CHAPTER 15
1965 Guide And Data Book
growths. Similarly, periodic mechanical removal of dimes
from readily accessible areas reduces ths chemical biocide
requirements and make them more effective.
Chlorine and cblorina-yieiding compounds, such as sodium
hypochlorite and calcium hypochlorite, are among the most
effective biocidal chemicals. However, they are not always
applicable to the control of organic materials in cooling sys
tems. In air washers, for instance, their odor may become
offensive; in wood cooling towers, excessive concentration? of chlorine can cause rapid deterioration of wood construe*
tion, and in metal equipment, higher concentrations of chlo
rine can accelerate corrosion. In systems large enough to
justify equipment for the controlled feeding of chlorine, itB
use may be both safe and economical.
The use of chlorinated phenol? is much safer and usually provides satisfactory control of most slime and algae condi
tions. Certain quaternary ammonium compound? are.also
used as biocides from time to time. They must be used carer
fully, however, because some of them are foam-generating
compounds, and their concentration must be carefully con
trolled, or they must be used in conjunction with foam
suppressors. A recent effective addition to the biocidal chemi
cals is tributyl tin oxide, which can be used .alone or in con junction with quaternary ammonium compounds.
Copper sulfate, which is used widely for the control.of algae
in lakes and reservoirs, should not be used in cooling systems
because the copper can plate out on ferrous surface?, causing accelerated pitting. In alkaline waters, it precipitates out and
is ineffective. Proprietary compounds are available in which
copper is chemically combined in complexes of much greater stability which may be used safely in such equipment and in all waters.
The manner of feeding slime control chemicals to a system
is of great importance. Often, the continuous feeding of low
dosages is neither effective nor economical. Better results may
be obtained by shock feeding larger concentrations to the
system in order to achieve a toxic level of the chemical in the
water for a sufficiently long time to kill the organisms present.
At times, organisms tend to appear to build up an immunity
to the particular chemical being used so that it may be neces
sary to change the biocidal chemical occasionally, in order
to keep the organic growths under control.
Suspended Solids. Suspended solids are undesirable in heat*
ing and cooling water systems. Settling out on heat exchange
surfaces, they can be as effective as scale or slime in reducing
heat transfer. They may accumulate to an extent sufficient
to interfere with water flow, and localized corrosive attack can occur beneath such accumulations. Abrasive dirt particles
can cause excessively rapid wear of such moving parts as pump
shafts and mechanical seals.
.>
Although no chemical treatment procedures are available
for removal of suspended solids particles, corrective meas
ures can be taken in some cases when the potential problem
is sufficiently serious. In larger cooling-towers, the suspended
solids content can be kept to an acceptably low level by the
use of side stream filters. These are ordinary sand filters.a?
other filters through which 1 to 5 percent of the circulating
water is continuously passed-
Before any new system is put into operation, it is important
to flush it thoroughly, to remove as much suspended ma
terial as possible. A chemical detergent rWning is also desir
able in such cases.
1
The protection of localised areas can frequently be carried
out by special methods. Thus, pump-packing glands or me
chanical shaft seals can be protected by fresh water makeup/
or by circulating water from the pump, caring, through a
cyclone separator or filter, into the lubricating chamber. ,
Gross solid contaminants are kept out of large once-through
cooling systems by wtauw of trash screens. Recirculating sya.
terns utilize strainers. In closed recirculating systems particles
of mill scale and of some iron oxide corrosion products are
magnet-responsive and can be removed by utilizing magnetic
separators or strainers in which the screens are
of a
magnetic alloy or in which permanent magnets have been
fastened to the screens.
'
In smaller equipment, a good dirt control measure is the
installation of backflush connections and shut-off valves on
all condensers and heat exchangers, so that they can be readily
hackflushcd with makeup water or detergent solutions to
remove accumulated settled dirt.
