8 at 100'C. Dielectric Strength The dielectric strength of Pyroclor is equal to or better than the best quality mineral oil and has the dielectric qualities required for the voltage stresses encountered in trans formers over the entire temperature range of operation. Permittivity The permittivity of Pyroclor is much closer to the permitti vity of cellulose and this leads to a greater uniformity of stress in impregnated press board. D.C. Resistivity Satisfactory Pyroclor sampled from a transformer may have a d.c. resistivity as low as 2.5 x 1010Qcm at 100:C. D.C. resistivity of Pyroclor is thus seen to be much lower than that of mineral oil by comparison. This inevitably leads to lower insulation resistance on finished transformers filled with Pyroclor than on their counterparts filled with oil. This is. however, quite normal and is an accepted characteristic of Pyroclor-filled transformers. 65 ?S<0 SHOli 6 Pyroclor-filled Transformers in operation Effect of Temperature The electrical engineer can place a Pyroclor-filled trans former anywhere in the distribution system, right at the centre of load if necessary because of these two important factors: 1. Pyroclor is fire-resistant. Where oil will ignite readily. Pyroclor will extinguish flame. 2. Pyroclor, unlike oil. is thermally stable. It suffers no change up to temperatures of 1757C and is affected very little beyond that point. Let us examine fire resistance more closely and take into account other operating conditions--electrical load (pres sure build-up), the effect of time and exterior contamination. 66 Fire resistance The fire resistance of Pyroclor may be easily demonstrated For example if Pyroclor is aerosoled in a container it may be sprayed out onto a conventional gas burner easily extingui shing the flame. A similar test with mineral oil will result in the immediate formation of a powerful jet of burning atomised liquid. . In the laboratory, teste may be conducted using oxyacetylene welding flame and electrically heated metal strips. Pyroclor fluids will not ignite when sprayed on such high temperature sources. In contrast, mineral oil will readily ignite to produce immediate and sustained burning. See also Pyro clor--Flash Point and autogenous ignition .. . page 64. It is for these reasons that a Pyroclor-filled transformer installation does not require fire fighting equipment, fire walls or anv other special fire precautions. Should the fluid escape as a result of a severe local fire it would tend to dampen and blanket the flames. Transient arcing and Pressure build-up Transient arcing or corona discharge is not unusual in all types of transformers and is usually caused by load fluctua tion. switching surges or lightning. If Pyroclor is raised above 1751C by local over-heating or transient arcing small quantities of hydrogen chloride gas may be formed. This gas will be immediately absorbed by the gas scavenger in Pyroclor. Thus any pressure build-up or possible attack on the iron core or cellulosic insulation of the transformer is avoided. Experience based in over forty years ofcontinuous operation of Pyroclor-filled units shows that the gas scavenger does not normally need replenishment, the initial amount being capable of lasting the life of the transformer. Sealed Pyroclor-filled transformers arc constructed to with stand normal operating pressure fluctuations. Pressure relief valves or bursting discs can be incorporated as additional protection if required. The effect of time The breakdown strength of Pyroclor in a properly sealed transformer does not deteriorate with age despite possible variations in power factor and volume resistivity. It is frequently found that megger readings taken on Pyroclorfilled transformers are considerably lower than those taken on oil-filled transformers. This is quite normal and the transformer is quite safe for use. The lower reading is simply a reflection of the much lower DC resistivity of Pyroclor compared with mineral oil. The reliability of Pyroclor is not affected by such low megger readings. One of the oldest Pyroclor-filled transformers in Britain installed in 1941 67 External Contamination Pyroclor-filfed transformers can be operated successfully in adverse environments. Satisfactory operation has been achieved in countless applications which include exposure to the dust and dirt of building sites, the metallic dust of load centred industrial factory installations or even the atmosphere surrounding a blast furnace. The layers of dust which may accumulate on a transformer during the years should have no effect on its operating efficiency. One source of external contamination which really will affect a Pyroclor-filled transformer in service is water. Water