Document x5M4X8Knj0aXg5Op00jgEav0b

602 CHAPTER 22 1958 Guide Table 6. Factobs to Convebt J=B=fl Finned-Tube Steam Ratings to Hot Water Ratings at Temperatures Indicated Average Radiator Temperature Factor Average Radiator Temperature Factor Average .Radiator Temperature Factor 150 0.45 155 0.49 160 0.53 165 0.57 170 0.61 175 0.65 180 0.69 185 0-73 190 0.78 195 0.82 200 0.86 205 0.91 210 0.95 215 1.00 220 1.05 Btuh per linear foot at specified water flow rates and average water tem peratures.. ; The rating of a . finned tube unit in an enclosure having a top outlet is established at a.value not in excess of the test capacity (which is the heat extracted from the steam or water in the unit under standard test condi tions). For .finned-tube with other types of enclosures or. covers a per centage is added for heating effect which varies up to a maximum of 15 percent depending on the height and type of enclosure or cover. The addi tions made for heating effect must be shown in the manufacturer's litera ture. ,. , ' .... Corrections for Non-Standard Conditions The heat output of a radiator, convector, baseboard or finned-tube heatdistributing unit is an exponential function of the temperature difference between the air in the room and the heating medium in the room-heating unit, or, expressed as an equation where H = c.-<0" H = heat output, Btu per hour (Btuh). (1) Table 7. Correction Factors for Direct Cast-Iron Radiators and Convectors* Steam Press. (Approx.) Gage Vacuum In. Hg. Abe Lb per Sq In. Heating Factors fob Direct Cast-Iron Radiators Temp F. Steam or Water Room Temperature F 80 75 70 65 60 55 50 Factors pob Convectors Inlet Air Temperature F 80 75 70 65 60 55 50 22.4 20.3 17.7 14.6 10.9 6.5 Lb per Sq In. 1 6 15 27 52 3.7 4.7 6.0 7.5 9.3 11.5 15.6 21 30 42 67 150 2.58 2.36 2.17 2.00 1.86 1.73 1.62 3.14 2.83 2.57 2.36 2.15 1.98 1.84 160 170 180 2.17 2.00 1.86 1.73 1.62 1.52 1.86 1.62 1.44 1.73 1.52 1.35 1.62 1.44 1.28 1.52 1.35 1.21 1.44 1.28 1.15 2.57 2.15 1.84 2.35 1.98 1.71 2.15 1.84 1.59 1.98 1.71 1.49 1.84 1.59 1.40 1.71 1.49 1.32 1.59 1.40 1.24 190 200 1.44 1.35 1.28 1.21 1.28 1.15 1.21 1.10 1.15 1.05 1.10 1.00 1.05 0.96 1.59 1.40 1.49 1.32 1.40 1.24 1.32 1.17 1.24 1.11 1.17 1.05 1.11 1.00 215 1.10 1.05 1.00 0.96 0.92 0.88 0.85 1.17 1.11 1.05 1.00 0.95 0.91 0.87 230 250 270 300 0.96 0.81 0.70 0.58 0.92 0.78 0.68 0.57 0.88 0.76 0.66 0.55 0.85 0.73 0.64 0.53 0.81 0.70 0.62 0.52 0.78 0.68 0.60 0.51 0.76 0.66 0.58 0.49 1.00 9.83 D.7G 9.56 0.95 0.79 0.68 0.54 0.91 0.76 0.65 0.53 0.87 0.73 0.63 0.51 0.83 0.70 0.60 0.49 0.79 0.68 0.58 0.48 0.65 0.56 0.47 * To determine the sixe of a radiator or a convector for a given space, multiply the beat loss of the space in Btu per hour by the proper factor from the above table and select radiator or convector having an equiva lent Btu per hour rating. An alternate method is to divide the heat loss in Btu per hour by 240 and multiply the result by the proper factor from the above table and select radiator or convector having an equivalent square foot rating. To determine the heating capacity of a radiator or. a convector under conditions other than the basic ones with the heating medium at a temperature of 215 F, and the room temperature at 70 F in the case o>- * radiator, and the inlet air temperature at 65 F in the case of a convector. divide the heating capacity at toe basic rating conditions by the proper factor from the above