Document xG7E9Kgky6R5Vjd5Yew9mYOQ

INSTRUMENT FUNCTION OUTLINE TTTLE #4 Surge Tank Temperature Control SHEET 2 OF 5 DEPARTMENT 246 LOOP HUMBER- 031 ' CLASSIFICATION __ TIC-31 2.0 COMPONENT AND CALIBRATION DATA OPERATING DATA MECHANICAL DATA A. TW-31 Thermowell Location: Ground level on Tank 537 B. ' TIC-31 Temp. Indicating Controller Location: l4 1 levels NW of tank 537 ' Air Supply: 20 psig Output: 3-15 psig Action: Inc. temp. ' Dec. output Span: 150OC ` C. TV-31.1 Control Valve Location: l4' level, north of Tank 537 Input: 3- 15 psig Action: Air to close Pails open D. TV-31.2 Control Valve Location: l4' level, north of Tank 537 Input: 3-15 psig Action: Air to open Fails close A. Alloy Engr. Thermowell #510-Vl8 lb" 150# R.F. Fig. Aluminum l8" below thread 3/4" NPT female thread Bulb: x 3 15/16" ID: .510" . ' . . B. Taylor Temp, Ind. Contr, #44lRM113l8 Range: 0 - 150C 25' Inconel capillary Ext.: 30' bendable Prop. Bank: 1-100/ Accuracy: . 1% '. Serial # 1131 IMO: none IPMO: 087 - . , - C. Fisher Gov. Control Valve #657-A li" 150# Fig. carbon steel body 1-5-" 316 SS Micro-Flute trim Teflon packing, skirt-top guiding Serial No.: 4435032 ` " " Seat Ring: 1C2368-3507 S.C. 41-60939 IMO: 45 IPMO: 126 Packing Set: 1R2902-0101 Actuator Size 40 Travel 1-1/8" Valve Plug: 2N5521-000A D. Fisher Gov. Control Valve //667ES l" 150#/''lg. Carbon Steel Body 3/8" 316 SS Micro-form trim Teflon V Packing, skirt-top guiding IMO: 45 ' ` ' ' IPMO: 126 , _ Actuator size 30 Travel 3/4" Split Range: 7-15 psig Range Spring: IFI768 Packing Set: 1R2900-0101 S.C.4l-6l908 Serial No. 4228347 PCB-ARCH-EXT0374031 INSTRUMENT ' FUNCTION OUTLINE , DEPARTMENT246 TJTT.F.'#4 Still Pot Level Control - & Alarm. LOOP NUMBER 1 SHEET ' 1 OF 4 ' CLASSIFICATION WRITTEN BY ___ . DATE 5/b9 REV. BY . ' DATE 028 LICA-28_ ' REV. NO. 1.0 NEED FOR LOOP ' . ' . ' ... This loop is needed to insure that there is a constant level in the still pot and that there will always he un distilled material in the pot available for distillation. 1.1 DESCRIPTION OF LOOP ... 1.1.1 Function . The function of this loop is to control the level of undistilled material in the still pot and to activate a high or low alarm when required. 1.1.2 System Performance Required. The level should be maintained + 5" of set point. 1.1.3 Accomplishment of Function ' . v The level transmitter senses the level in the tank and sends a 3-15 psig air signal to the level indicating controller. The controller compares this signal with a set point and sends a 3-15 psig air signal to a control valve to compensate for variation from set point. The control valve allows either more or less material into the tank dependent upon the signal from the controller. The transmitter also sends an air signal to a dual unit pressure switch which activates a high or low level alarm. PCB-ARCH-EXT0374032 INSTRUMENT FUNCTION OUTLINE TITLE Still Pot Level Control & Alarm SHEET 2 OF DEPARTMENT LOOP NUMBER CLASSIFICATION 246 028 LICA-28 2.0 COMPONENT AND CALIBRATION DATA OPERATING DATA MECHANICAL DATA LT-28 Level Transmitter /}, Fisher Gov. Level Trans. #2500.T-249BP Location:! l4' level, over Tank 511 Air Supply: 20 psig Output: 3-15 psig 4" 150# R.F. Fig. Carbon Steel Body Torque Tube IK 4053-000A 316 SS 1" x 93" Displacer W/l6" Ext. -Displacer 1P7330-316 SS J.C.32-39514 W/Piped & Mtd. Air Set Calibration Pull - 0-3# 802 Zero Setting - Zero Span Setting - .82 IPMO - 127 Serial - * 4464406 (3 LIC-28 Level Indicating Contr. l3 Fischer & Porter Level Ind. Contr. #51-1351ABEC Location: Panel Air'Supply: 20# IAS Range: 0-100 Lin. Output: 3-15 psig Prop Band: 2-500$ Action.: Inc. input Reset Rate: .02 - 5 min. Dec. Output