Document x5KbME0yzVNGMwK8kgNeZNYYQ
ABSTRACT
This document presents the findings of a study of available wastewater management and treatment technology for the purpose of determining toxic pol lutant effluents concentrations and daily load achievable in three industrial categories: polychlorinated biphenyls (PCBs) manufacturing; capacitor manu facturing; and transformer manufacturing.
All plants in the above categories have PCB discharges to either water ways or sewage treatment plants, under normal operating conditions. All plants have discharges to storm sewers or directly to waterways under heavy rainfall conditions.
Extensive survey of wastewater treatment technologies and cooperative laboratory work with several suppliers of treatment equipment and research facilities has confirmed that carbon adsorption technology is the best current candidate for successful removal of PCBs from the wastewaters. As an alterna tive uv-ozonation was considered. This technology is still in the research stage; however, it offers potential of ccrrplete destruction of PCBs all the
way to CO2' water and HC1.
Another adsorbent technology now in the development stage, AMBERLlTE polymeric adsorbents, has demonstrated a PCBs removed, efficiency roughly equivalent to carbon daring laboratory tests. Further testing is needed with this adsorbent to accurately assess its potentiality.
For scrap oils and burnable solid wastes generated at these plants, high temperature, controlled incineration offers a straightforward method of de struction, whereas scientific landfilling appears to be the best suited mode of disposal for nonbumable contaminated solids.
Zero discharge objectives can be best achieved by eliminating discharge streams and developing recycle systems. All non-contact cooling water vrould be segregated, cooled, and recycled. All other wastewater streams would be pretreated. The portion of the pretreated water which would be used in the plant would be treated with carbon, while the excess water would be
i. DSW 032923
STLCOPCB4016885
insinerated in a specially designed system which would allow for energy recovery.
Supporting data, rationale for the selection of above reocmmended treat ment technologies and associated costs are contained in this report.
DSW 032924 ii.
STLCOPCB4016886
TABLE OF CONTENTS
SECTION I - INTRODUCTION.................................................................................................
1
1.0 OBJECTIVE OF THIS STUDY.............................................................................................1
2.0 SCOPE OF mis STUDY.............................................................................................
2.1 Industry Characterization................................................................. 2.2 Control and Treatment Technologies for PC3s Wastes . . 2.3 Capital and Operating Costs for Selected Treatment
Technologies ........................................................................................
1 2 2
3
3.0 REPORT CONTENT..........................................................................................................
3
SECTION II - SUMMARY AND CONCLUSIONS.............................................
4
SECTION III - RB^iMENDATICNS........................................................................................ 15
SECTION IV - WATER USE AND WASTE CHARACTERIZATION.......................................... 18
1.0 INTRCOUCTICN.....................................'................................................................. 18
2.0 SPECIFIC WATER USES............................................................................................. 18
3.0 INDUSTRY AND PROCESS WASTE CHARACTERIZATION..................................... 19
3.1 Manufacturing Process - Polychlorinated Biphenyls (PCBs) 20
3.1.1 Process Description................................................................. 20
3.1.1.1 PCB Production and Usage ............................ 22
3.1.2 Raw Wastes................................................................................... 3.1.3 Plant Water Usage................................................................. 3.1.4 Wastwater Treatment and Housekeeping...................
24 24 27
3.1.4.1 Treatment Facility for the Effluent from Sauget Complex................................................... 31
3.1.5 Plant Effluents.......................................................................... 31
3.2 Askarel Capacitor ManufacturingIndustry.............................. 32
3.2.1 Askarel Capacitor Manufacturing Plants................. 34
.............
-
3.2.1.1 3.2.1.2 3.2.1.3 3.2.1.4
Askarel Handling................................................... Process Description ................................. . , Raw Wastes................................................................ Water Use.................................................................
36 37 42 42
iii DSW 032925
STLCOPCB4016887
TABLE OF CONTENTS (Con't)
SECTION IV (Con't)
3.2.1.5 Wastewater Treatment...................................... 46 3.2.1.6 Effluent Ccnposition..............................................52
3.3 Askarel Transformer ManufacturingIndustry..............................52
3.3.1 Transformer Manufacturing Plants................................59
3.3.1.1 Askarel Handling.......................................................61 3.3.1.2 Process Description..............................................62
3.3.1.2.1 Assembly and Askarel Filling Procedure for the Distribution and PowerTransformers. ... 62
3.3.1.3 3.3.1.4 3.3.1.5 3.3.1.6
Raw Wastes ................................................................ 68 Water Use. ......................................................................69 Wastewater Treatment..............................................71 Effluent Composition ......................................... 75
SECTION V - SELECTION OF POLLUTANT PARAMETERS............................................................79
1.0 INTRODUCTION....................................................................................................................79
2.0 SIGNIFICANCE AND RATIONALE FOR SELECTION OF POLLUTANT PARAMETERS....................................................................................................................80
2.1 Polychlorinated Biphenyls ................................................................ 80
2.2 Chemical Oxygen Demand (COD).................................................................81
2.3 Fats, Oils and Greases...............................................................................82
2.4 Suspended Solids .............................................................................................82
2.5 Dissolved Solids........................
83
2.6 Other Constituents.............................................................................. . 83
SECTION VI - WASTEWATER TREATMENT TECHNOLOGIES........................................................84
1.0 INTRODUCTION....................................................................................................................84
1.1 Similarities and Contrasts Between PCBs Wastes and Con trol Practices in their Production, and in their Use as Dielectrics.............................................................................................84
1.2 Summary of Waste Managenent ProblemAreas...................................85
1.2.1 1.2.2 1.2.3 1.2.4
Waste Liquid PCBs and Contaminated Scrap Oil . . 85
PCBs in Wastewaters......................................................................86
PCBs Contaminated Solid Wastes ..........................................86
Air Emissions of PCBs...............................
87
iv DSW 032926
STLCOPCB4016888
SECTION VI (Don't)
TABLE OF CONTENTS (Con't) `t
Page
1.3 Summary of Current PCBs Waste Control Practices ....
1.3.1
1.3.2 1.3.3 1.3.4
Control of Waste Liquid PCBs and Contaminated Scrap Oils...............................
Control of PCBs in Wastewaters..................................... Control of Solid Wastes Contaminated with PCBs . Control of Air Enissions of PCBs................................