ingress should always be avoided. For example if the Pyroclor reaches a moisture level of 70 ppm the dielectric properties may be seriously degraded. This is one of the main reasons why sealed Pyroclor-filled transformers are recommended. Unsealed units require the installation cf protective devices such as silica gei to prevent water being drawn in by the natural breathing of the unit. Experience shows that inadequate maintenance of the breather gel can often render such protection useless. The Weight of Pyroclor-filled Transformers Pyroclor is approximately twice as heavy as mineral oil (Sec table). Generally the weight of a Pyroclor-filled transformer does not pose any particular problem when installed in high rise structures. Local floor strengthening may be necessary but present day architects generally allow for varying load stresses on intermediate floors, the tolerance being well above the weight of a Pyroclor-filled transformer. Often the transformer and control gear can be located near main Size (kVA) 500 750 1.000 1.500 TABLE IOil-Filled Dry-Type 1 Class C (weights in pounds) 5200 6,600 8.100 14.000 5.000 5.000 7.300 9.800 Pyroclorfilled 7.000 8.500 11.000 17.000 6* support areas where additional high floor loading may be tolerated. Pyroclor-filled tranformers have been installed in e'evated locations in many tall buildings and rarely has local floor strengthening been required. See page 30- Transformer Faults.. Leakage A properly sealed Pyroclor-filled transformer should norm ally never leak, but if leakage does occur. Pyroclor should not be fed into a normal drainage system. Monsanto will advise on disposal. Major Faults As with most liquid filled transformer units major faults are extremely rare with Pyroclor-filled transformers. However, should sustained arcing result from a major fault condition in a Pyroclor-filled transformer, hydrogen chloride gas would be formed but since hydrogen chloride is a noncombustibie/non-explosive gas there will be no danger of a resultant fire. The quantity of gas formed is directly pro portional to the intensity of arc and roughly the same amounts of gas are evolved from Pyroclor as from mineral OIL PYROCLOR Hydrogen 60% Hydrogen Chloride UNSATURATtD HYDROCARBBNS 18% SATURATED NTOROCAR80NS 10% OTHERS (NITROGEN ETC ) 14% OTHERS (NITROGEN ETC.) Decomposition products: OH and Pyroclor oi! for a given arc intensity. However, in the case of mineral cil the gases will be a mixture of hydrogen and hydro carbons. Unlike hydrogen chloride, these gases are flam mable over a wide range of gas air mixtures. Whereas with transient arcing the gas scavenger additive in Pvrocior-filled transformers adequately copes with gas formation, under major fault conditions this additive would be unable to cope with the quantities of hydrogen chloride formed and the pressure in the transformer would build up. Pyroclor-filied transformers may be fitted with a pressure relief actuator or a pressure bursting disc to give additional protection against such a situation. Therefore, should hydrogen chloride gas be released from the transformer unit as a result of a major fault it would be expected to disperse rapidly as transformers are generally located in well venti lated areas to facilitate cooling. It should be noted that the formation of gas will only continue whilst the arc is actually striking across the fluid. As soon as the overload current protection devices trip, arcing and the formation of hydrogen chloride will cease. Hydrogen chloride is an irritant gas. but it is easily detectable at concentrations below the harmful level. The quantity of hydrogen chloride liberated under major fault conditions is not likely to have a harmful effect on personnel provided they withdraw from the area or wear breathing apparatus. The gas may cause irritation of the eyes. nose, throat and lungs. If necessary irritation of the eyes may be relieved by flushing with water. Pvroclor derives its fire resistance from the halogen atoms in its molecular structure. Because of this some engineers have supposed that either chlorine or phosgene could be liberated by arcing. Five independent studies in three countries where askarels are extensively used have shown that both theoretically and in practice these gases are NOT produced: U.S A. FRANCE GERMANY Underwriters Laboratory Report Underwriters Laboratory Mi$c. Hazard Report Jay P `Study of the Formation of Phosgene by Decomposition of Chlorinated Hydrocarbon m the electric arc'' Paper: "Chimie et Industrie' 92, No 5 {Nov. '9641 Chemische Techniscie Reichsanstalt May 21 1 940 Report Farben Fabnken Baver 1964 Regulations and Codes of Practice For Indoor Transformer Installations When siting of transformers indoors by