Selection of Water Treatment
'
Prom tiie preceding section it is apparent that there are a number of methods available for the correction of almost any water-caused difficulty. If there is any singla statement in the field of water treatment which approaches a universal truth, it is that rio one treatment method is applicable to all In any one system, the selection of the proper water treatment method and the details of the chemicals and equipment neces sary to apply that method will depend upon a considerable number of factors. Most people quickly recognize that the chemical characteristics of the water are important and they may even recognize that these characteristics change with the operation of the equipment. The influence of economics upon
the choice of water treatment method is also .fairly clear. Less often is there recognition of the other nonchemical influ ences upon*the selection of the proper water treatment.77
Among these nonchemical factors are the design of inc& vidual major components of the system, such as the cooling tower or boiler, the operation of the equipment, and hnmn factors, such as the quantity and quality of operating per sonnel available.
Once-through Systems. Economics is the overriding consid eration in the treatment of water in once-through systems: The quantities of water to be treated are usually so large that any treatment other than simple filtration or the addition of a few ppm of a polyphosphate, silicate, or other inexpensive chemical would not be feasible. In such systems it is generally less expensive to invest more in corrosion resistant materials of construction rather than to attempt to treat the water.
Open Recirculating Systems. The selection of water treat ment for open recirculating systems is affected to a consider able extent by the size of the system. At one extreme, large industrial cooling tower systems use such huge quantities of water that it is necessary to minimize the concentration of any treatment chemical used. In these systems, sizeable expendi tures for chemical treatment and control equipment <^n be justified, as can the use of competent operating personnel. At the other extreme, in small air-conditioning and refrigera tion cooling towers, the total amount of.water used is so small that multiplying chemical concentrations by a factor of ten can mean the expenditure of only a few more dollars per month, whereas the cost of the entire system is such that little or nothing can be justified by way ofchemical feeding or auto-, matic control equipment, and only part-time, unskilled operating personnel can be employed.
Thus, a typical water treatment scheme for a large industrial cooling tower system operating at upwards of 10,000
gpm drcylation rate might include scale control by means of a controlled bleed and alkalinity reduction by automatically pH-controiled sulfuric acid feed combined with corrosion con trol- The latter is obtained by feeding a mixed inhibitor with, a concentration on the order of 60 ppm, with efficacy that wqqid depend both upon the maintenance of a pH within a
Corrosion and Deposits
239
___reaee (between 6 and 7) and on periodic con-
Sedddorination with chlorine gas tor dime control
rv/thpotber hand, in a small am-conditioning or refngera.
- ud
^jcuiatang at 100 gpm, treatment might
-^nfcontrolled bleed to minimise scale formation, and
jg^Lfa-oance of 200 to 500 ppm of sodium chromate for
"""7"" control- plus the occasional apphcation of a shock ^30f Kjdium pentachlorophenate for the control of organic
^^comprehensive discussion of water conditioning for airconditioning systems has appeared recently-
Closed Recirculating Systems. In theory, no treatment should be needed for the water in closed recirculating systems (hot water heat, chilled water, combined cooling and heating) because the'total amount of scale that could be deposited from the water initially filling the system would be insufficient to interfere significantly with heat transfer. In the case of corro sive water, the total amount of corrosion damage resulting from the initial fill would not be serious. However, operating experience in a great many of these systems has shown that appreciable water losses are the rule rather than the excep tion1* and, therefore, sound engineering practice dictate
that they'be treated.
,, .
4 1V
With makeup waters which are scale-forming at the
operating temperatures, the use of a softened makeup is desir
able. Treatment for corrosion control should be used with all
waters. The selection of such treatment is often determined
by other considerations. Although chromates are the most
effective corrosion inhibitors for these systems, the yellow
color of the chromate may rule out its use in locations where
a leak or an inadvertently opened valve may -cause staining
of rugs or other furnishings. In such cases, recourse may be
had to buffered nitrites with mercaptobenzthiazole, or to
sulfites in hot systems. The use of pbfwpbn.ti>H or polyphosphates should be avoided.
in closed systems because of the ultimate precipitation of cal cium phosphates which may result in the clogging of orifices
and vents.
ffigh temperature hot water systems are a special class of
closed systems. The typical treatment for such systems is
Koffgnmg and deaeration of the makeup combined' with
internal treatment to adjust the pH to the alkaline ride and
to maintain a email sulfite residual.'
In hot water heating systems, the concentration of chro
mate or nitrite inhibitor is normally higher than that carried
for chilled water systems.