87
87 88 89 91
2.0 CANDIDATE PCBs WASTE TREATMENT TECHNOLOGIES CONSIDERED ... 92
2.1 Treatment of Waste Liquid PCBs and Contaminated Scrap Oils.............................................................................................................. 93
2.1.1 Incineration . . . . f....................................................... 2.1.2 Sanitary or Scientific Landfill................................
93 95
2.2 Treatment of Wastewaters Containing PCBs............................ 95
2.2.1 Carton Adsorption................................................................ 95
' 2.2.1.1 PCBs Adsorption Testing by Carborundum ' Company ................................................................. 97
2.2.1.2 PCBs Adsorption Testing by ICI-US ... 98 2.2.1.3 PCBs Adsorption Testing by Calgon Corp. 102
. 2.2.1.3.1 Adsorption Treatment of the Wasta^ater.................................105
' 2.2.1.3.2 Reactivation of the Granular Carbon. ..........................................106
2.2.1.3.3 Carbon Treatment .................... 107 2.2.1.3.4 Materials of Construction . . 107
2.2.1.4 Carbon Regeneration Alternatives - Wet
Catalytic Oxidation ..................................... 108
2.2.1.5 Further Applications Data
.........................109
2.2.2 Ultraviolet-Assisted Ozonation . ......................................109
2.2.2.1 Molecular Responses to Ultraviolet
Region Energy.................................................. Ill
-.
2.2.2.2 Ebotodegradaticn of PCBs,......
112
.. . .. 2.2.2.3 Experimental Factors in UV-Assisted
, Ozone Oxidation of PCBs...........................113
' 2.2.2.4 Destruction of PCBs and Refractory
Organics at Houston Research, Inc.. . 114
"" .......2.2.2.4.1 PCBs Destruction Data .... . . ; - -2.2.2.4.2 Operating Data Obtained from
. , Refractory Organics Tests .
114 114
v. DSW 032927
STLCOPCB4016889
TABLE OF CONTENTS (Con't)
2.2.2.5 Destruction of PCBs and Refractory Organics at Vfestgate ResearchOorp. . . 116
2.2.2.5.1 PCBs Destruction Data......................116 2.2.2.5.2 Pilot Scale Tests of Refractory
Organics Decomposition . . . 122
2.2.2.6 2.2.2.7
Laboratory Test Results from AiResearch
Oorp.................................................................................127 Ccmnents on UV-Ozone Tests...............................127
2.2.3 Non-Carbon Adsorbents for PCBs............................................127
2.2.3.1 The Aniberlite XAD Series of Macroreticular Resins............................................................................128
2.2.3.1.1 PCBs Adsorption Testing.... 128 2.2.3.1.2 Process Concept for Resin Ad
sorption of PCBs...............................129
2.3 Treatment of PCBs - Contaminated Solid Wastes.......................130
2.3.1 Incineration.........................................................................
130
2.3.2 Sanitary Landfill........................................................................132
2.4 Treatment of Air Emissions....................................................................132
2.4.1 2.4.2 2.4.3
Condensation Methods...................................................................132 Granular Adsorption Methods.................................................132 Catalytic Oxidation of Organics in Evaporated
Effluents..........................................................................................132
2.5 The Potential for Zero Discharge......................................................133
3.0 RATIONALE AND SELECTIONS OF CURRENTLY RECOMMENDED WASTE TREAT MENT METHODS..................................................................................................................134
3.1 Incineration Reocrtmended for Liquid PCBs and Scrap Oils . 134
3.2 Carbon Adsorption and UV-Assisted Ozonation Recotrmended
for PCBs in Wastewater........................................................................13b
3.3 Incineration and Landfill Reocmended for Contaminated
Solids..................................................................................................................136
3.4 Dry Carbon Filter Adsorption Recommended for Control of
Air Emissions................................................................
136
SECTION VII - COST OF TREATMENT AND CONTROL TECHNOLOGIES.............................138
1.0 SUMMARY................................................................................................................................138
1.1 Plant to Plant Cost Variations...............................
140
DSW 032928
STLCOPCB4016890
SECTION VII - Don't
TABLE OF CONTENTS (Con't)
P4ge
1.2 Activated Carbon Terminal Treatment System............................142 1.3 Costs Based on Volume Flew ................................................................143
2.0 COST REFERENCES AND RATIONALE.........................................................................143
2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10
Interest Costs and Equity Financing Charges .......................143 Time Basis for Costs..............................................................................144 Useful Service Life..............................................................................144 Depreciation................................................................................................144 Capital Costs ................................................................................................144 Annual Capital Costs..............................................................................144 Land Costs.....................................................................................................144 Operating Expenses........................................................................................145 Rationale for Incineration Costs........................................................145 Definition of Levels of Treatment...................................................148
2.10.1 Effect of Varying Effluent PCB Concentrations . . 148 2.10.2 Zero Discharge Definition .... ..................................... 149
3.0 PCB WASTEWATER TREATMENT PLANT DESIGN PARAMETERS AND COSTS . . 150
3.1 Introduction......................................................................................................150 3.2 Pretreatment......................................................................................................154
3.2.1 Equalization and Separation Basin............................... 154
3.2.1.1 Equalization Basin Capital and Operating Cost...............................................................................156
3.2.1.2 Equalization Basin Costs ................................ 156
3.2.2 Multimedia Filtration.................................................................156
3.2.2.1 Filtration Costs ................................................... 160
3.3 Activated Carbon Treatment System for Removal of PCBs Frcm Wastewater.............................................................................................160
3.3.1 Activated Carbon System Design..........................................167
3.3.1.1 Regeneration of Spent Carbon ....................... 175 3.3.1.2 Economic Analysis of Carbon Treatment of
PCB Contaminated Wastewater........................178
3.3.2 UV-Ozonation - Potential Alternative.................................180
3.3.2.1
3.3.2.2 3.3.2.3 3.3.2.4
Description of System Components and
Rationale for Cost Evaluation........................180
Capital Costs.................................................................188
Operating Costs......................
188
Total Treatment System Cost for Zero
Discharge System...................................................200
vii DSW 032929
STLCOPCB4016891
SECTION VII (Con't)
TABLE OF (XWTENTS (Con't)
Page
3.3.3 3.3.4
3.3.2.5 Total Wastewater Treatment Plant Costs . Using Activated Carbon or Ultraviolet
Light Catalyzed Ozonation .......................