the system of load centring building regulations and codes of practice have to be taken into account. The "regulations For the Electrical Equipment of Buildings'" published by the Institution of Electrical Engineers, 1966 edition. Section C-5(Page 63) recommends: "Where fixed oil-filled apparatus of a capacity exceeding 20 gallons is used, means shall be provided for draining away surplus oil and for preventing the escape of oil into any other part of the building." Note: It is recommended that oil-filled apparatus installed within a building and having an oil capacity exceeding 50 gallons be placed in a chamber of fire-resisting construction, ventilated to the outside of the building only. There is no British Code of Practice covering the installation of Pvrocior-filled transformers. Reference can be made to the National Electric Code of the American Standards Association (1956) Article 450. Section 4522. page 152. 69 MOMS 0 7 7 0 5 5 7 Fluid Checks ft O 2 * 1. Sealed Transformers A properly designed, sealed Pyroclor-filled transformer needs no maintenance. 2. Unsealed Transformers Unsealed transformers (e.g. breather types) have been manufactured. Even these, when Pyroclor-filled, require no maintenance in the true sense. However, inspection of the fluid may be necessary at intervals to determine whether it has retained in full original electrical properties. Either the transformer manufacturer or user may wish to perform these simple fluid checks and the following is the procedure. Sampling Procedure A sample should be taken as close to the top of the liquid surface as possible in addition to a sample from the bottom of the transformer. If sampling tube connections are attached to the valves for ease of sampling, tubes should be made of either dean glass, stainless steel, aluminium or tin for rigid types and silicone rubber or teflon tubing for flexible types. It is best to take the sample from a trans former which is warm and operating at average or maximum load. Sampling of the warm Pvrodor more truly represents its condition during operation. Samples of Pvroclor to be used in tests of electrical pro perties. i.e. resistivity and power factor, are very easily 70 contaminated, and it is essential to follow the procedure recommended below in order to obtain true measurements. If a result is poorer than anticipated, the whole procedure should be repeated for a second sample (more than once if necessary). Sample Bottle Narrow necked glass bottle with bakelite screw-on cap is suitable. The sealing washer inside the cap should prefer ably be PTFE. but a paper disc can be used, if covered by a layer of aluminium foil. Other seals such as rubber, etc., will cause sample contami nation. Preparation of the Sample Bottle (a) If the bottle is new. wash out the bottle and cap with water and detergent (household type), rinse out with running warm water and then rinse three times with distilled water. If analytical quality acetone is available, give a final rinse with this to speed the drying process. (Do not use technical quality acetone as contamination is likely.) Dry in a clean oven for half an hour at approximately 110 C (longer if the acetone rinse is omitted) and keep the bottle closed in a drying cabinet until required. (b) If the bottle has been previously used (for Pyroclor sampling), first wash out with a hydrocarbon solvent such as benzene or petroleum ether, then carry out the cleaning procedure as described above. The Sampling Operation Remove the cap from the sample point and wipe the end of the pipe with a dry tissue. Race a receptacle under the sample pipe and run off about five litres. Then without stopping the flow place the sample bottle under the pipe and rinse out the internal surfaces fnot forgetting the screw cap) three times with Pyroclor before filling with sample to about 90% full. Take special care to avoid touching the sample point with the neck of the sample bottle. Put the screw cap on and tighten immediately. Close sample dis charge valve and replace cap. Clean the exterior of the bottle as necessary with a clean tissue. The materia! used for rinsing etc. should be discarded. (See section 9 regarding arrangements for disposal of waste product.) If the sample is to be stored for an appreciable time before testing, the bottle (even if of dark glass) should be wrapped in aluminium foil or opaque paper and placed in a card board tube or other container suitable for transportation. Sampling should be preferably carried out under cover, if this is impossible, precautions must be taken to keep any rain from the vicinity of the sample pipe and bottles. Sampling out of doors in wet weather conditions should be avoided, if at all possible. In such