table. Radiators, Convectors, Baseboard and Finned Tube Units 603 c = a constant determined by test from Equation 1. t, = average temperature of heating medium, Fahrenheit. For hot water the arithmetical average of the entering and leaving water temperatures is used. f = room air temperature, Fahrenheit. Air temperature 60 in. above the floor is generally used for radiators while the entering air temperature is used for all other types of heating units. n = an exponent which equals 1.3 for cast-iron radiators, 1.4 for baseboard ra diation, and 1.5 for convectors. For finned-tube units n varies with both air and heating medium temperatures. Correction factors to convert out puts at standard rating conditions to outputs at other conditions are given in Tables 6, 7, and 8. Table 8. Correction Factors for Finned-Tube and Baseboard Radiation* Steam Pressure Approx Heating Medium Factors fob Finned-Tube Factors fob Baseboard Gage Abe Steam Inlet Air Temperature, F Inlet Air Temperature. F Vac- Lb uum per In. Hg Bq In. 80 75 70 65 60 55 50 80 75 70 65 60 55 50 22.4 3.7 20.3 4.7 17.7 6.0 14.6 7.5 10.9 9.3 6.5 11.5 eq in. i 15.6 6 21 15 30 27 42 iy'Z 67 150 2.80 2.50 2.20 1.95 1.81 1.67 1.54 2.86 2.61 2.38 2.20 2.03 1.89 1.76 160 2.34 2.14 1.94 1.75 1.62 1.50 1.37 2.38 2.20 2.03 1.89 1.76 1.64 1.56 170 2.01 1.86 1.70 1.56 1.46 1.36 1.26 2.03 1.89 1.76 1.64 1.54 1.44 1.38 180 1.76 1.65 1.53 1.42 1.32 1.24 1.15 1.76 1.64 1.55 1.44 1.38 1.29 1.23 190 1.53 1.45 1.36 1.28 1.20 1.12 1.03 1.54 1.44 1.37 1.29 1.22 1.16 1.09 200 1.38 1.31 1.24 1.16 1.09 1.02 0.95 1.38 1.29 1.23 1.16 1.09 1.05 1.00 215 1.17 1.12 1.06 1.00 0.95 0.90 0.85 1.16 1.10 1.06 1.00 0.95 0.92 0.88 230 1.00 0.97 0.93 0.90 0.86 0.82 0.78 1.00 0.96 0.92 0.88 0.84 0.81 0.77 250 0.88 0.85 0.82 0.78 0.75 0.71 0.67 0.86 0.82 0.79 0.76 0.73 0.70 0.68 270 0.75 0.73 0.70 0.68 0.65 0.62 0.59 0.73 0.70 0.68 0.66 0.63 0.61 0.59 300 0.62 0.60 0.58 0.56 0.54 0.52 0.50 0.58 0.57 0.55 0.53 0.52 0.51 0.49 To determine the heating capacity under conditions other than the basic onee with the heating memum at a temperature of 215 F, and the inlet air temperature at 65 F, divide the the heating capacity at the Oaaic rating conditions by the proper factor from the above table. Enclosure, Paint, Humidity Effect The general effect of an enclosure placed about a direct radiator is to restrict the air flow, and diminish the proportion of output due to radiation. Enclosures of proper design may, however, improve the heat distribution within the room as compared to the heat distribution obtained with an unenclosed radiator.7-9 For a radiator or cast-iron baseboard the finish coat of paint affects the neat output. Oil paints of any color will give about the same results as u"Painted black or rusty surfaces, but an aluminum or a bronze paint will f m06 heat emitted by radiation. The net effect may be a reduction 0 10 percent or more in the total heat output of the radiator.10- "17 Some commercial enclosures and shields for use on direct radiators are water pans for the purpose of adding moisture to the air lb 1,16 ^Lm' ^'es^s'3 show that an average evaporative rate of about 0.235 a rarT t ^ (SA ft f water surface) may be obtained from such pans, when 25 An *S s^eam heated and the relative humidity in the room is between to in * .Percent*- This source of supply of moisture alone is not adequate maintain a relative humidity above 25 percent on a zero day.