Cost of Implementing Carbon Adsorption Treatment for Selected Plants .......................................................
Zero Discharge ....;. ... ........
200
205 212
3.3.4.1 3.3.4.2 3.3.4.3 3.3.4.4 3.3.4.5
Description of Dry Cooling Tower . . . Design Criteria................................................... Capital Costs....................................................... Operating Costs................................................... Cost of "Zero Discharge" for Selected
Plants...........................
212 213 213 213
218
3.3.5 Carparison of "Zero Discharge" with Discharge to Surface Waters .....................................................................
218
3.4 Scrap Oil Incineration ..................................................................... 222
3.5 Solid Waste Incineration.......................................................... 223
3.6 Totail Industry Treatment Costs . ........................................ . 224
APPENDIX A - Plant 106's Position Statement on Daw's XFS-4169 Capacitor Dielectric Liquid
APPENDIX B - PCB Adsorption Testing by XAD-4 Resin
APPENDIX C - Description of Macroreticular Resins frcm Rohn and Haas Co.
APPENDIX D - Non-Carbon Adsorption and Other Research Stage PCB Treatment
Technologies
. ..
. ...
APPENDIX E - Energy Requirement for Various Treatment Options
')
OSW 032930
STLCOPCB4016892
SECTION II SUMMARY AND OCNCLUSICNS The table on the succeeding page gives a quantitative summary of daily FCB waste loads achievable by PCB manufacturer and the two major PCBs users (capacitor and transformer industries) . This information was derived frcm data supplied by these industries and presents estimates of amounts of PCB wastes currently discharged by these industries to the environment via water, land and scrap oil generated and destroyed by these facilities via inciner ation. The results of this study are grouped into three broad categories. First, those dealing with industrial characterization, production, use and emissions. The second group contains those giving an overview of available technologies for treatment of various PCB wastes and the third summarizes the costs associ ated with currently recommended waste treatment methods.
Industrial Characterization 1. The domestic annual production of PCBs in 1974 was 40,466,000 lbs of which approximately 22,000,000 lbs was used by capacitor manufactur ers and 12,000,000 lbs was used by transformer industries. The balance reflects inventory changes and about 5,395,000 lbs of export sales. 2. There are a total of 37 PCB user (capacitor and transformer) plants in the U.S. and one PCBs manufacturer. Of the 38 plants, 10 dis charge their effluents into the water ways while the remainder dis charge PCBs into the sewage treatment plants. All plants in these categories have discharges under heavy rain fall conditions. 3. In addition to air emissions, there are three types of waste materi als generated at these plants that require treatment and proper handling in order to minimize the PCB entry into the environment. These are:
4 DSW 032931
STLCOPCB4016893
PCB Manufacturer Capacitor Industries Transformer Industries
TABLE 1 SUWftBY CF WASTE LOADS
PCB Discharge in Waterways
or Sewers
3,06 lbs 5.86 lbs
0.17 lbs
Daily Average Land-Destined PCD Wastes
301 lbs
4440 lbs
Unknown
Scrap Oils to
Incineration
1425 lbs 3968 lbs 1750 lbs
5 DSW 032932
STLCOPCB4016894
(a) waste waters containing trace quantities of PCBs (10 to 500 ppb PCBs)
(b) waste PCBs, scrap oils and small quantities of process water highly contaminated with PCBs
(c) burnable and non-bumable solid materials contaminated with PCBs.
Quantitative estimates of these wastes are given in Table 1. 4. The quantities of land-destined wastes originating at the PCBs and
capacitor manufacturing plants were estimated from sparse data sup plied by a few plants. Similar information is not available from the transformer industry. These plants normally drum their solid wastes and have inconplete information on the number of drums ac cumulated annually. Some plants compact their wastes prior to drum ming; others drum their wastes without the benefit of compacting. There are no adequate records to quantify these wastes. At sane plants, the majority of this waste category, however, exists in an enormous total waste volume and probably at relatively low concen trations of PCBs. Further efforts are needed to adequately define these wastes. 5. As yet, very little is being done to control air emissions. The general assumption is that the vapor pressure of PCBs is so low that there will be essentially no air contamination. A few facilities, however, were reported to be filtering and chilling exhaust air frcm PCBs impregnation areas. 6. While the emissions of PCBs to water are expected to decrease due to improved pollution abatement of waterborne wastes, the release of PCBs to air and land is expected to increase. The primary source of increasing air emissions is the increase in the load of incineration materials due to proper handling of wastes which were previously discharged into the waterways or sewers. The quantities of landdestined wastes will also increase due to improved housekeeping measures.
6
DSW 032933
STLCOPCB4016895
7. Since most water used at these facilities is for non-contact cooling purposes, at most plants it is possible to significantly reduce the effluent volume by segregation of wastewaters, recycling and proper housekeeping measures.
8. Most plants have already undertaken PCBs containment programs in order to minimize the entry of PCBs into the environment.
9. There is no commercial scale wastewater treatment for PCBs removal being practiced beyond those of gravity settling of the heavy PCBs layers as a sludge from the bottom of simps or tanks, and skinning of a contaminated oil-layer from the water surfaces.
10. Wastes in PCBs production and PCB wastes in capacitor and transformer manufacturing differ primarily in that the producer generates seme higher boiling, highly chlorinated and polycyclic materials referred as "Montar" that are separated from the Aroclor products and in cinerated. Thus the users of PCBs do not receive the higher boiling materials. Aroclor 1016 is the principal PCB used by capacitor industry; at seme plants Aroclor 1242 and 1221 are also being used in limited quantities. Mineral oil is the principal coolant oil used by the transformer industry. PCB transformer oils (blends of 60 to 70 percent Aroclor 1254 or 1242 and 40 to 30 percent trichloro benzene) are used in only 5-10 percent of these plants' manufacturing volume. However, it has been concluded that the characteristics of the waste materials and effluents generated in all these facilities are, in general, similar enough so that the same kinds of treatment technologies can be utilized for purposes of controlling PCB entry into the environment.
11. Most industrial analysis for PCBs in wastewaters are based cn grab samples and probably have not been more accurate than about - 50% at the one and ten ppb level.
DSW 032934
STLCOPCB4016896
12. Rivers receiving PCBs discharges for a nurrber of years vary greatly in PCBs content with time, apparently depending upon PCB content in storm water runoff and the degree to which bottom sediment is agi tated and suspended.