circumstances make a note of the adverse conditions. Routine samples of Pyroclor should be checked for: 1. Appearance 2. Dielectric Strength 3. Moisture Content 4. Loss Tangent 1. Appearance A blue, green or red cast in clear Pyroclor shows that it is extracting colour from internal materials. This is not an operating hazard when the dielectric strength stays above 40 kV. when the moisture content is low and when there is no leakage. However, this condition calls for a check on the interior construction of the transformer and a re-assessment of the compatibility of materials used in its construction. If the Pyroclor is dark brown or black, with small carbon particles present and if the dielectric strength is low. then heavy arcing has been occurring and immediate action should be taken. Because Pyroclor does not oxidise, sludge or decompose in normal use it can suffer only minor contamination. Turbi dity combined with high dielectric strength is due to insula tion particles, metallic dust or dirt in the Pyroclor. However, insulation efficiency may still be excellent, even though the D.C. resistivity may be impaired. Care must be taken to distinguish this particle contamination from the precipita tion of the gas scavenger which occurs at low temperatures. 2. Dielectric Strength Measure this following the procedure in BS 148:1959. Appendix F. If the dielectric strength has decreased signifi cantly below 40 kV this indicates moisture pick-up, arcing or both and immediate action should be taken. Dielectric strength is a major indicator of the operating efficiency of Pyroclor. Visual and dielectric tests are the only ones necessary for routine inspection and well-sealed transformers have run satisfactorily for 30 years on the original Pyroclor. 3. Moisture Content Water will migrate from a transformer's solid insulation to the Pyroclor liquid and vice versa, depending on tempera ture. When the transformer is hot, the moisture is likely to be found in the Pyroclor and accounts largely for periodic variations in dielectric strength--higher in winter months. Should the dielectric strength ever drop below 40 kV, measure the water content by the Karl Fischer method in ASTM D 1533-61. Over 70 ppm the dielectric strength of Pyroclor drops below the efficient insulating value and immediate action should be taken. 4. Loss Tangent The loss tangent (power factor) of a new transformer should range from I % to no more than 5%. It is normal to expect the loss tangent to increase in a satisfactorily operating 71 HONS 0 7 7 0 S 7 CD m o n rw O c/> * 0 1 Pyroclor-filled transformer, but the overall loss tangent will not be much beyond 5%. The moisture level and dielectric strength will remain satisfactory. Occasionally the loss tangent of an unarced, satisfactorily operating Pvroclor-filled transformer may be relatively high, for example 15%. The loss tangent of the Pyroclor will also be high, as much as 50% at 20 C and 50 Hz. If this is the case, check the dielectric strength. If there is a downward trend, this indicates the probability of moisture entry which should be confirmed by the Karl Fischer test 72 for water content. Reclamation Provision is made to reclaim the Pyroclor in the event ol unexpected deterioration due to minor arcing, entrance of moisture and the presence of other contaminants. Reclama tion services are offered by Dalton & Co. Belper. Derby shire. The following fable gives the typical properties of new and used Pyroclor. MCNS 0 7 7 0 5 S Typical Values found in Pyroclor under various conditions Inspection check points Colour Clarity A New Pyroclor B Pyroclor in properly built' new or rebuilt units prior to use Light straw Light straw Clear, free from particles Clear, practically free from particles B After normal ooeration (a survey of 50 units most 2 to 5 years old. some 10) D Non-arced but sftgbtty contaminated Pyroclor in improperly built units.' new or sfightly used E Same Pyroclor as in Column 0--after refining F Heavily arced Pyroclor due to neglect and internal electrical malfunction Light straw Can have blue green or red cast Cast remains showing extrac tion of soluble colour Black Clear, pace of particles Clear slight amount of particles Clear free from particles Contains carbon particles Water content 30 ppm 30 ppm 10--70 ppm. all dissolved water 20--100 ppm, all dissolved water 30 ppm max Near 152 ppm saturation level plus possible undrtsohred water Dielectric strength at 25 C-- B.S. 148 (kV) O.C. restivity at 100 C. 500 v/mm (T Q cm) 40 kV min 1 40--55 kV 40--51 kV 34--48 kV 40 kV min 5--17 kV 0.04 minimum usually at least 0.1 0.015 to 0.040 About 0.005 At least 1.5 About 0.003 Loss tangent (power factor) at 50 c/s 1 kV/mm 100* C (%) 2Sa C (%) 2 to 5 0.05 to 0.1 10 to 25 0.5 to 2 10 to near 80 0 5 to near 10 30 to new 100 about 7 to over 15 2 to 5 0.1 to 0.2 100 at least 255 1 A properfy bmlt transformer is defined as one in which the materials of construction 9<s chemically and electrically compatible with Pyroclor. 