On June 3, 1969,-1 had -sf*phone conversation with Bbb
Pollardy of Un^on Electric Company, hcije in St. Lobi3. Bob Is the Chief-Cable Engineer at Unldm Electric.j j
Bob stated that he had not heard of anjj applications
where askarel-filled cables had been U5(dd; He thought the reasons were:
compatibility with other materials lh the systert
toxicity problems;
1
high cost (most important).
He quoted a price differential of 30^/gkllon for mitieral
oil to $1.60/gallon for askarel. 1 >
Most of the oil-filled cable applications at Ifni on 'Electric
are what they term as sub-transmission ^>r network circuits,
usually 138 KV or below.
I r .!;i .i- ..|
Bob stated that at one time, UE used asakiearreell! ttVV--aannssffcbrmers
throughout their entire system. Howevetf, after an khalyoia
of their system and their safety record,! they felt ppat
It was not necessary to continue to pay ]the 'prl-mlum] Tor
the askarel. Therefore, they changed o/er tb bll where
they could. Askarel is used In areas where required,by
building codes or where Union Electric t)ilnkt It wovild
be a hazard even though it isn't required. . Iritthelf' own
sub-stations, they are using mineral oil!. ' )! | : II
Bob said that he has seen several askarel transformers
blow up and as expected, warm or hot oil' would bo th$ only
problem whereas with the oil-filled transformer depending
upon the temperature prior to explosion or rupture, vtjho oil
would oomc out in flame. However, by controlling ttyi con
ditions in which these transformers are located, the safety
hazard was considerably reduced. The control) conditions,
are sprinkler systems, fire-proof doors,(sumps to catch
the oil, etc.
\ ''
096381 monS
2-
:
'I '' ! : :
An Interesting sidelight; when filling the underground
cables with the mineral oil, they use. a degassing procedure
prior to putting the oil In the pipe. Bob said that this .
was done by pulling a vacuum on the oil and then allowing
the air to escape. Aa far as equipment is concerned, he
stated that they were using some very, old; equipment and
they now have very little Use of this equipment because
of their low rate of installation Of underground cable.
Bob said that present day building codes hormally allow flammable materials to be used under controlled conditions.
This is the area In which an oil-filled cable would be
classified. Therefore, there is no pressbre being put on by the municipalities and government bodies that control the building codes to use askarel.
Bob Pollardy sees no advantage in paying more money for
askarel for cables and ..in. his .tenure of. twenty years jof
.
working with cables', he has seep relatively'.Tew. fires 'caused
by flammable
qiUtu
.Jthati these-Aacibled.4re
all underground; therefore, very inaccessible art far las ' i
external sources starting a fire. Most ol the breakdowns l [
are electrical shorts because of a breakdown ifrjthe dielectric
strength of the fluid.
'
^ I I 1 I. 1
Bob had heard of Pirelli in Europe and knew that, he was working on some new types of cable systemi. However,' he said European and American cable engineering methods Were quite divergent.
I would be interested in knowing mohe about Pihejlli'sl work
in Europe. My conclusions to date are the in .this ebuntry there is no market at the present time foi an .haknreli-fllled cable; however, in Europe there may be one bfedbu; - ferent governmental regulations, populatic diet local building codes, etc.
I would appreciate any information aftrailal lb'i fr
Europe concerning this, artdil^vrouTdijbe'glc a
information that you think Would be useful
'
.
! '. : i I : r
/deb
Wilsbi
MCINS 096382