13. Wherever there have been PCB operations in the past, there are proba bly high concentrations in local waterways bottom sediments.
14. All water streams have greatly lcwered PCBs contents: (a) when solids are removed (b) when dispersed or dissolved oils are removed (c) When the stream comes in contact with a wide variety of solid surfaces (d) when no surface active agents are present.
15. Over the past 45 years, waste PCBs frcm transformer and capacitor operations have been used as local road oiling compounds. Semetimes they were discarded in dumps adjaaent to manufacturing facilities. These are sources of long term leaching of PCBs into waterways, par ticularly with storm water runoff.
Overview of Available Technologies for the Treatment of Various PCB Wastes 1. The most advanced treatment technology in use is incineration. The PCBs manufacturer and one user have plant scale incineration capable of destroying PCBs with very high efficiency. There are at least two ocnmercial services (Rallins Environmental Services and Chemtrol Pollution Services) available, with four incinerator locations in the Eastern and Southern U.S., that destroy PCBs. 2. Incineration is primarily applicable to waste PCBs and scrap oils contaminated with PCBs. All installations have the capacity of "burning" sons contaminated wastewater but, of course, the pro portion of that water to the exothermic oil burning must be kept low.
8 DSW 032935
STLCOPCB4016897
3. Only one ocmnercial incineration service (Rollins) can routinely handle all kinds of PCBs contaminated transformer and capacitor com ponents , sludges, fuller' s earth and other solids, as long as they can be contained in a 47 gallon fiber drum. One PCB user cenpary incinerates transformer internals for purposes of metal recovery.
4. Adequate methodology is available for those plants wishing to con trol the release of PCBs to the environment. Currently available technologies can be applied to the efficient removal of PCBs frcm wastes, or their destruction with the other wastes.
5. The PCBs content of wastewaters., can be-lowered to the 1 ppb level or
belew by carbon adsorption, macroreticular polymer resins and proba
bly other adsorbents.
.
6. Carbon adsorption is currently the best available technology for plant scale treatment of PCBs wastewaters. This conclusion is based on laboratory tests with PCBs in water, and cn the long background of plant scale use of carbon adsorption for removal of organics frcm water.
7. UV-ozonation technology is the best demonstrated method, on the labo
ratory scale, for destruction of PCBs in wastewaters when the streams
occur in large volume, on a relatively continuous flew basis and with
PCBs at the ppb concentration levels. This technology has the po
tential for conversion of PCBs to CX^ t
and HC1.
8. Waste liquid PCBs and scrap oils contaminated PCBs are best handled, as a guideline, by high tenperature (2000-2400F) and long residence tine (2-3 seconds) incineration. However, because of incinerator design variables, the conditions should be chosen in each case to lead to 99.999% destruction.
9. . Incinerators should be equipped with low tenperature alarms, and low tenperature shut down of PCBs feed. They should have high efficiency water scrubbers to prevent HC1 dissemination.
9 DSW 032936
STLCOPCB4016898
10. The best incinerator corrbination for handling wastes from these in dustries is a rotary burner fired by a liquid burner, and followed by an afterburner and scrubber system. The rotary burner can be designed to handle a variety of solid materials, and the liquid burner can handle both the oily and water type wastes.
11. Polymeric resins (AMBERLTIES) were found in laboratory tests to be approximately as effective as carbon in removing PCBs fran water. Further pilot scale testing is needed with this newer (than carbon) technology to accurately assess its potential.
12. Although still in the laboratory stage, catalytic reduction of PCBs offers the possibility of reduction to biphenyl and HCl? and cata lytic oxidation offers a potential for destruction of PCBs to C02 H20 and HCl.
13. Reverse osmosis and ultrafiltration appear to offer a long term po tential for a more maintenance-free, and lcwer operational cost method of separation of PCBs from water. Success is dependent upon specialized membrane development new being carried out at several facilities.
14. It is believed that treatment systems employing activated carbon and possibly UV-ozonation could produce effluents which vrould be at or belcw the limits of detectability for PCBs with currently available analytical techniques. However, since no full scale systems for the treatment of PCBs are in operation at this time, this possibility cannot be confirmed.
15. Unfortunately, no methodology is presently available which can guarantee "zero discharge" to the environment. "Zero discharge" ob jectives can be best met now by eliminating discharge streams and developing recycle systems. All streams that are high in pollutants aM can't be treated for reuse and the rainwater runoffs should be collected and incinerated.
10
DSW 032937
STLCOPCB4016899
Costs Associated with Currently Iteocrmended Waste Treatment Itethods
1. The Table on the succeeding page summarizes the estimated maximum capital and annual costs for the treatment of wastes generated in each industry category. As shewn treatment of all contaminated and potentially contaminated wastewaters, the incineration of scrap oils and the incineration of contaminated solid waste generated in the domestic production and utilization of PCBs is $35.50 million and $9.61 million, respectively. The total annual cost given above represents $0.28 per pound of PCB utilized within the U.S., based on 1974 data.
2. Rainwater contribution to the capital and annual wastewater treatment costs was estimated at 15 and 25 percent, respectively. If significant isolation of the contaminated areas can be achieved these costs will be somewhat reduced.
3. The estimation of total maximum costs anticipated for the manufacturer and users of PCBs was facilitated by preparing cost estimates for each plant site visited during the course of this study and then aggregating to the total industry category on the basis of the percentage of the total industry represented by the visited plants.
4. The treatment system includes settling for solids removal, oil skimming, equalization, fine media filtration, terminal PCB treatment, flow measure ment and sampling, and discharge to surface receiving waters. All sludges and free floating oils are disposed of through incineration. All backwash waters used in the system are recycled back to the gravity settling basin for treatment. All spent adsorbent is destroyed by incineration (far wastewater flews up to 300 gpm) or regenerated on-site for reuse (for waste flows above 300 gpm).
5. An activated carbon system was selected as the terminal PCB treatment method for purposes of estimating the maximum total costs. A potentially viable alternative to carbon adsorption, UV-ozonation, has less well de fined capabilities. Additionally, it is believed that unless tlie UVozonation system can do an equal or better jcb of destroying PCBs at a lower cost, it will not be selected by these industries.