Brine systems require still higher inhibitor concentrations
because of the high conductivity of the solutions. Minimum
chromate concentrations, for example, are 1800 ppm sodium
chromate in calcium chloride brine and 3600 ppm sodium
chromate in sodium chloride brine.
Bailers. Many volumes have been written about boiler water
treatmenti-^^' and it would be presumptuous to attempt
more than the most superficial coverage of this subject in the
space available. Probably the most important observations
that can be made here are to call attention to the facts that a
wide range of treatment procedures can- be used' for boiler
waters, and that, in any particular ewe, the method selected
must depend upon the composition of the makeup Water, the
operating pressure of the boiler, and the makeup rate, as
well as other -considerations.
Probably the greatest number of boilers in use are low pres
sure boilers for the generation ofsteam or hot water for space
beating. Yet, less has been written about water treatment for.
these boilers than jor the high pressure boilers used for electric
power generation, t -
- . ,
A low pressure Wm heating boiler should have. a. very-
Table 10 .... Typical Boiler Water Quality Require ments for Various Operating Pressures*
Operating Prawora PS
to 250
250-500 500-1000 *
Over >000
Suspended Solids
Phosphate** Oil
0000
300-700 300-500 200-400
10.5-115 10.5-11.C 10.5-ll.C 10.5-10.8
125
50-90
10-35 0.1-2.5
2500-3000 2000-250C 1000-200C 500-1000'
300-600 150-300 40-150
0.015 0.007*. 0.005
30-60 40-80
30-60 20-50
15-30 20-40
10-40
1.0
AS nba except pH in ppm. ** Rust- Other vxluea era This Ubh provides as incooplste guide only. Moradslaita) iflwrtgtliow must be "<i Defora setting requirements for say specific baler.
limited makeup requirement, and the most common waterside problem with such boilers is corrosion. Treatment with higher chromate concentrations on the order of 500 to 2000 ppm sodium chromate, or with alkaline materials to keep the pH of the boiler water above 10.5 with a caustic alkalinity of at least several hundred ppm (as CaCOtj, is generally sufficient. Actually, some of the most serious damage can be caused during the summer layup of such boilers, and it is particu larly important to have a sufficiently high inhibitor concen
tration present at such times.*1 As operating pressures and makeup rates go up, the corro
sion problem does not decrease, but the scale problem in creases in. importance. In very general terms, corrosion is controlled by the use of an open heater or, at higher operating pressures, a deaerating heater to remove oxygen from the boiler feedwater, the maintenance of a sulfite or hydrazine residual as an oxygen scavenger in the boiler water, and the maintenance of a sufficiently high pH in the boiler water. Scale is controlled by external softening and by internal treatment to precipitate residual traces of calcium, generally as a phosphate (hydroxy apatite), and magnesium (as mag nesium hydroxide or a baric silicate). A rough birds-eye view` of boiler water quality requirements is given in Table 10.
Treatment of the boiler water is also often affected by the end use of the steam. This may range from reduction^ of alkalinity so it can minimize condensate line corrosion by keeping carbon dioxide low in the steam, to silica removal for the protection of steam turbines against siliceous turbine blade deposits. Antifoam agents are'also used for improved'
boiler operation and steam quality. Return Condensate Systemt. Three approaches are used in
the niininnKing of corrosion in condensate'systems: (1) elim inating alkalinity from afl water entering the boiler bo as to ' mimmitt the amount of steam in the condensate lines, (2) the
use of volatile amines, such as morpholine and cyclohexyl-' amine, to neutralize carbon dioxide and thus raise the pH of the condensate, (3)'the introduction of filming amines, such' as octadecylamine, into the steam so as to form a thin,, hy drophobic filnr on the condensate'line surfaces. Thelatter is particularly effective in minimizing corrosion by oxygen:
UNDERGROUND CORROSION
The occurrence of corrosion activity on subsurface strue-.
Uires must always be anticipated. In addition to the .eco nomic loss attributable-to actual ,destruction of the under-,
ground facilities by corrosion, the loss of valuable fluids and
continuity of service, and. the creation of hazards to life and
property must be considered.
' -
\