Document x5M2RQEoZGN072veNQ1wD51x1

uonsanto TO Wilson W. Overall - St. Louis June 5, 1969 ; W.i 1 IK; olJarb-lijilCH P.; EtthignbsI ASKAREL-PXLLED ELECTRICAL CABLES) 1 J. U. iBnrdint| . I j.; 1 f 'S Richard Davis ..,! I :';!1 4 .I ` i ;! On June 3, 1969,-1 had -sf*phone conversation with Bbb Pollardy of Un^on Electric Company, hcije in St. Lobi3. Bob Is the Chief-Cable Engineer at Unldm Electric.j j Bob stated that he had not heard of anjj applications where askarel-filled cables had been U5(dd; He thought the reasons were: compatibility with other materials lh the systert toxicity problems; 1 high cost (most important). He quoted a price differential of 30^/gkllon for mitieral oil to $1.60/gallon for askarel. 1 > Most of the oil-filled cable applications at Ifni on 'Electric are what they term as sub-transmission ^>r network circuits, usually 138 KV or below. I r .!;i .i- ..| Bob stated that at one time, UE used asakiearreell! ttVV--aannssffcbrmers throughout their entire system. Howevetf, after an khalyoia of their system and their safety record,! they felt ppat It was not necessary to continue to pay ]the 'prl-mlum] Tor the askarel. Therefore, they changed o/er tb bll where they could. Askarel is used In areas where required,by building codes or where Union Electric t)ilnkt It wovild be a hazard even though it isn't required. . Iritthelf' own sub-stations, they are using mineral oil!. ' )! | : II Bob said that he has seen several askarel transformers blow up and as expected, warm or hot oil' would bo th$ only problem whereas with the oil-filled transformer depending upon the temperature prior to explosion or rupture, vtjho oil would oomc out in flame. However, by controlling ttyi con ditions in which these transformers are located, the safety hazard was considerably reduced. The control) conditions, are sprinkler systems, fire-proof doors,(sumps to catch the oil, etc. \ '' 096381 monS 2- : 'I '' ! : : An Interesting sidelight; when filling the underground cables with the mineral oil, they use. a degassing procedure prior to putting the oil In the pipe. Bob said that this . was done by pulling a vacuum on the oil and then allowing the air to escape. Aa far as equipment is concerned, he stated that they were using some very, old; equipment and they now have very little Use of this equipment because of their low rate of installation Of underground cable. Bob said that present day building codes hormally allow flammable materials to be used under controlled conditions. This is the area In which an oil-filled cable would be classified. Therefore, there is no pressbre being put on by the municipalities and government bodies that control the building codes to use askarel. Bob Pollardy sees no advantage in paying more money for askarel for cables and ..in. his .tenure of. twenty years jof . working with cables', he has seep relatively'.Tew. fires 'caused by flammable qiUtu .Jthati these-Aacibled.4re all underground; therefore, very inaccessible art far las ' i external sources starting a fire. Most ol the breakdowns l [ are electrical shorts because of a breakdown ifrjthe dielectric strength of the fluid. ' ^ I I 1 I. 1 Bob had heard of Pirelli in Europe and knew that, he was working on some new types of cable systemi. However,' he said European and American cable engineering methods Were quite divergent. I would be interested in knowing mohe about Pihejlli'sl work in Europe. My conclusions to date are the in .this ebuntry there is no market at the present time foi an .haknreli-fllled cable; however, in Europe there may be one bfedbu; - ferent governmental regulations, populatic diet local building codes, etc. I would appreciate any information aftrailal lb'i fr Europe concerning this, artdil^vrouTdijbe'glc a information that you think Would be useful ' . ! '. : i I : r /deb Wilsbi MCINS 096382