Document x5M4X8Knj0aXg5Op00jgEav0b
602
CHAPTER 22
1958 Guide
Table 6. Factobs to Convebt J=B=fl Finned-Tube Steam Ratings to Hot Water Ratings at Temperatures Indicated
Average
Radiator
Temperature
Factor
Average
Radiator Temperature
Factor
Average
.Radiator Temperature
Factor
150 0.45 155 0.49 160 0.53 165 0.57 170 0.61
175 0.65
180 0.69 185 0-73
190 0.78 195 0.82
200 0.86 205 0.91 210 0.95 215 1.00 220 1.05
Btuh per linear foot at specified water flow rates and average water tem peratures.. ;
The rating of a . finned tube unit in an enclosure having a top outlet is
established at a.value not in excess of the test capacity (which is the heat
extracted from the steam or water in the unit under standard test condi
tions). For .finned-tube with other types of enclosures or. covers a per
centage is added for heating effect which varies up to a maximum of 15
percent depending on the height and type of enclosure or cover. The addi
tions made for heating effect must be shown in the manufacturer's litera
ture.
,. ,
' ....
Corrections for Non-Standard Conditions
The heat output of a radiator, convector, baseboard or finned-tube heatdistributing unit is an exponential function of the temperature difference between the air in the room and the heating medium in the room-heating unit, or, expressed as an equation
where
H = c.-<0"
H = heat output, Btu per hour (Btuh).
(1)
Table 7. Correction Factors for Direct Cast-Iron Radiators and Convectors*
Steam Press. (Approx.)
Gage Vacuum In. Hg.
Abe Lb per
Sq In.
Heating
Factors fob Direct Cast-Iron Radiators
Temp F. Steam or
Water
Room Temperature F 80 75 70 65 60 55 50
Factors pob Convectors
Inlet Air Temperature F 80 75 70 65 60 55 50
22.4
20.3 17.7
14.6 10.9 6.5
Lb per Sq In. 1
6 15 27
52
3.7 4.7 6.0 7.5 9.3 11.5
15.6 21 30 42 67
150 2.58 2.36 2.17 2.00 1.86 1.73 1.62 3.14 2.83 2.57 2.36 2.15 1.98 1.84
160 170
180
2.17 2.00 1.86 1.73
1.62 1.52
1.86 1.62
1.44
1.73 1.52
1.35
1.62
1.44 1.28
1.52
1.35 1.21
1.44
1.28 1.15
2.57
2.15 1.84
2.35 1.98
1.71
2.15 1.84
1.59
1.98
1.71 1.49
1.84
1.59 1.40
1.71 1.49 1.32
1.59 1.40 1.24
190 200
1.44 1.35 1.28 1.21
1.28 1.15
1.21 1.10
1.15 1.05
1.10 1.00
1.05 0.96
1.59 1.40
1.49 1.32
1.40 1.24
1.32 1.17
1.24 1.11
1.17 1.05
1.11 1.00
215 1.10 1.05 1.00 0.96 0.92 0.88 0.85 1.17 1.11 1.05 1.00 0.95 0.91 0.87
230 250
270
300
0.96
0.81 0.70
0.58
0.92
0.78
0.68 0.57
0.88
0.76 0.66
0.55
0.85
0.73 0.64
0.53
0.81 0.70 0.62
0.52
0.78 0.68
0.60 0.51
0.76 0.66
0.58 0.49
1.00 9.83 D.7G 9.56
0.95 0.79
0.68 0.54
0.91 0.76
0.65 0.53
0.87 0.73 0.63 0.51
0.83 0.70 0.60
0.49
0.79 0.68
0.58 0.48
0.65 0.56 0.47
* To determine the sixe of a radiator or a convector for a given space, multiply the beat loss of the space in Btu per hour by the proper factor from the above table and select radiator or convector having an equiva lent Btu per hour rating.
An alternate method is to divide the heat loss in Btu per hour by 240 and multiply the result by the proper factor from the above table and select radiator or convector having an equivalent square foot rating.
To determine the heating capacity of a radiator or. a convector under conditions other than the basic ones with the heating medium at a temperature of 215 F, and the room temperature at 70 F in the case o>- * radiator, and the inlet air temperature at 65 F in the case of a convector. divide the heating capacity at toe basic rating conditions by the proper factor from the above table.
