CHAPTER 24
1965 Guide And Data Book
Top Side W - m + 2d - 0.625 + 2 X 1.5 3.625 in.
Bottom Side W -- m + 2d * 2.0 + 2 X 0.5 ~ 3.0 in.
Hiring the larger value of W, the area of Zone A is (12 X 3.625)' /144 = 0.302 sq ft. The area of Zone B is 2.0 - 0.302 = 1.698 sq ft.
To determine the area transmittance for Zone A the struc ture within the sone is divided into five sections parallel to the top and bottom surfaces as shown in Fig. 3. The area con ductance C`A of each' section is calculated by adding the area, conductances of its metal'and non-metal paths. The ares con ductances of the sections are converted to area resistances 1/(C A) and added, to obtain in the total resistance of Zone A. These rali*datinnn are shown in the following table.
SocSoo
Arvo X Codtdsnn
C-A
1/fC-AJ - */A
Air (outside, 15 mph)
No. 1, Roofing No. 2, Gypsum
concrete No. 3, Steel No. 3, Gypsum
concrete No: 4, Steel
No. 4, Glass fiber No. 5, Steel
Air, (umde)
0.302 X 6.0
0.302 X 3.0 0.302 X 1.66/1.125
0.052 X 312.0/0.625 0.250 X 1.66/0.625
0.0104 X 312/1.00 0.292 X 0.25/1.00 0.167 X 312/0.125 0.302 X 1.63
1.812 0.552
0.906 1.105 0.445 2.250
26.0 0.664
jo.038 .
3.24 J0.302 ,, 0:073 416.0 0.002
0.493 2.030
Total R/A - 6.279
Area transmittance of Zone A -- A/B - 1/6.279 = 0.159.,
For Zone B, the unit resistances are added and then converted to ana transmittance as shown in the following table.
Section'
Airfoutside, 15 mph) Roofing Gypsum concrete Glass fiber '' Air (inside)
Total resistance of a sq ft,
' Eei&cnce, ft
1/6.0 - 0.17 1/3.0 - 0:33 1.75/1.66 - 1.05 1.00/0.25 - 4.00 1/1.63 - 0.61
= 6.16
Unit transmittance -* l/R -- 0.162
Area transmittance V-A' ` "
'
for Zone B - 1.698 X 0.162 > 0.276
tor Zone A
0.159
Total area transmittance of basic area Transmittance per sq ft 0.435/2.0 " 0.218
-- 0.435
In tests on similar construction, made by the guarded hot box method, one laboratory reported a 17 value of. 0.219 Btu
per (sq ft) (hr) (F deg), and another laboratory reported a fj value of 0.206 Btu per (sq ft) (hr) (F deg).
When the steel is a large proportionof the heat path, as in Example S, the detailed calculations of resistance in sections 3, 4, and 5 of Zone A are not justified. If only the steel were considered, the final result of Example f would be unchanged.
If the steel path is small, such as for a tie rod, the detailed calculations for sections 3, 4, and 5 are necessary.
Caution
A panel with internal metallic structure, bonded on one or both sides to a metal skin or covering, presents special prob lems of lateral heat flow not covered in the foregoing Zone Method.'
Series Heat Flow Through Unequal Areas
A construction may be made up of two or more layers (fiat or of small curvature), of unequal area, separated by an air space and arranged so that heat.flows through the layers in series. The most common such construction is a ceiling and roof combination where the attic space is unheated and unventilated. A combined coefficient based bn the most conven ient area from air inside to air outside ran be calculated from Equation 8.
(8)
The combined coefficient U is the reciprocal of Rt or, U - MRr.
C7 = combined coefficient to be used with A\. Rt * total resistance to aD elements in series. Ui, Ut, , Up = coefficient of transmission of Aj, Ax, ,An
respectively. ai, n*, , n, -- area ratios At/Ai, At/Au * , A,/At, re
spectively.
