Document xG7E9Kgky6R5Vjd5Yew9mYOQ
INSTRUMENT FUNCTION OUTLINE TTTLE #4 Surge Tank Temperature Control
SHEET
2
OF
5
DEPARTMENT
246
LOOP HUMBER-
031 '
CLASSIFICATION __ TIC-31
2.0
COMPONENT AND CALIBRATION DATA
OPERATING DATA
MECHANICAL DATA
A. TW-31 Thermowell
Location: Ground level on Tank 537
B. ' TIC-31 Temp. Indicating Controller
Location: l4 1 levels NW of
tank 537 '
Air Supply: 20 psig
Output: 3-15 psig
Action: Inc. temp.
' Dec. output
Span: 150OC
`
C. TV-31.1 Control Valve
Location: l4' level, north
of Tank 537
Input: 3- 15 psig
Action: Air to close
Pails open
D. TV-31.2 Control Valve
Location: l4' level, north of Tank 537
Input: 3-15 psig Action: Air to open
Fails close
A. Alloy Engr. Thermowell #510-Vl8
lb" 150# R.F. Fig. Aluminum
l8" below thread
3/4" NPT female thread
Bulb:
x 3 15/16"
ID: .510"
.
'
. .
B. Taylor Temp, Ind. Contr, #44lRM113l8
Range: 0 - 150C
25' Inconel capillary
Ext.: 30' bendable
Prop. Bank: 1-100/
Accuracy: . 1%
'.
Serial # 1131
IMO: none
IPMO: 087
-
. ,
-
C. Fisher Gov. Control Valve #657-A
li" 150# Fig. carbon steel body
1-5-" 316 SS Micro-Flute trim
Teflon packing, skirt-top guiding
Serial No.: 4435032
` "
"
Seat Ring: 1C2368-3507 S.C. 41-60939
IMO:
45
IPMO:
126
Packing Set: 1R2902-0101
Actuator Size 40 Travel 1-1/8"
Valve Plug: 2N5521-000A
D. Fisher Gov. Control Valve //667ES
l" 150#/''lg. Carbon Steel Body
3/8" 316 SS Micro-form trim
Teflon V Packing, skirt-top guiding
IMO: 45
'
` '
'
IPMO: 126
,
_
Actuator size 30 Travel 3/4"
Split Range: 7-15 psig
Range Spring: IFI768
Packing Set: 1R2900-0101 S.C.4l-6l908
Serial No. 4228347
PCB-ARCH-EXT0374031
INSTRUMENT ' FUNCTION OUTLINE
, DEPARTMENT246
TJTT.F.'#4 Still Pot Level Control
-
& Alarm.
LOOP NUMBER 1
SHEET '
1
OF 4
'
CLASSIFICATION
WRITTEN BY ___ .
DATE 5/b9 REV. BY .
' DATE
028
LICA-28_ ' REV. NO.
1.0 NEED FOR LOOP '
. '
.
'
...
This loop is needed to insure that there is a constant level in the still pot and that there will always he un distilled material in the pot available for distillation.
1.1 DESCRIPTION OF LOOP
...
1.1.1 Function
.
The function of this loop is to control the level of undistilled material in the still pot and to activate a high or low alarm when required.
1.1.2 System Performance Required.
The level should be maintained + 5" of set point.
1.1.3 Accomplishment of Function
'
.
v
The level transmitter senses the level in the tank and sends a 3-15 psig air signal to the level indicating controller. The controller compares this signal with a set point and sends a 3-15 psig air signal to a control valve to compensate for variation from set point. The control valve allows either more or less material into the tank dependent upon the signal from the controller. The transmitter also sends an air signal to a dual unit pressure switch which activates a high or low level alarm.
PCB-ARCH-EXT0374032
INSTRUMENT FUNCTION OUTLINE
TITLE
Still Pot Level Control & Alarm
SHEET
2
OF
DEPARTMENT LOOP NUMBER CLASSIFICATION
246 028 LICA-28
2.0
COMPONENT AND CALIBRATION DATA
OPERATING DATA
MECHANICAL DATA
LT-28 Level Transmitter
/}, Fisher Gov. Level Trans. #2500.T-249BP
Location:! l4' level, over Tank 511
Air Supply: 20 psig Output: 3-15 psig
4" 150# R.F. Fig. Carbon Steel Body
Torque Tube IK 4053-000A
316 SS 1" x 93" Displacer W/l6" Ext.
-Displacer 1P7330-316 SS J.C.32-39514
W/Piped & Mtd. Air Set
Calibration Pull - 0-3# 802
Zero Setting -
Zero
Span Setting -
.82
IPMO -
127
Serial - *
4464406
(3 LIC-28 Level Indicating Contr. l3 Fischer & Porter Level Ind. Contr. #51-1351ABEC
Location: Panel
Air'Supply: 20# IAS
Range: 0-100 Lin.
