American Society of Heating and Ventilating Engineers Guide, 1925-26
reliable, because as a rule the chimney is designed by an engineer and must be well built to sustain such a heavy load and the height is such as to produce considerable head or force to offset unfavorable weather con ditions, etc. Chimneys in this class produce about 0.009 in. draft per ft. of height in zero weather with 600 deg. in the stack according to the
formula:
where
P = H (TM-)
\ io
*8 /
P = draft pressure in inches of water. H = height of chimney in feet. To = absolute temperature of outside air. rs = absolute temperature of stack gases.
For low-pressure heating boilers, water heaters and warm air furnaces conservative modern practice in the matter of chimney sizes is in accord ance with the_ accompanying schedule, Table 61:
61.Table.
Chimney Sizes
Warm Air
Furnace Capacity
IN Leader
Pipe
Sq. In,
Steam Boiler Capacity Sq. Ft.
OF Radia
tion
Hot
Water Heater Capacity
Sq. Ft. OF
Radia tion
Nominal Dimen
sions
of FireClay
Lining In.
Rectangular Flue
Actual Inside Dimensions
of Fire Clay
Lining In.
Actual Area
Sq. In.
Effec tive
Area Sq. InJ
Round Flue
Inside Diameter
of Lining
In.
Effec tive Area
Sq. In.
Height in Ft. from
Grate
790 590 973 8)4x13
7x11)4 81 70
35
1000
690 1140
900 900 '
1490 1490
13x13 8)4x18
UKxn%
6^x16^
127
no
99 100
10
79
1100 1820
12 113 40
1700
2800
13x18 11)4x16)4 183 156
1940 3200
15 177
2130
3520
18x18 15J4xl5J4 248 195
2480 4090 20x20 . 17)4x17)4 298 234
45
3150 5200
18 254 50
4300 7100
\ 20 314
5000 8250 24x24
21x21
441
4600 7590
20x24* 480 326
55
. 5570 9190
24x24
576 380
60
5580 9200
22 380
6980 11500
24 452 65
7270 12000
24x28
672 468
8700 14400
28x28
784 531
9380 15500
27 573
10150 16750
30x30
900 616
10470 17250
28x32
896 635
11800 19500
30 707 70
14700 24300
33 855
17900 29500
36 1018
Dimensions below are for unlined rectangular flues.
106
American Society of Heating and Ventilating Engineers Guide, 1925-26
Chimneys recommended for larger boilers 15 to 250 hp. are propor tioned in accordance with the report made by a joint Committee of the American Boiler Manufacturers Association and Stoker Manufacturers Association and approved by these organizations. The sizes are given in Table 62)
Table 62. Height of Stack for Average Installations (Sea Level) i . Forced Draft Stokers
Per Cent Rating................................. Draft Furnace....................................... Friction Loss (Boiler)........................ Friction Loss (Breeching)...................
Total Draft Required................... ..... Height of Stack (Ft.)...........................
100 0.15 0.18 0.10 0.43
80
150 . 0.15 0.4
0.10 0.65
112
200 0.15 0.65 0.10 0.90
145
250 0.15 .0.9 0.10 1.15
178
300 0.15 1.20 0.10 1.45
220
Diameter op Chimney in Inches for Horizontal Return Tubular Boilers
Height of Stack in Feet--For Sea Level and 60 DEG. FAHR. OUTSIDE TEMP. ASSUMED FRIC TION Loss in Stack O.lrn. per 100 ft.
Nominal H. P.
15 20 . 25 3Q 35 40 50 60 75 90 100 115 125 150 175 200 210 225 250
100% Rating ..
150% Rating
13 14 14 16 16 18 17 19 18 20 19 21 20 23 21 24 23 26 25 28 26 29 27 31
28 32 30 34 32 36 33 38 34 38 35 40
36 41
200% Rating
17 18 20 21 22 23 25 27 29 31 33 34 35 38 40 43 44 45 47
Draft at Base of Stack
0.12 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65
--
100% Rating
21 26 35 43 52 60 69 78 86 95 104 112
--
150% Rating -
200% Rating
22 28 37 . 46 56 65 74 84 93 102 112 121
25 30 41 51 61 71 81 91 101 111 122 132
--
Data on Which Tables are Based
j Rating............ Efficiency___
100% 150% 200% 65% 65% 63%
Stack Temp, deg.fahr...... .
450 500 550
1
CO,................
8%
9% 10%
Lbs. of Gas............
85 77 73
Average Friction Loss Through Boilers
Per Cent Rating....... .
100
150
200
250
300
Loss Ins., Water............ 0.1to0.3 0.2to0.6 0.3to0.9 0.5tol.4 0.7tol.9
Friction loss through boiler varies according to construction. . For Furnace Draft.--Allow 0.15 for. forced draft. For Natural Draft 0.35 in. or higher should be used depending upon rate of combustion and fuel used.
For Breeching Friction Loss.--Allow 0.05 in. for each right angle bend and 0.1 in. per 100 ft. of length. Lross sectional area should be 20 per cent larger tliau that of 6tack.