Accuracy: Serial No. 4797A14 IMO:. None IPMO: ' 165 . LV-28 Control Valve ^Fisher Gov. Control Valve #66/-A Location: l4' Level, Tank 511 " Input: 3-15 psig Action: Air to open Fails close over l" 150# Fig. Carbon Steel Body 1" 316 SS Micro-Flute Trim * Teflon Packing: Skirt-Top Guiding IMO: 45 ' IPMO: 126 Valve plug - S.C. 4l-6o4l6 LSA-28 Pressure Switch ^/Barksdale Pressure Switch #D2T-Hl8 Location: Panel Input: 3-15 psig SetPoint: Hi(85$),Lo(l2$) Fct: Hi & Low level alarms Spdt Contact/115 V., 10A. Bronze Diaphragm, IPS Range: 0-l8 psig . Conduit Conn.: NPS Setting: Trips at 4.2# on drop - Trips at 13-8# on rise Stores Code: 44-73246 PCB-ARCH-EXT0374033 PCB-ARCH-EXT0374034 INSTRUMENT FUNCTION OUTLINE , DEPARTMENT 246 TITLE Still Pot Level Control LOOP NUMBER 028 _ '& "Alarm .. . ' SHEET ^ OF ^ ' CLASSIFICATION LICA-28 WRITTEN BYDATE" REV*BYDATE REV.NO. 3-0 OPERATION OF LOOP . 3.1 NORMAL OPERATION ` ' ' . ' The normal operation of this loop is to control the level of. the material in the still pot at a field set point. An alarm will sound when level is high or low. High level is 85" from bottom bend line. Low level is 12" from bottom bend line. Set point is 49$ on controller. 3.1.1 Start Up Instructions . , ' A. Open valves in air line and check air supply to ' loop. B. Check level controller reading against stick measurement or Intermediate Storage Tank readings for accuracy. . . C. Maintain level in tank as per operating . instructions. . 3-1-2 Shut Down Instructions ' A. Put controller on manual and close control valve by moving set point to lowest setting. . B. Close all block valves, in loop. 3-1-3 Manual Operating Instructions A. Put controller on "Manual" set point on 9# air to valvej check level frequently. B. There is no by-pass on LV-23- 3.2 INTERLOCKS None. . 3.3 ABNORMAL OPERATIONS 3-3-1 Air Failure pn/i \LV S LiryVu An air failure to the loop(-w.ill cause the control valvq to fail closed and the level jjj.n the still /potrAvill1 decrer\asC' e. CC* V~ihec\rk "1lm e-ivn--e, l -ff' rSTgiR^tly1 *' m. -r/ ' - v / 3-3-2 Power Failure Loss of power will, cause loss of alarm system. __ IShf M*sujL, PCB-ARCH-EXT0374035 . INSTRUMENT FUNCTION OUTLINE DEPARTMENT 246 ....... ...... INSTRUMENT FUNCTION OUTLINE DEPARTMENT 246 TITLE ' Therminol To #4 Heat Exch . ~ ' Flow ConEroT ~~ LOOP NUMBER____________0 26______ SHEET -4 OF 4 CLASSIFICATION FIC-26 WRITTEN BY ____ DATE___ REV.BY. DATEREV. NO. 3.0 OPERATION OF LOOP 3.1 NORMAL OPERATION . . Set therminol flow as per operating instructions (0-100%). 100% is equal to 200 gpm. Increase in therminol flow will result in larger boil-up, decrease in flow will result in slower boil-up. . 3-1.1 Start Up Instructions Check all air pressures, align manual valves to heat 'exchanger, start therminol pump. 1 3.1.2 Shut Down Instructions Set flow controller to O gpm, close manual valves to heat exchanger. 3.1.3 Manual Operations ' Set flow controller to manual, regulate air pressure to control valve. 3.2 INTERLOCKS None 3.3 ABNORMAL OPERATIONS 3.3.1 Air Failure , Air failure to the loop will cause loss of control, the control valve will close, the flow to heat exchanger will stop. 3.3.2 Power Failure Power failure to the loop will not affect control power failure to therminol pump will cause loss of flow.- PCB-ARCH-EXT0374037 INSTRUMENT FUNCTION OUTLINE , ; DEPARTMENT 24 6 TITLE #4 Still Pot Flow Totalization LOOP NUMBER____ 027 ________ . ; & Alarm . SHEET i OF 4 _ _ CLASS IFICATIONfoa-27 WRITTEN' BY. Brawley DATE 4/28/69 REV. BY DATE REV.NO, 1.0 NEED FOR LOOP . ' This loop is needed to determine .the amount of input to . the tank. This information then determines when the process is' to be temporally terminated and lime added or the tank emptied. 