DSW 032938 11
STLCOPCB4016900
TABLE 2
Industry
MAXIMUM PCB INDUSTRY TREATMENT COSTS
Capital Cost
Total Annual Cost
PCB Producer Capacitor Manufacturing Transformer Manufacturing
Total
$ 1,600,000 16,600,000 17,300,000
$35,500,000
$ 595,000 4.200.000 4.815.000
$9,610,000
Toteil Cost Per Pound of PCB utilized
Total Cost Per Pound of PCB discharged to waterways
$ 0.28 $ 2896
Cost Per Pound Produced or Used
$0,015 0.190 0.401
12
DSW 032939
STLCOPCB4016901
6. A carbon adsorption system will remove PCBs from industrial effluents to a level of one ppb or less. It is impractical to design an activated carbon system to obtain a choice of effluent concentrations. The operat ing cost savings for operations at various effluent PCS concentrations are expected to be too small to justify designing carbon adsorbers for PCBs removal at higher than one ppb level.
7. The work performed by Houston. Research and Westgate Research on UVozonaticn indicates that the final concentration is a function of resi dence time, and that UV-ozonation systems can be designed to achieve any desired effluent PCB concentration.
8. Preliminary comparisons of the capital costs of the two systems show at least a 100 percent greater cost for the ozone system over the carbon. When pretreatment costs are combined with treatment, the UV-ozonation process is about 10 percent higher than the carbon process.
9. The design and fabrication of incineration equipment is a highly proprie tary industry, it is believed that any attempt to estimate the cost of such systems on a rational basis would be fruitless. In addition, it seems quite improbable that the smaller PCB user plants would find it ecortmically justifiable to install and operate such a system for de struction of scrap oils and solid wastes contaminated with PCBs. The al ternative to cn-site incineration is contract incineration. For purposes of cost estimation and based on the range of prices quoted by service companies, a flat rate of $0.10 per pound has been assumed for all scrap oil and solid wastes even if they are generated by facilities which have tin on-site incinerator.
10. Contract incineration of large volute, dilute aqueous streams does not seem to be a feasible alternative due to the logistics and transportation cost. For purposes of achieving "zero discharge", capital costs for on site incineration systems were developed. In this case, the accuracy of capital cost estimates are not deemed as critical in view of the high operating cost, primarily fuel cost, associated with this system.
13 DSW 032940
STLCOPCB4016902
11. The least cost "zero discharge" system comprises segregation of waters . used in the plant and cooling and recycling all nan-contact cooling water. All other wastewaters will be routed to a centred system for equalization, settling and fine media filtration. The portion of the water to be utilized in the plant will be subjected to terminal treat ment with carbons, the excess water will be subject to incineration in a specially designed system vhich would iiave the potential of energy recovery.
12. Capital and total annual costs to achieve "zero discharge", based on the system described above, was developed for selected plants. It was con cluded that the total annual oosts for "zero discharge" was about 2.0 to 12.0 times the cost of the carbon system (close loop cooling water case) when rainwater was included.
13. Rainwater runoff is a direct function of the locations' rainfall and run off area. The rain runoff area may or may not be dictated by the size of tlie production facility. This single flew could provide tlie largest flow variation for all production facilities.
14. For the "zero discharge" system the rainwater contribution to the annual wastewater incineration cost is very high. Oonparison of the two "zero discharge" cases i (1) inclusion of rainwater runoff as incinerating material and (2) exclusion of rainwater runoff ] indicates the annual cost of the case 1 to be 2 to 42 times the cost of the case 2 for the various plants under study.
15. As a rough approximation, energy requirement for waste incineration is directly proportional to the hydraulic load of the unit. Water inciner ation is far more energy intensive than scrap oil incineration.
16. Energy requirement of each plant is proportional to the total hydraulic load of the pretreatment and terminal treatment systems.
14 DSW 032941
STLCOPCB4016903
SECTION III REXXU^ENDOTIOMS
There are indications within the PCBs manufacturer and PCBs user indus tries that progress is being made in air and water pollution abatement; how ever, little is being done to assure that the land-destined wastes are dis posed of in an environmentally sound manner. This shortcaning can be attributed to higher costs associated with handling large volumes of wastes further information is needed regarding methods and costs of handling landdestined wastes.
Based on the summary and conclusions cited in Section II, the following reoarnendations are made:
1. Verification sampling should be conducted under controlled conditions in order to define the levels of PCBs discharged into the environ ment with higher degree of accuracy.
2. Promulgation and enforcement of regulations for water pollution abatement fran stationary sources should be continued. Regulations for non-point sources should be initiated to minimize the entry of PCBs into the environment.
3. The use of more biodegradable PCB (Aroclor 1016) in transformer ap plications should be encouraged.
4. New regulations should be developed and enforced to ensure that the land-destined wastes from these facilities are disposed of in an en vironmentally sound manner.
5. Additional data should be developed to adequately characterize solid wastes generated by these three industries and then define methods and costs of handling these wastes.
6. Ihe capability of various incineration facilities should be deter mined for PCBs destruction on a given doctored feedstock using a pre developed and specific test plan. Analysis of available data indi cated that there are differences of opinions as to optimum terrperature level and residence time for PCB incineration.
15 DSW 032942
STLCOPCB4016904
I ow
7. Waste PCBs liquids and scrap oils contaminated with PCBs should be incinerated in approved facilities. New incineration facilities can be installed in cne year.
8. Every effort should be made at each plant to minimize flows. The source of rain runoff contamination should be traced and efforts should be directed to isolate the contaminated areas.
9. Disposable foot coverings and outer garments should be provided at each plant; work clothing should not be allowed to leave the plant other than via solid waste.
10. All spills should be cleaned via rags or floor dry and disposed of in waste drums for incineration. All solid waste should be disposed of in impervious sealed containers.
11. As a housekeeping measure, all sinks in the PCB impregnation and PCBs handling areas should be contained. The wash water frcm these sinks should be properly treated prior to disposal.
12. Wastewaters containing PCBs should be treated by the standard sani tary procedures of settling the sludges and sediments, removal of suspended solids, and skimming to remove floating oils; all prior to specialized terminal treatment for PCBs.
13. Wastewater pretreated as reocrrmended above should then be treated in carbon adsorption columns for removal of PCBs to the ppb levels or. less.
14. Spent carbon should be regenerated in an environmentally sound man ner, or sent to approved incineration along with other PCBs wastes.