1 Above data relates to Pyrodor fluid not to the insolation resistance or loss tangent measurements on the transformer ttsert 73 Design of Pyroclor-filled Transformer Compatibility of Construction Materials: Pyroclor is an entirely different material from mineral oil despite some superficial physical resemblances. For example, Pyroclor will soften and plasticize a number of plastics and resins that are suitable for use in mineral oil transformers. If such incompatible materials are polar, they will ionize to a greater extent in Pyroclor than they would in mineral oil and so adversely affect the dielectric strength. For these reasons, only materials compatible with Pyroclor should be used in transformer construction. Pyroclor has a greater tendency to "creep" than oil. It is by its nature a more searching and penetrating liquid. For this reason, Pyroclor should not be added either as re-fill or top up to a mineral oil transformer. Conversely, a Pyroclorfilled transformer should not be topped up with mineral oil. Mineral oil is soluble in Pyroclor but any oil present will reduce its fire resistance. It is recommended that a maximum oil content of 2% is not exceeded and mixing of the two coolants is avoided at ail times. 74 Coolant Volume For economy, a Pyroclor-filled transformer design usually attempts to keep the liquid volume required as low as practical because it is more costly than oil. However, even without radical re-design the volume of fluid can be reduced by rounding the comers of the tank. Cooling tubes with oval or star-shaped cross-section will also reduce the fluid volume. Hermetically Sealed Units Because of their dependability and long service life. Pyroclorfilled transformers are normally hermetically sealed. A sealed unit made with compatible materials, requires no subsequent maintenance or fluid testing. Sealed units will also afford the most reliable protection against entry of moisture. Sealed units are sometimes designed with "top hat" con struction providing an expansion chamber with air or nitrogen filled space. The gas in this chamber is often sealed in at a slight negative gauge pressure when cold to allow for the expansion of the coolant at operating temperatures. With sealed units, it is customary to install rupture discs for pressure relief. They are constructed to burst at 10. 14. 15 or IK pounds pressure, plusorminus 3 pounds. They are usually sited such that the transformer tank withstands 25% over normal operating pressure. An alternative pressure relief system is the use of a spring-actuated pressure relief vent. Tap Changers Since frequent arcing deteriorates Pyroclor, it is unsuitable for switchgear and on-load tap changers below the liquid surface are not recommended. The normal construction practice is to provide some form of mechanical interlock on tap changing equipment to prevent it being actuated on load. Terminal Entry It is recommended that terminal connections be brought through side walls below the surface of the Pyroclor as free water would tend to float on the more dense Pyroclor. If this is not possible then it is recommended that the terminals be encased in a suitable sleeving to prevent the possibility of a flash over in the rare event that water enters the transformer and migrates to the liquid surface. Storage, Handling and \ Disposal of Pyroclor ' Drums Inside storage is recommended to prevent contamination of the product by water. If the drums have to be stored outside they should be stacked on their sides to prevent water accumulating around the bungs and being breathed into the drum during severe ambient temperature changes. Drum storage areas should be organised so that any leak ages are collected for safe disposal. Partially emptied drums should not be left open to the air and filled transformers should be closed to the air as soon as possible. Bulk The supply of Pyroclor in bulk tank car loads, offers many advantages to medium and large volume users, compared with drum deliveries. Unloading, storing and transferring to 16 the transformers is safer, easier, faster and cheaper. Material losses due to spillage and incomplete emptying of drums are eliminated. The possibility of product contamination during handling is greatly reduced. Even where storage and handling facilities are not at present available, the economics of bulk handling may quickly pay for the tanks and piping systems required. A booklet indicating the type of system necessary for