HEATING VENTILATING AIR CONDITIONING GUIDE 1941
Heating Cycle
Similar fan systems are used for heating, as well as for ventilating occupied spaces, by increasing the number of coils to four or five. Where they are all installed together the control remains the same as shown in Fig. 2j and the additional coils are controlled directly from a room ther mostat which also causes T% to turn on full heat while the room is cool, but to function as described previously while the room is warm. This facilitates rapid heating of the room, after a vacant period.
An alternate plan is the use of a fan discharge thermostat whose control point can be automatically varied, and a room thermostat to reset it. Thus when the room is cold, air is delivered at a maximum tem perature designed for rapid heating, and when the room is too warm, the air is kept as cool as can be safely introduced, or as the weather permits. The discharge temperature varies between these two extremes at the command of the room thermostat, until it finds the proper point for the existing conditions. This makes it unnecessary to vary the fan discharge thermostat manually to prevent overheating in moderate weather, or chilling in cold weather.
The heating coils are often separated into two groups, one at the suction side of the fan, controlled as shown in Fig. 2, and the other on the down stream side of T3, controlled from the room. Control T2 is then called the tempered air thermostat;
In all types of fan heating systems it is desirable to have the tempered air thermostat in the fan discharge where stratification has been broken up by the fain.
Where a fan system supplies heat to several rooms or zones that require separate treatment, the tempered air control can remain as in Fig. 2, and the variation can be supplied in any of the following ways:
1. By installing a separate duct to each zone, and using individual heating coils, each under control of its respective room thermostat.
2. By installing double chambers at the fan discharge, only one of which is supplied with additional heating coils. Individual room or zone ducts have mixing dampers which allow air to be taken from the warm air chamber, the tempered air chamber, or both, as demanded by their respective room thermostats. With this arrangement, precautions must be taken to prevent the warm air from being churned back and into. the tempered air while a number of the mixing dampers are calling for the latter. If the warm air is controlled at a constant temperature under all conditions, the coils should be placed not less than 8 ft from the fan discharge and the dividing plate extended back several feet toward the fan. A good solution for the problem is to use an automatically adjusted thermostat in the warm air chamber, controlled by an outdoor thermostat so as to carry maximum warm air temperatures in the coldest weather and minimum in moderate weather.
3. By using a trunk duct, and varying the amounts of air delivered, by dampers at individual outlets or for the various zones. If a minimum amount of air is required for ventilation, the dampers must not close entirely. Thus to prevent over-heating, the trunk duct temperature must be varied according to the weather, as previously described. Also static pressure control may be needed. See a subsequent sub-head for a more detailed discussion of this subject.
Case 1 is illustrated in Fig. 3. Thermostat T in the fan discharge con trols outside and return air through damper motors Di and D%, face and by-pass dampers through damper motor Dz and the steam supply to a heating coil through valve V3. By having the face damper closed, and
610
CHAPTER 33. AUTOMATIC CONTROL
the by-pass open, before steam is throttled, there can be no danger of freezing the coil. Thus the D3 operation is completed before Vi starts. However, the relationship between D\ and D2 controlling the amount of recirculation, and D% regulating the amount of steam heat added, depends on the design of the ventilation system. . If the maximum. amount of outside air is desired for ventilation, and the return air is used only during the heating-up period, Dl and D2 complete their operation to bring in all outside air. before D3 starts. On the other hand if greatest heating econ omy is desired and full outside air is to be used only to prevent over heating, D3 completes its motion to close the face damper, before D\ and Dt start. Any relationship can be attained between these two extremes. Relay R prevents T from closing the outside damper completely, when a minimum of outdoor air is required during operation. Valves V3 and V3 control the steam supplied to booster coils for two zones, in accordance
with the requirements of room type zone thermostats, not shown in the diagram. Humidistat H, in the return air, regulates the amount of water supplied through Vt to the spray heads. Humidification
Humidification with air washers has been mentioned in. connection with control of ventilating systems. Where ample room air change is provided, it is generally assumed that the dew-point of the conditioned space will :soon equal that of the delivered air. This is due to exterior walls, especially glass, being less pervious to vapor flow than to heat transmission. With partial recirculation, dew-point control prevents over-as well as under-humidification, for ordinary installations.
Where air washers are not used, humidification may be accomplished by water sprays, preferably with heated water; by steam heated water in pans; or by steam jets, if their odors are not objectionable. Sub-atmos pheric steam cannot be.used, of course, for jets, and is not of much more value in coil heated pans. In all these cases the control is obtained by
611