Radiators, Convectors, Baseboard and Finned Tube Units
603
c = a constant determined by test from Equation 1.
t, = average temperature of heating medium, Fahrenheit. For hot water the arithmetical average of the entering and leaving water temperatures is used.
f = room air temperature, Fahrenheit. Air temperature 60 in. above the floor is generally used for radiators while the entering air temperature is used for all other types of heating units.
n = an exponent which equals 1.3 for cast-iron radiators, 1.4 for baseboard ra diation, and 1.5 for convectors. For finned-tube units n varies with both air and heating medium temperatures. Correction factors to convert out puts at standard rating conditions to outputs at other conditions are given in Tables 6, 7, and 8.
Table 8. Correction Factors for Finned-Tube and Baseboard Radiation*
Steam Pressure
Approx
Heating Medium
Factors fob Finned-Tube
Factors fob Baseboard
Gage Abe Steam
Inlet Air Temperature, F
Inlet Air Temperature. F
Vac- Lb
uum per
In. Hg Bq In.
80 75 70 65 60 55 50 80 75 70 65 60 55 50
22.4 3.7 20.3 4.7 17.7 6.0 14.6 7.5 10.9 9.3
6.5 11.5
eq in. i 15.6 6 21 15 30 27 42 iy'Z 67
150 2.80 2.50 2.20 1.95 1.81 1.67 1.54 2.86 2.61 2.38 2.20 2.03 1.89 1.76 160 2.34 2.14 1.94 1.75 1.62 1.50 1.37 2.38 2.20 2.03 1.89 1.76 1.64 1.56 170 2.01 1.86 1.70 1.56 1.46 1.36 1.26 2.03 1.89 1.76 1.64 1.54 1.44 1.38 180 1.76 1.65 1.53 1.42 1.32 1.24 1.15 1.76 1.64 1.55 1.44 1.38 1.29 1.23 190 1.53 1.45 1.36 1.28 1.20 1.12 1.03 1.54 1.44 1.37 1.29 1.22 1.16 1.09 200 1.38 1.31 1.24 1.16 1.09 1.02 0.95 1.38 1.29 1.23 1.16 1.09 1.05 1.00
215 1.17 1.12 1.06 1.00 0.95 0.90 0.85 1.16 1.10 1.06 1.00 0.95 0.92 0.88 230 1.00 0.97 0.93 0.90 0.86 0.82 0.78 1.00 0.96 0.92 0.88 0.84 0.81 0.77 250 0.88 0.85 0.82 0.78 0.75 0.71 0.67 0.86 0.82 0.79 0.76 0.73 0.70 0.68 270 0.75 0.73 0.70 0.68 0.65 0.62 0.59 0.73 0.70 0.68 0.66 0.63 0.61 0.59 300 0.62 0.60 0.58 0.56 0.54 0.52 0.50 0.58 0.57 0.55 0.53 0.52 0.51 0.49
To determine the heating capacity under conditions other than the basic onee with the heating memum at a temperature of 215 F, and the inlet air temperature at 65 F, divide the the heating capacity at the Oaaic rating conditions by the proper factor from the above table.
Enclosure, Paint, Humidity Effect
The general effect of an enclosure placed about a direct radiator is to restrict the air flow, and diminish the proportion of output due to radiation. Enclosures of proper design may, however, improve the heat distribution within the room as compared to the heat distribution obtained with an unenclosed radiator.7-9
For a radiator or cast-iron baseboard the finish coat of paint affects the neat output. Oil paints of any color will give about the same results as u"Painted black or rusty surfaces, but an aluminum or a bronze paint will
f m06 heat emitted by radiation. The net effect may be a reduction 0 10 percent or more in the total heat output of the radiator.10- "17
Some commercial enclosures and shields for use on direct radiators are
water pans for the purpose of adding moisture to the air lb 1,16 ^Lm' ^'es^s'3 show that an average evaporative rate of about 0.235 a rarT t ^ (SA ft f water surface) may be obtained from such pans, when 25 An *S s^eam heated and the relative humidity in the room is between
to in * .Percent*- This source of supply of moisture alone is not adequate maintain a relative humidity above 25 percent on a zero day.