the efficient handling of Pyroclor in bulk is available from Monsanto. As soon as a changeover to bulk delivery is contemplated, experienced Monsanto personnel will be available for site discussions regarding the most efficient type of installation for the particular location and an offloading procedure appropriate to that particular installation. T HONS 0 7 7 0 6 3 A modern installation for filling transformers with Pyroc/or from a hulk storage tank. 77 MOMS 0 7 7 0 6 4 Handling Precautions Pyroclor drums and containers carry the following label which gives general instructions for handling: IMPORTANT CHLOROD1PHENYLS (42%-54%) (or 60%) (PCB) This oroductcontair$ POLVCfJLOR,NATED 31 PHENYLS (PCB's) which some studies have shown may be oersisten*. an environmental contaminant anc. ocssibty. injurious to certain forms of bird. aauat*c and animal life. PREVENT ANY ENTRYINTOTHE ENV1R0NMENTTHR0UGH SKILLS. LEAKAGE. DISPOSAL. VAPOURISATION. RE-USEOF CONTAINERS OR OTHERWISE. SPILLS. LEAKAGES AND WASTE PROOUC" MUST BE COLLECTED. Use of this oroductmustbe restricted to aoolications which can be controlled so that entry into the environment does not occur and to aoolications in which it cannot come into contact with food, animal feedstuffs or oharmaceutica*s. HARMFUL SUBSTANCE IF TAKEN INTERNALLY OR IF IN PROLONGED CONTACT WITH THE SKIN. CAUSES IRRITATION OF SKIN AND EYES. DURING SHIPMENT AVOID SPILLS AND LEAKAGE INTO INLAND WATERWAYS AND THE SEA Store away from food, anima' feedstuffs and pharmaceuticals. . Keep container tightly closed. Do not eat or smoke when using. Avoid breathing vapours, mistorfumes. Do not wear contaminated clothing. Wash product from skin with soao and water. Wash eyes by flushing with water. In addition to the above we can add that: 1. Animal toxicity tests (small mammals) indicate that acute oral toxicity is low but that acute dermal toxicity may be moderate. 2. When handling the fluid minimise contact with the skin and wash any off with soap and water. People with sensitive skins should wear gloves resistant to chlorinated solvents or apply a silicone hand cream. 3. Should Pyroclor accidentally splash or be rubbed into the eyes, they should be rinsed thoroughly with water for a few minutes. It is suggested that all operators be pro vided with safety glasses as Pyroclor will cause pain if it gets into the eves. 4. Elementary rules of hygiene should be applied--such as not smoking, eating or drinking during handling and contaminated clothing should be discarded. 5. Pyroclor should be handled at ambient temperatures in well ventilated areas. If a Pyroclor-filled transformer is 78 to be opened, it should be allowed to cool down to room temperature before opening it. If hot Pyroclor has to be handled, a respirator with an active carbon canister should be worn. Disposal of empty drums and waste Pyroclor Empty drums should not be re-used for anything except scrap Pyroclor. Unwanted empty drums should be dis posed of by a specialised waste disposal contractor familiar with PCB's who will crush the drums and bury them on an approved toxic dump in accordance with local regulations. Handling of Pyroclor in bulk will minimise the problems associated with handling of drums. Waste Pyroclor should be disposed of by special high temperature incineration at 1000 'C minimum with a residence time of 1.5 seconds or longer or alternatively by a method conforming to local regulations. Care must be exercised during such disposal and (he ultimate use of Pyroclor to avoid pollution, particularly of sewers and waterways. 11 Glossary of Terms O o v) z o The following glossary of terms has been designed as an alphabetical ready-reference guide. Applications Pyrodor-filled transformers have a wide range of applica tions including steel works, glass factories, public buildings, stores and offices. See pages 5-70. "Uses of Pyroclor-filled Transformers*'. Arcing Arcing will occur beneath the surface of Pyroclor analogous to arcing mineral oil in the event of a major electrical break down. However, the only gaseous product of the decom position of Pyroclor by electric arc is hydrogen chloride which is non-explosive and non-flammable. This compares with the production of hydrogen by arcing under the surface of mineral oil. However, whereas the hydrogen produced with mineral oil tends to cool the arc, the hydrogen chloride produced with Pyroclor does not have this effect and arcing would tend to persist rather longer with Pyroclor than with mineral oil. In the event of small transient arcs taking place, the small quantities of hydrogen chloride which would affect the electrical properties of Pyroclor are absorbed by a gas scavenger which is dissolved in the liquid, but this gas