Output: 3-15 psig
Prop Band: 2-500$
Action.: Inc. input
Reset Rate: .02 - 5 min.
Dec. Output
Accuracy:
Serial No. 4797A14
IMO:.
None
IPMO:
' 165
.
LV-28 Control Valve
^Fisher Gov. Control Valve #66/-A
Location: l4' Level,
Tank 511 " Input: 3-15 psig Action: Air to open
Fails close
over
l" 150# Fig. Carbon Steel Body
1" 316 SS Micro-Flute Trim *
Teflon Packing: Skirt-Top Guiding
IMO:
45
'
IPMO:
126
Valve plug - S.C. 4l-6o4l6
LSA-28 Pressure Switch
^/Barksdale Pressure Switch #D2T-Hl8
Location: Panel
Input: 3-15 psig SetPoint: Hi(85$),Lo(l2$) Fct: Hi & Low level alarms Spdt Contact/115 V., 10A.
Bronze Diaphragm,
IPS
Range: 0-l8 psig .
Conduit Conn.:
NPS
Setting: Trips at 4.2# on drop
-
Trips at 13-8# on rise
Stores Code: 44-73246
PCB-ARCH-EXT0374033
PCB-ARCH-EXT0374034
INSTRUMENT FUNCTION OUTLINE
,
DEPARTMENT
246
TITLE
Still Pot Level Control
LOOP NUMBER
028
_
'& "Alarm
.. .
'
SHEET
^ OF
^
'
CLASSIFICATION LICA-28
WRITTEN BYDATE"
REV*BYDATE
REV.NO.
3-0 OPERATION OF LOOP
.
3.1 NORMAL OPERATION
`
'
' .
'
The normal operation of this loop is to control the level
of. the material in the still pot at a field set point.
An alarm will sound when level is high or low. High
level is 85" from bottom bend line. Low level is 12"
from bottom bend line. Set point is 49$ on controller.
3.1.1 Start Up Instructions
. , ' A. Open valves in air line and check air supply to
'
loop.
B. Check level controller reading against stick
measurement or Intermediate Storage Tank
readings for accuracy.
. .
C. Maintain level in tank as per operating
. instructions.
.
3-1-2 Shut Down Instructions
'
A. Put controller on manual and close control valve by moving set point to lowest setting.
. B. Close all block valves, in loop.
3-1-3 Manual Operating Instructions
A. Put controller on "Manual" set point on 9# air to
valvej check level frequently. B. There is no by-pass on LV-23-
3.2 INTERLOCKS
None.
.
3.3 ABNORMAL OPERATIONS
3-3-1 Air Failure
pn/i
\LV S
LiryVu
An air failure to the loop(-w.ill cause the control valvq
to fail closed and the level jjj.n the still /potrAvill1
decrer\asC' e. CC* V~ihec\rk "1lm e-ivn--e, l -ff' rSTgiR^tly1 *' m.
-r/ ' - v
/
3-3-2 Power Failure
Loss of power will, cause loss of alarm system.
__ IShf M*sujL,
PCB-ARCH-EXT0374035
. INSTRUMENT FUNCTION OUTLINE
DEPARTMENT
246
....... ......
INSTRUMENT FUNCTION OUTLINE
DEPARTMENT
246
TITLE ' Therminol To #4 Heat Exch .
~ '
Flow ConEroT ~~
LOOP NUMBER____________0 26______
SHEET
-4 OF
4
CLASSIFICATION
FIC-26
WRITTEN BY
____ DATE___
REV.BY. DATEREV. NO.
3.0
OPERATION OF LOOP
3.1 NORMAL OPERATION
.
.
Set therminol flow as per operating instructions (0-100%).
100% is equal to 200 gpm. Increase in therminol flow
will result in larger boil-up, decrease in flow will
result in slower boil-up.
.
3-1.1 Start Up Instructions
Check all air pressures, align manual valves to heat 'exchanger, start therminol pump.
1 3.1.2 Shut Down Instructions
Set flow controller to O gpm, close manual valves to heat exchanger.
3.1.3 Manual Operations
'
Set flow controller to manual, regulate air pressure to control valve.
3.2
INTERLOCKS
None
3.3 ABNORMAL OPERATIONS
3.3.1 Air Failure
,
Air failure to the loop will cause loss of control, the control valve will close, the flow to heat exchanger will stop.
3.3.2 Power Failure
Power failure to the loop will not affect control power failure to therminol pump will cause loss of flow.-
PCB-ARCH-EXT0374037
INSTRUMENT FUNCTION OUTLINE ,
;
DEPARTMENT
24 6
TITLE #4 Still Pot Flow Totalization LOOP NUMBER____ 027 ________
.
;
& Alarm
.