15. Waste capacitor and transformer components, absorbent solids, adsor bents, soil, cloth, paper, wood and similar solids contaminated by PCBs should be incinerated in a rotary kiln. The exhaust should be fed to an incineration unit for liquid PCBs, equipped with after burner and scrubber to assure destruction of all PCB vapors. Such facilities can be installed in cne year.
16 OSW 032943
STLCOPCB4016905
16. Exhaust air from PCB impregnation areas should be filtered through absorbent carbon, with chilling, if necessary, to meet clean air quality standards. This equipment can be installed in one yaar.
17. Research on the catalytic oxidation of dilute PCB vapors in air streams should ]>3 conducted to determine the feasibility of low temperature destruction of PCBs by an energy saving process. This method will take more than three years to develop.
18. Research on UV-ozonation should be continued to achieve the follow ing goals: a) determination of optimum conditions for a continuous flow reactor system using actual wastewaters b) conduct on-site demonstration tests using portable equip ment at a PCB using plant, operating on a wastewater slip stream c) design, construct and operate a pilot unit, on actual wastewater, to develop reliable capital and operating cost UV-ozonization treatment technology can be fully developed and in stalled in three years.
19. Pilot scale R&D on reductive dechlorination should be continued to obtain reliable capital and operating costs. This method will proba bly be available for plant scale application in three years time.
20. Laboratory research on catalytic oxidation as a method of PCBs des truction should be initiated. The feasibility of wet catalytic oxidation using suspended commercial catalysts at elevated tempera tures (200-500C) and elevated pressures (500 to 1000 psi) should be determined. This method will take more than five years to develop.
17 DSW 032944
STLCOPCB4016906
. Treatment and housekeeping measures practiced at the facilities and on-going PCB containment programs
. Plant waste effluents found and their composition
3.1 Manufacturing Process - Polychlorinated Biphenyls (PCBs)
3.1.1 Process Description
Monsanto, the sole domestic manufacturer of PCBs, manufactures this chemical in their Sauget, Illinois plant. The basic raw material is biphenyl which is manufactured frcm pure benzene in another Monsanto plant. The PCB manu facturing operation is conducted in two steps. First, biphenyl is chlorinated with anhydrous chlorine in presence of ferric chloride to produce crude PCBs and then the crude PCBs are distilled to obtain the finished product. A schematic flow diagram of this process is given in Figure 3.1.1-1.
The reaction section consists of 6 reactors (3 batch and 3
cascade). Currently Monsanto manufactures four different types of Aroclors (1242,
1016, 1254 and 1221). For the manufacture of any given product, the chlorinator
is charged with proper quantities of biphenyl and catalyst and heated beyond the
melting point of biphenyl. The flew of vaporized chlorine is then started and
the charge is circulated with a pump. Throughout the chlorination, the temperature
is kept above the melting point of the mixture, but below 150C to avoid excessive
sublimation and plugging of the line discharging the hydrogen chloride produced
by the chlorination. The reaction pressure is maintained near atmospheric. The
degree of chlorination is principally determined by the time of contact with anhy
drous chlorine. The contact time varies from 12 to 36 hours for the manufacture
of different Aroclor types.
degree of chlorination is measured by the specific
gravity of mixture or the ball and ring softening point when the product is
viscous.
The vapors from the chlorinator (HC1 containing PCBs) are scrubbed with liquid Aroclor and the gaseous HC1 is sent to another plant at the Sauget complex for purification. The crude product is held at an elevated tem perature and blown with dry air for several hours, after which it is sent to the raw Aroclor storage tank where a'few tenths of 1 percent of alkali is stirred
20 OSW 032945 STLCOPCB4016907
Figure 3.I.MA- PREPARATION OF CRUDE CHLORINATED BIPHENYLS-MONSANTO KRUMMRICH PLANT
r * Am
1CCOOLER
LIQUID
PCS
MCI TO
JL_1 PURIFICATION
BIPHENYL k . r
BATCH
AROCUOR
CHLORINATOR a HC! 6A3
SCRUBBER
CRUDE AROCLOR
1_________
FCI,
Ih-o f^
tVEKT
r-.... -- -- DEMISTER AIR
SCRUBBER
-H,0
ALKALI
BLOWER TANK
RAW AROCLOR STORAGE
TO Figure 3.I.I-IB-DISTILLATI0N OF CRUDE PRODUCTS-MONSANTO KRUMMRICH PLANT
RAW AROCLOR
GAS FIRED RETORT
VACUUM
OVERHEAD
DISTILLATION
*2
SHELL a TUBE CONDENSER
STEAM
1
p--"HgO VAPOR
STEAM JET EJECTORS -- HjO CONDENSATE
AROCLOR 1016
bottoms
r _rAf HCI TO PURIFICATION AIR TO HjO
SCRU83ER (CASCADE REACTORS)
ALKALI
CHLORINATION SECTION
STORAGE
/ DETAILS SAME \
\ AS ABOVE j
NON-CONTACT COOLING WATER
r
1 STILL [(VACUUM )|
L montars to INCINERATION
STEAM
HjO VAPOR
_____ c
t AIR
STEAM JET
EJECTORS -- HjO
CONDENSATE
-AROCLOR 1254
DSW 0 3 2 9 4 6
with the material to react with any remaining hydrogen chloride or ferric chloride. The air from the blower tank is scrubbed with water and vented to the atmosphere
<
through a demister. The raw Aroclor is subsequently batch distilled under reduced
pressure to remove the color, and the traces of hydrogen chloride and ferric chloride. The methods of purification are different for the different types of end products. Raw Aroclor 1254, 1242 and 1221, each are distilled in stills under reduced pressure, achieved via steam jet ejectors; the condensate from the still is the finished product while the bottoms are the Montars which are drummed and sent to incineration.
The distillation section for the 1016 product consists of a gas fired retort and a vacuum distillation tower, The latter is used to allow the separation of the higher chlorinated, less biodegradable ccrpounds from the relatively lower chlorinated and more biodegradable ones. The raw Aroclor (42% chlorinated material) is fed into the reboiler. The vacuum in the tower is main tained at about 100 mg Hg via steam jet ejectors. The steam is partially con densed and the condensate is discharged into the plant discharge sump. The first cut from this tower is recycled back to the retort. At a preset overhead temp erature the 1016 product is collected and sent to the product storage. The high boiling residue from the tower is sent to a subsequent chlorination cycle and the resulting raw Aroclor is distilled in a still. The overhead from this still is the finished product. The bottoms frcm this tower are the Montars, which are sent to incineration.
