Document x1oLyzbV06e0mG8Zr5ZOwxGEJ

Specialties, Heating C. A. Dunham Co. Administrative and General Offices: 450 East Ohio Street, Chicago Factories at Marshalltown, Iowa, and Toronto, Ont., Canada BRANCH SALES OFFICES: Birmingham, Boston, Charlotte (N.C.), Chicago, Cincinnati, Cleveland, Columbus (Ohio), Dallas, Davenport, Denver, Des Moines, Detroit. El Paso, Indianapolis, Kansas City, Los Angeles, Louisville, Milwaukee, Minneapolis, New Orleans New York, Omaha, Philadelphia, Pittsburgh, Portland (Ore.), Rochester, St. Louis, Salt Lake City, San Francisco, Seattle, Troy, Washington (D.C.) C. A. DUNHAM CO., LTD., General Offices and Factory, Toronto., Ont. 1523-41 Davenport Road BRANCH SALES OFFICES: Calgary, Montreal, Ottawa, Toronto, Winnipeg, Vancouver, Halifax. FOREIGN SALES OFFICES: 18 St. Thomas Street, S.E.I., London, England; St. John's, Newfoundland Distributors: Munsing & Co., Paris, France, 47 Rue Fontaine-au-roi Manufacturers of The Dunham Differential Vacuum Heating System and Specialties . HEATING . SERVICE This Service is delivered through over 70 Branch and Local Sales Offices throughout the United States, Canada and the United Kingdom. These Branch and Local sales offices bring Dunham Heating Service as close to your office as your telephone. Consult your telephone directory for the address of our office in your city. An engineer will counsel with you on any project. DUNHAM DIFFERENTIAL VACUUM HEATING SYSTEM U. S. Patent No. 1644114 (Additional patents in the United States, Canada and Foreign Countries applied for, and pending) This system will heat properly any building, without the usual fuel and heat waste caused by overheating and by excessive window ventilation. It furnishes steam to the radiators at the rate they are using it, by circulating it at a high degree of vacuum or sub-atmospheric pressure, with correspondingly low radiator tem perature; or by operation of a control valve it can be operated as a mechanical vacuum return line system at the pressure above atmosphere, which the weather condition calls for.' A fixed differential with the return pressure always lower than the radiator pressure is maintained. This produces circulation with sub-atmospheric pressures (vacuums) on the steam side of the system. Economical operation is the. natural result of such perform ance. The system is simple in design, durable and flexible to meet vary ing weather conditions. The outstanding feature of economy of operation is accomplished by sup plying heat to the radiators at the rate the building is using it, by; Condensate in Lbs.-per 100 Sq. Ft. of Net Radiation per Hour Regulating the subatmospheric pressure, or 578 C. A, Dunham Co. ; -S----- --r ; . .v.v, Specialties, Heating the degree of vacuum, at which the steam circu lates in the supply piping and radiators. Controlling the vacuum in the return piping so that a substantially con stant difference in pressure is maintained between the radiators and return piping at all pressures. Briefly the operation of the system is as follows: The generation of steam, when starting with a cold boiler under vacu um, begins at a much lower temperature due to sub-atmospheric pressure because of the vacuum produced by the pump. Temperature Difference. Degrees Fahrenheit Cost of Heating 100 Sq. Ft. Net Radiation per Hour based on Gas at $1.00 per 1000 Cu. Ft. This results in an ap preciable saving of fuel. radiators function under these wide The steam expands under this vacuum ranges of pressure. All air and water is condition and fills the radiators (just as it released from the radiator, but steam is does when generating on pressures above not released. See Chart 1060A on page 581 atmosphere) with the result that sub for explanation. stantially the entire radiator surface In severe weather the pressure can be works at temperature corresponding to the regulated to supply steam at such a rate vacuum maintained in the system. The that in the boiler, supply piping and Differential Controller on the pump main radiators, pressures at or greater than tains the condition in the return at a atmosphere will be maintained while pressure less, or a vacuum greater, than in operating as a mechanical vacuum return the radiator. Circulation is thereby line system. maintained irrespective of supply pressure . During the Fall, mild Winter and or vacuum. The system fills with steam Spring weather, the steam is circulated at the various sub-atmospheric pressures. under the sub-atmospheric pressures and The Dunham Radiator Traps on the vacuum condition necessary to provide The Heat Emitted by a Radiator Depends on the Temperature Difference Between Radiator and the A ir of the Room Radiator Temperature Depends on Pressure of Steam in Radiator 579