1.1 DESCRIPTION OF LOOP 1.1.1 Function ,, The function of this loop is to count the number of gallons . put into the still pot, and to sound an alarm when a preset amount is reached. 1.1.2 System Performance Required . ' . This system should totalize the final gallon count within + 150 gallons of actual total input and should meter the . flow rate within + 1/2 gpm of actual rate. 1.1.3 Accomplishment of Function The flow meter transmitter operates on a positive displacement principle and sends an electrical pulse to a counter for every . given amount of displacement. The counter receives the pulses from the transmitter and counts one for every ten pulses re ceived. PCB-ARCH-EXT0374038 IMSTRUMEMT FUNCTION OUTLINE TITTE #4 sti11 Pot Flow Totalization & kSHEET 2 OP DEPARTMENT LOOP NUMBER. CLASSIFICATION 246 . ..... n?7 _ ; Foa-97 2.0 COMPONENT AND CALIBRATION DATA OPERATING DATA MECHANICAL DATA A. FT-27 Flow Meter Transmitter Location: 14' level, over tank 511l Flow: 6-37 GPM Working Pressure: 30-80 psig Pulses/Gal.: 1 Switch Rating: .2 AMP Totalizer: 5 Digit - Non Reset . 10 Gal./Count B. FQA-27 Flow Batch Totalizer ' Location: Panel Input: 6-37 GPM (Pulses/Min.) Pulse Source: 115 Vac, .5 A. Display: 5 Digits Counting Coil: 115 VDC Contact: SPOT @250 Vac, 2 A. Power Supply: 115 Vac Operating Voltage: DC *Build-in DC rectifier for coil operation A. Brooks Inst. Co. Flow Meter Trans. #94 55-B7C-01-C-111-010 Meter Size: 1" Conn.: 1", 150# Fig. R.F. ASA Material: Housing D Gears , Shaft f 316 SS Flanges ) Bearings: Hard carbon Gasket & Seals: Teflon B. Presin Flow Batch Totalizer #F185 For Repairs: Ship to: Presin Co., Inc. Trap Fails Road Shelton, Conn. 06484 PCB-ARCH-EXT0374039 INSTRUMENT FUNCTION OUTLINE DEPARTMENT ' 246 TITLE #4 Still Pot Flow TotaTi 7,at-inn LOOP NUMBER 027 INSTRUMENT FUNCTION OUTLINE DEPARTMENT______ __246 TITLE #4' Still Pot Flow Totalization LOOP NUMBER______ Q27 SHEET 4 WRITTEN BY ' OF / .. CLASSIFICATION ~ DATE__REV,,BY DATE FQA-27 REV. NO. 3.0 OPERATION OF LOOP ' 3.1 NORMAL OPERATION . The flow integrator is used to measure input to still from intermediate storage tank and sound an alarm when a pre-set amount is reached. 3.1.1 Start Up Instructions . Check electrical supply to loop and manually test alarm . system. Energize feed totalizer. 3.1.2 Shut Down Instructions None . 3.1.3 Manual Operating Instructions None 3.2 INTERLOCKS ' ' ' None 3.3 ABNORMAL OPERATIONS . 3-. 3.1 Air Failure ' No effect on loop. 3.3.2 Power Failure Loss of control of measurement of material to still pot. PCB-ARCH-EXT0374041 INSTRUMENT FUNCTION OUTLINE DEPARTMENT____ _____246________ ___ __ TITLE Therminol To #4 Heat E-xch . LOOP NUMBER__ --026 --------- -- i SHEET 1 Flow Control 'OF 4 ' CLASSIFICATION FIC-26_______ _ WRITT'lfr^Y"-5^^1 eY__ DATE4728/69 REV.BY ___ DATE__________REV. NO. 1.0 NEED FOR LOOP This loop is needed to heat process stream to a temperature such that the correct boiling process occurs in the constant pressure still pot. . 1.1 DESCRIPTION OF LOOP . 1.1.1 Function The function of this loop is to control the flow of the hot therminol. 1.1-2 System Performance Required . The flow rate should be maintained + 5 *GPM of set point. 1-1-3 Accomplishment of Function , The rate of flow of therminol is determined by an orifice plate and flow transmitter. The transmitter sends a 3-15 psig air signal to a flow indicating controller which compares this signal to a set point and sends a corresponding 3-15 psig air signal to a control valve to compensate for variation from set point. PCB-ARCH-EXT0374042