scavenger is not designed to cope with the large quantities of gas produced in the event of a major internal fault. Askarel An askarel is defined as a liquid which is itself fire resistant and does not produce under arc conditions or thermal decomposition mixtures of gases which are themselves explosive or flammable. Askerel is a generic term for a group of fire resistant pro ducts used as electrical insulating media. Breathers Where breather transformers are filled with Pyroclor the silica gel breather must be regularly maintained to prevent it becoming water saturated and allowing entry of moisture into the transformer. The fluid in such units should be regularly inspected. {See External Contamination page 68.) Conservator If a breather unit is used it would be normal also to use a conservator to prevent loss of the volatile component of the Pyroclor through the breather. 79 Class A Pyrodor was developed for this class of insulation. Compatibility of Materials Pyrodor is a natural plasticiser for a variety of resins and plastics normally used in oil-filled transformers. If polar, these materials ionise to a greater extent in Pyrodor and so increase dielectric losses. Cost Although Pyrodor itself is more expensive than mineral oil and the basic cost of a Pyroclor-filled transformer is still about 30/;', greater than that of its oil-filled counterpart, the installed cost can be significantly less as a result ofecono mies which can be made in installation. No fire-fighting equipment, firewalls, pebble drains, etc., are required. Siting Pyroclor-filled transformers near the load centre reduces L.V. cable runs and maintenance bills are almost entirely eliminated {see pages 48 to 56 for further details on economies). D.C. Resistivity D.C. Resistivity of Pyrodor is lower than that of mineral oil. Thus a low resistivity reading on a Pyrodor transformer, for example 10 megohms, is quite normal and does not indicate deterioration of the fluid. Such a transformer would be entirely safe for service. A reading of 100 megohms would be expected with an oil-filled transformer. Dielectric Strength The dielectric strength of Pyrodor is equal to, if not better than, best quality mineral oils and is suitable for the entire temperature range of transformer operation. Explosion Risk In the unlikely event of a persistent arc beneath the surface of Pyrodor owing to a major insulation breakdown the tank could be split by the pressure increase due to generation of gases. Pressure relief \alves or bursting discs are usually 80 incorporated to safeguard against this possibility. In an oil-filled transformer there is the added possibility of explosion due to ignition of hydrogen evolved during arcing. Only non-explosive gases are evolved w hen Py rodor is arced. Filling Pyrodor in drums or in bulk is ready for filling trans formers directly. Filling of Pyrodor transformers is best carried out indoors on a dry day and care should be taken to seal the transformers as quickly as possible afterwards to present ingress of moisture. Fire Resistance Askarels are the most widely used fire-resistant transformer coolant and installations can safely be made in areas where fire risk is considerable, especially indoors. Gases Phosgene and chlorine are NOT formed as decomposition products of Pyrodor. The main decomposition product is hydrogen chloride. Handling Precautions See page 77. Heat Transfer The heat transfer characteristics of Pyrodor are similar to those of mineral oil. Hydrolysis Pyrodor is resistant to attack by water; although water will dissolve in Pyrodor and naturally affect its dielectric properties. At room temperature the maximum solubility of water in Pyrodor is about 100 parts per million and Pyrodor normally contains less than 30 parts per million. Insurance In some countries fire insurance premiums can be reduced with Pyroclor-filled transformer installations. HONS 0 7 7 0 6 6 Installation There is no British Code of Practice covering the installation of askarel-filled transformers. Reference, however, may be made to the Canadian Code of Practice and the National Electric Code of the American Standards Association (1956) Article 450. Section 4522. page 156. L.V. Cable Runs Pyroclor-filled transformers can be installed at the load centre and long runs of expensive low-voltage cable are reduced. See "Cost Savings using Pyroclor-filled Trans formers'*, pages 48-56. Load Centring Details of cable economies due to load centring Pyroclorfilled transformers are shown on pages 48-56. Maintenance A properly designed, scaled Pyroclor-filled transformer needs no maintenance. Unsealed transformers require inspection. See page 70. Megger Readings It is frequently found that megger readings taken