For special orders, in order to increase electrical resistivity,
the Aroclors are stirred, at an elevated temperature, with a few tenths of 1% of well-dried fuller's earth and then filtered through paper.
All Aroclors are stored at 150F. Steam coils are used on the storage tanks for heating these tanks.
3.1.1.1 PCB Production and Usage The William G. Krummrich plant at the Sauget complex
has an annual design capacity of 48 million pounds chlorobiphenyls. Table 3.1.1.1-1
22
DSW 032947
STLCOPCB4016909
TABLE 3.1.1.1-1 PCB MANUFACTURE & SALES
U.S. production Domestic sales U.S. export sales
(Thousands of pounds)
1974
First Quarter 1975
40,466 34,406
5,395
8,532 . 7,986
1,538
Domestic Sales by PCB Grade
Aroclor 1221 Aroclor 1242 Aroclor 1254 Aroclor 1016
57 6,207 6,185 21,955
10 2,201 2,115
3,660
Predominant Utilization of Aroclors
Aroclor 1221 it 1016 Aroclor 1242 & 1254
.
.
Capacitor applications Transformer applications
23
DSW 032948
STLCOPCB4016910
present data from Monsanto related to production and sales on PCBs for the year 1974 and the First Quarter of 1975. Table 3.1.1.1-2 presents approximate molec ular oonposition of these Aroclors as published by Hutzinger et al (0, Hutzinger, S. Safe and V. Zitko, "Chemistry of PCBs", ORC Press, 1974).
The majority of the PCBs produced in this plant is marketed domestically. At present, almost all Monsanto's PCB production is being used in "closed electric systems" (transformer and capacitor applications).
3.1.2 Raw Wastes The raw wastes from the manufacturing area consist of the
liquor from the scrubber, the condensate from the steam jet ejectors, water used for showers and eye baths, miscellaneous floor wash downs, waste oil collected in drip pans and drums, and montars which are the bottom cut from their stills. The composition and the quantities of the individual waste stream are not monitored. All effluent streams generated in the manufacturing area are directed into the sunps in this area. The waste oil collected in the drip pans and the montars are emptied into 55 gallon drums and sent to incineration.
The raw wastes generated in the incinerator consist of the venturi scrubber liquor and the water phase fron the separator sunp in the incin erator area. The composition of the combined stream is monitored. However, the composition of the individual streams is not known. Non-product PCB discharges are shown in Figure 3.1.2-1. It has been estimated that this plant generates about 25 lbs. of scrap oil and Montar per ton of PCB produced. Additionally the quantities of material sent to landfill approximates to 5.4 lbs. per ton of PCB produced. Additionally, reports that the plant's PCB contribution to air is under 1 lbs/day.
3.1.3 Plant Water Usage On the average, the PCB plant uses a maximum of 388,800 gallons
of water and a maximum of 360,000 lbs. of steam, daily. Water is used for non contact cooling purposes in shell and tube condensers, in a water scrubber, for floor washings, for showers and in eye baths. Steam is used in the steam jet
24 DSW 032949
STLCOPCB4016911
TABLE 3.1.1.1-2 APPROXIMATE MOLECULAR COMPOSITION OF AROCLORS
Chlorobiphenyl Wo Cj^sd C12H8Cl2 C12H7C13 C12"6C14 C12H5C15 C12H4a6 C12H3C17 C12H2a8 C12H1Q9 C12Q10
1221 11 51 32 4 2
0.5 ND ND ND ND ND
Aroclor Type or Grade
(percent canposition)
1242
1254
<0.1
<0.1
1 <0.1
16 0.5
49 1
25 21
8 48
1 23
<0.1
6
ND ND
ND ND
ND ND
1016 <0.1
1 20 57 21
1 <0.1 ND ND ND ND
*ND - Denotes non-detectable
25 DSW 032950
STLCOPCB4016912
STLCOPCB4016913
M
O
V)
5 o ui Ul
Rgure3.t.2-I-NON-PRODUCT PCB DISCHARGES AT MONSANTO'S KRUMMRICH PLANT
VAPOR FROM JET EJECTORS EXHAUSTS FROM THE SCRUBBER---------------SURFACE AREA EVAPORATION (IN GENERAL)-
CONDENSATE FROM STEAM EJECTORS NON-CONTACT COOLING WATER-----------SCRUBBER LIQUOR ----------------------------------
MONTARS BOTTOMS FROM SEPARATOR SUMP------COLLECTION FROM ALL DRIP PANS
RAGS FOR CLEANING----FLOOR DRY---------------------SPENT FILTER PAPERS FULLERS EARTH -----------
a
ejectors and for steam tracing purposes. The plant uses municipal water and purchased steam.
Hie process water frctn this facility consists of the liquor frcm their scrubber and the steam condensates which are discharged in one of the two sumps in the manufacturing area.
Additionally, 273,600 gallons of water are used in the incin erator daily for quenching the hot gases from the fire box. The resulting weak muriatic acid in the quench pot is used in the venturi scrubber and in the packed tower.
Hie type and quantities of water used and discharged at this plant are summarized below.
Water Balance
. Manufacturing Plant
Quantities, GPP______
Process Water in water scrubber misc. floor wash dcwns condensate from steam jet ejectors
Non contact cooling water shcwers, eye bath
condensate from steam tracers Total
Used
14,400 7,200 --
360,000 7,200 --
388,800
Discharged
14,400 7,200
14,400 360,000
7,200 28,800 432,000
Incinerator water used for hot gas quenching water phase from the sump Total
273,600 --
273,600
273,600 14,400
288,000
3.1*4 Wastewater Treatment and Housekeeping
Monsanto reports significant environmental controls at their Krummrich, Sauget plant. Since 1969, they have invested more than 22 man-years of work and millions of dollars in this program. The in-house goals have reduced the PCB discharges into water to about three pounds per day.
27 n DSW 032952
STLCOPCB4016914
A John Zink designed incinerator was erected at Sauget in 197, to safely dispose of PCBs. A schematic flow diagram of this operation is given in Figure 3.1.4-1. Aroclor is steam atomized and fed into the fire box. Natural gas is used for corrbustion and the feed is incinerated at temperature above 2200F at 5 percent excess oxygen with a retention time of 2-3 seconds. The gases are quenched with water and the exhausts from the quench pot are passed through a high-energy venturi scrubber, then through a packed column which is irrigated by the weak muriatic acid originating from the quench pot. Exhausts are then vented to atmosphere through a demister. These exhausts as well as the effluent from the incinerator section are monitored.