It should be noted that the overall coefficient should be multiplied by the area Ai to determine the heat loss. Values of Uu U% Vi , Ur should be calculated *nng Equations 1, 2, or 3, and, if any layer contains parallel heat flow paths (i.e., windows or dormers on roofs), Expiation 6 may be used.
In the calculation, the resistance of the air, spaces between layers should be accounted for by assigning one half of an appropriate air space resistance to each of the layers, rather than the conductance of the surface.
OVERALL COEFFICIENTS AND THHR PRACTICAL USE
The values in Tables 2,3, and 4 for component elements and materials were selected by the ASHRAE Technical Com mittee 2.4, Thermal Insulation and Moisture Barriers, as representative. They are based on available published data obtained by the guarded hot plate method (ASTM C177-45) or by the guarded hot box method (ASTM C236-54T). Because there are variations in commercially available ma terials of the same type, not all of thw selected representative values will be in exact agreement with data for individual products. The exact value for a certain manufacturer's ma terial can be secured from unbiased teste or from guaranteed date of the manufacturer.
The most exact method of determining the heat transmis sion coefficient for a given combination of building materials assembled as a building section is to test a representative section in a guarded hot box. However, it ia not practicable to test all the combinations which may be of interest in building' construction. Experience has indicated that V values for many
Design Heat Transmission Coefficients
421
Table 2 .... Surface.Conductances and Resistances for StQI Air
AS aodvefonee rafa** expressed it Bfw pet (hr)
dtg feap <&B)
SECTION S. UMMTT tataMly Vato of Vcrtao Sufacrf ood
Eftecfrr*
of Air Spacet
15 mnh Wind Any (for winter)
7V4^nph Wind Any (forsummer
6.00 0.17 4.000.25
constructions, when calculated by the methods given in this
chapter, using accurate
*
and when corrections an are in good agreement hot box measurements.
Simplified Procedure for Determining U Values
Tables 5 through 17 represent a short cut enabling the engineer to determine and compare values for many modes of ~ construction: The procedure is to determine the U vahie for
the uninsulated construction in Tables 5 through 15; the bene- fit derived from the addition of insulating-materials ts shown
in Table 16 (Part A to Part E). The fipal U value can be cor rected for framing by use of Fig. 4. Additional summer-values for ventilated .and nonventiiated attics are given in Table 17.
This simplified procedure provides a quick means ter the engineer to evaluate carefully the economic considerations in volved in the seWtion nfan insulating material, as adapted to
various building constructions.
Spedal attention must be given to vapor barriers as oute'
lined in Chapters 22 and 23. Moisture from condenration or.
other.'sources materially reduces the heat-flow resistance of
insulation.
alculated for areas between framing. See Fig. 4 if an allowance b
x>Abeir mspaadceeforerstihstwanecfefevcat.lues used are those shown in Table 3,
Air spaces are } in. or more in width. Variations of conductivity with mean temperature are neg
lecCteodr.rections for framingto be made on basis of parallel heat flow through 2 X 4 in. (nominal) studs, 16 in. on centers, the framing covering 15 percent of wall area/as shown in Fig. 4.
Thermal resistance for gypsum board and insulating board apply equally to plain material and to those which may be
decInoraotredderattothceofnadcetnosrey othreontatbhleesjo, ba.n average resistance value
(AvJ2) has been used in sonic tables for types of materials hav
ing approximately the same thermal resistance values. The dif-
foronrA'between the average value and the exact value for any
*--
--------- ---
hi
Values Used in Calculation' of U Value Tables ;
Tables 5 through 15 are based on values given in Table 4.
The following conditions have been used:
_Equilibrium or steady-state heat transfer/ eliminating effects
of heat capacity: Surrounding surfaces at ambient air.temperatures. . . Exterior wind velocity of 15 mph for wwter nnd 7J> mph for
summer.
..............
' ' '.
Surface emissmty of ordinary budding materials 0.90.
Stud space in frame construction not, insulated. (See Table
16 formethod of,correcting for added.insulation.) . .
. In construction involving air spaces^ thc //.-values shown are