on Pyroclor-filled transformers are much lower than those on their oil-filled counterparts. This is a reflection of the very much lower d.c. resistivity of Pyroclor compared with mineral oil. Noise Pyroclor-filled transformers are quiet in operation because of the effective dampening of core noise by the high density coolant. Over-Voltage Pyroclor-filled transformers can be installed where over voltages due to lightning or switching surges may occur. Oxidation Pyroclor has exceptional resistance to oxidation. If an askarel-filled transformer is operated under normal con ditions the fluid need not be changed or filtered during the life of the transformer, page 64. Permittivity Compared with the permittivity of mineral oil that of Pyroclor is much closer to the value for cellulose, leading to greater uniformity of stress in impregnated press board and paper windings. Reliability Properly designed and installed, askarel-filled transformers will give trouble-free service foraminimum of 30 wars. Since their introduction in 1932 the manufacturers report finding the overall failure rate to be less than 0.5% for all units under test and service conditions Refilling Oil Units The replacement of existing oil filling in transformers is not generally recommended since Pyroclor may attack the gaskets and many of the sleeving materials, paints and varnishes commonly used with oil. Accordingly, leakage may occur or electrical breakdown may result. In theory, if all materials could be replaced with Pyroclor resistant materials, then the oil could be replaced by Pyroclor. Sealed Transformers Properly designed, sealed transformers need no maintenance. These are usually hermetically sealed with an air or nitrogen space to allow for expansion. Siting Examples of economies achieved by siting Pyroclor-filled transformers indoor*. close to the load centre, are given on pages 48-56 and are available separately in detail from Monsanto. 81 MOMS 0 7 7 0 6 7 Size Pyroclor-filled transformers are usually a little smaller and more compact than other units and can operate at higher voltages than air-cooled transformers. Solubility Water is slightly more soluble in clean PyToclor than in mineral oil. but solubility in used or unused Pyroclor is much the same (solubility approximately 130 p.p.m. at 30C. as opposed to approximately 90 p.p.m. at 30'C. in new mineral oil). Space Saving Well-sealed transformers can be used in dusty or corrosive atmospheres in such spaces unsuitable for other equipment eg. Pyroclor-filled transformers have been installed close by a battery of blast furnaces. Switchgear Pyroclor is unsuitable for use in switchgear since arcing produces hydrogen chloride gas which in moist atmospheres might cause attack of the metallic parts of the switchgear. Tap Changing On load tap changing beneath the surface of the Pyroclor will result in the formation of hydrogen chloride gas and carbon. It is therefore not recommended. Thermal Stability Pyrodor is thermally stable up to 175C. Small quantities of hydrogen chloride are produced above this temperature but are absorbed by the gas scavenger, preventing attack on the iron core or cellulosic insulation. 82 Toxicity Animal toxicity tests indicate that acute oral toxicity is low but that acute dermal toxicity may be moderate. See page 77. Vapour Pressure The variation of vapour pressure of Pyroclor and Pyroclor ETR with temperature is shown on page 62. Viscosity Pyroclor has been blended to match theviscosity-temperature characteristics of mineral oil (see page 62). Voltages Askarel transformers working at 120 kV have been made, but most work in the region of 11 kV since this is the usual level of distribution voltage. The majority of units, normally working indoors, are found in the range between 50 kVA and 4 MVA. Volume Reduction For successful transformer design using Pyroclor it is desirable to keep the liquid volume to a minimum to save cost. Useful economies can be made with round corner tanks, oval or star-shaped cooling tubes. Dead space fillings such as low resin wood or even glass marbles have also been used. Venting If Pyroclor-filled transformers are installed in confined spaces it is normal to vent the transformer to atmosphere. The vents are dosed by rupture discs. Although there is no Code of Practice in the U.K. for the installation of Pyroclorfilled transformers, this recommendation is in line with the Canadian Code of Practice covering the installation of such transformers. The National Electrical Code of the American Standards Association (1956). Article <50. Section 4522. page 156. also deals with the installation of askarcl-filled transformers. 1'*20(E)W-E-2<6 72) Pr>n**d Ov *dlev Ltd. Lonoo" N'9 4AG MOMS 0 7 7 0 6 8