In the incineration area, drainage is directed to trenches and piping which flow into a 10,000 gallon underground concrete basin. The water layer from this basin is pumped continuously, combined with the scrubber liquor, metered, monitored and discharged into the sanitary sewers of the Sauget complex and from there it is sent to the East St. Louis municipal sewers. The organic phase from the sump is periodically pumped into waste storage tanks for inciner ation.
Hie incineration unit has a rated design capacity of 10 million
pounds per year. However, since the start of its operation this unit has achieved
a service factor of about 0.60. Monsanto reports that this incinerator can achieve
a maximum of 6 million pounds of capacity annually; the unit is plagued with various
mechanical problems.
Monsanto uses their incinerator to process both their own wastes and as a service to other industries. The service charge for incineration is an average of 5<f per lb. of material, but the cost appears to be increasing.
The incinerator feed is brought into the plant either by truck in 55 gallon sealed drums, by tank trucks or by rail. The drums are opened, picked up by a fork lift and emptied into a concrete pit. The tank truck carrying the waste liquids enters the incinerator area and the liquid waste is then pumped frcm the truck into the pit. Hie material in this pit is periodically pumped via a vertical oertrifugal pump in one of the four 20,000 gallon, each, incinerator waste feed tanks.
28
DSW 032953
STLCOPCB4016915
Figure 3.1.4-1-PROCESS FLOW DIAGRAM OF THE JOHN ZINK INCINERATOR. ' AT MONSANTO'S KRUMMR1CH PLANT
DSW 0 3 2 9 5 4
The rail car is brought into a designated area close to the incinerator site. The material fran the rail car is normally puxped into a long term, 500,000 gallon storage tank. The material from this tank is pumped into the incinerator feed tanks located on the incinerator pad, when required.
Drainage is provided along the rail tracks. These drains enpty into the 10,000 gallon sump located under the incinerator pad.
In the manufacturing area, Monsanto has taken a number of significant steps to prevent loss of PCBs to the environment. Drainage is directed to trenches and piping, and then to one of two concrete 3,000-gallon underground settling basins. This insures PCB containment in case of accidental spill or equip ment failure. Relief valve lines and atmospheric vents are routed through catch tanks, or are redirected to settling basins.
When small quantities of PCBs are collected in the settling basins of the manufacturing area they are later pumped into 55 gallon drums, and eventually incinerated. The overflow from these sumps is combined with the non contact cooling water used at the plant, monitored and then discharged into the Sauget complex's sanitary sewer and from there to the East St. Louis municipal system.
PCBs are packed and shipped in galvanized-steel 55 gallon drums, or in railroad tank cars. All tank cars are top loaded. In the drum filling area spills are cleaned via rags or floor dry and these materials are drummed and sent to landfill located in the town of Sauget.
In the PCB truck or rail car loading area drainage is directed into a small concrete pit. The material accumulated in this pit is periodically pumped into the basins located in the manufacturing area.
Nitrogen blanketing is provided on storage tanks to eliminate any "breathing" of the tanks and resultant PCB escape.
Mist eliminators have been installed in vapor lines to eliminate the possibility of PCBs leaving the manufacturing area through these lines.
30 OSW 032955
STLCOPCB4016917
, Finally, underground sewers have been replaced with above ground sewers, and repaired or combined with others, so that the effluent fran the department can be monitored. In addition, this step will prevent any unknown buildup of PCBs in the sewer systems or any contamination of PCBs into other sewers.
A high housekeeping level is maintained in the plant itself. Housekeeping responsibilities which the operators have assumed are as follows:
' -
. All pumps are checked for leakage on every shift. Drip pans that collect leaks are emptied into scrap PCB drums.
All leaks cure reported and documented so that corrections can be made and settling basins observed.
. "Floor Dry" is used to absorb any PCBs that have spilled or leaked. If it becomes necessary to flush PCBs to the settling basin, a minimum amount of water is used.
. Sampling drums and scrap PCB drums are quickly palletized, labelled and transferred to the in cineration area.
3.1.4.1 Treatment Facility for the Effluent from Sauget Complex
The processing and incineration departments' aqueous effluent enters the plant sewer system, and this system discharges into the Sauget Village waste sewer system. The combined streams then flow to the village primary treatment plant. The village treatment plant is under expansion to a secondary chemical treatment plant, scheduled for 1976 completion.
Additionally, evaluations are being conducted to
include the village plant discharge in a projected regional biological treatment
plant.
'
'
3.1.5 Plant Effluents
This plant has no point source discharge from their operation. There is a single discharge from the manufacturing operation (the combined stream of process and non-contact cooling water) to the main sewer system of the Sauget
31 DSW 032956
STLCOPCB4016918
ocnplex ard there is a second discharge from the incinerator area to the same sewer system. The composition of these streams as reported by Monsanto are as follows:
flow rate, gpd PCBs, ppm PGBs, lbs/day
Effluent from the Manufacturing Operation
432,000
0.75
2.70
Effluent from the Incineration area
288,000
0.15
0.36
It has been reported that these effluents are clear liquids with essentially no suspended solids. The incinerator effluent my contain some amounts of chloride. However, no information is available on the chloride content.
3.2 Askarel Capacitor Manufacturing Industry
Presently 90-95 percent of all capacitors manufactured in the U.S. are of the PCB impregnated type. Two important types of capacitors are phase correctors on pcwer lines and ballast capacitors for fluorescent lighting. Aroclor 1016 is the principal PCB used in this application? at sane plants Aroclor 1242 and 1221 are also being used in limited quantities. The principal types of Aroclor impregnated capacitors and their applications are given below.
A. High Voltage Power
Generally AC capacitors are used to improve the power factor of a circuit. Rawer factor is the ratio of true power in watts to the apparent power as obtained by multiplying the current flowing to the load by the circuit voltage. The power factor correction can be made directly at the load or at utility substations. In the latter case high voltage units will be designed for 4,800 to 13,800 volt service. TO the utility engineer the use of capacitors is purely a matter of economics. The main benefits that result from the use of capacitors are:
1. Reduction of losses associated with the delivery of electrical power to the point of use.
32 OSW 032957
STLCOPCB4016919