SHEET
i OF
4
_ _
CLASS IFICATIONfoa-27
WRITTEN' BY. Brawley DATE 4/28/69 REV. BY
DATE
REV.NO,
1.0 NEED FOR LOOP
.
'
This loop is needed to determine .the amount of input to .
the tank. This information then determines when the process
is' to be temporally terminated and lime added or the tank
emptied.
1.1 DESCRIPTION OF LOOP
1.1.1 Function
,,
The function of this loop is to count the number of gallons . put into the still pot, and to sound an alarm when a preset
amount is reached.
1.1.2 System Performance Required . '
.
This system should totalize the final gallon count within
+ 150 gallons of actual total input and should meter the
. flow rate within + 1/2 gpm of actual rate.
1.1.3 Accomplishment of Function
The flow meter transmitter operates on a positive displacement
principle and sends an electrical pulse to a counter for every
.
given amount of displacement. The counter receives the pulses
from the transmitter and counts one for every ten pulses re
ceived.
PCB-ARCH-EXT0374038
IMSTRUMEMT FUNCTION OUTLINE TITTE #4 sti11 Pot Flow Totalization &
kSHEET
2
OP
DEPARTMENT LOOP NUMBER. CLASSIFICATION
246
.
..... n?7 _ ;
Foa-97
2.0
COMPONENT AND CALIBRATION DATA
OPERATING DATA
MECHANICAL DATA
A. FT-27 Flow Meter Transmitter
Location: 14' level, over
tank 511l
Flow: 6-37 GPM
Working Pressure: 30-80 psig
Pulses/Gal.: 1
Switch Rating: .2 AMP
Totalizer: 5 Digit - Non Reset
.
10 Gal./Count
B. FQA-27 Flow Batch Totalizer ' Location: Panel Input: 6-37 GPM (Pulses/Min.) Pulse Source: 115 Vac, .5 A. Display: 5 Digits Counting Coil: 115 VDC Contact: SPOT @250 Vac, 2 A. Power Supply: 115 Vac Operating Voltage: DC *Build-in DC rectifier for coil operation
A. Brooks Inst. Co. Flow Meter Trans.
#94 55-B7C-01-C-111-010
Meter Size: 1"
Conn.: 1", 150# Fig. R.F. ASA
Material: Housing D
Gears
,
Shaft
f 316 SS
Flanges )
Bearings: Hard carbon Gasket & Seals: Teflon
B. Presin Flow Batch Totalizer #F185
For Repairs: Ship to:
Presin Co., Inc.
Trap Fails Road
Shelton, Conn. 06484
PCB-ARCH-EXT0374039
INSTRUMENT FUNCTION OUTLINE
DEPARTMENT ' 246
TITLE #4 Still Pot Flow TotaTi 7,at-inn LOOP NUMBER 027
INSTRUMENT FUNCTION OUTLINE
DEPARTMENT______ __246
TITLE #4' Still Pot Flow Totalization LOOP NUMBER______ Q27
SHEET
4
WRITTEN BY
' OF /
..
CLASSIFICATION
~ DATE__REV,,BY DATE
FQA-27 REV. NO.
3.0
OPERATION OF LOOP
'
3.1 NORMAL OPERATION
.
The flow integrator is used to measure input to still from
intermediate storage tank and sound an alarm when a pre-set
amount is reached.
3.1.1 Start Up Instructions
.
Check electrical supply to loop and manually test alarm . system. Energize feed totalizer.
3.1.2 Shut Down Instructions
None
.
3.1.3 Manual Operating Instructions
None
3.2
INTERLOCKS
' '
'
None
3.3 ABNORMAL OPERATIONS
.
3-. 3.1 Air Failure
'
No effect on loop.
3.3.2 Power Failure
Loss of control of measurement of material to still pot.
PCB-ARCH-EXT0374041
INSTRUMENT FUNCTION OUTLINE
DEPARTMENT____ _____246________ ___ __
TITLE Therminol To #4 Heat E-xch .
LOOP NUMBER__ --026 --------- --
i
SHEET 1
Flow Control
'OF
4
'
CLASSIFICATION FIC-26_______ _
WRITT'lfr^Y"-5^^1 eY__ DATE4728/69 REV.BY
___ DATE__________REV. NO.
1.0 NEED FOR LOOP
This loop is needed to heat process stream to a temperature
such that the correct boiling process occurs in the constant
pressure still pot.
.
1.1 DESCRIPTION OF LOOP
.
1.1.1 Function
The function of this loop is to control the flow of the hot therminol.
1.1-2 System Performance Required
.
The flow rate should be maintained + 5 *GPM of set point.
1-1-3 Accomplishment of Function
, The rate of flow of therminol is determined by an orifice plate and flow transmitter. The transmitter sends a 3-15 psig air signal to a flow indicating controller which compares this signal to a set point and sends a corresponding 3-15 psig air signal to a control valve to compensate for variation from set point.
PCB-ARCH-EXT0374042