604 CHAPTER 34 1965 Guide And Data Book mrt* owner1 system piping as described in Chapter 10, 1964 Guide And Data Book. To assure a pressure drop sufficient for adequate `'-distribution, but at the time to provide against excessive pumping head where large water quantities are handled, water . coils.are provided with various water-circuit arrangements. For instance, a typical coil 18 tubes high and 6 tubes deep in the direction of air flow can be arranged for 6, 9, 18, 24, or 36 parallel water circuits, as conditions may require. .-^Orifices .-in individual tubes are occasionally-employed, but- ' are usually unnecessary as the resistance of individual- water ; circuits is generally sufficient to effect a satisfactory distri- y button. In precooling coils using well water, where there may be considerable sand and other foreign matter in the water, provision for cleaning of individual.tubes.is impor tant in order to assure a continuation of rated perform ance after the cooling units have been in service for a period of time. It is important, to arrange'water coils for complete drainage (see Fig. 2). The drains are usually provided1 in'the water piping at the coil header. r" Direct-Expansion Coils 1^ f=-- 6-eweutT* "Lrri a-CMeurrs Fig. 2 .... Various Water Grant Arrangements " fins for each tube.- All of these, as well as other less common types, are in iise, the selection for a particular installation being based on economic considerations, space require ments, and performance of individual derigria of coils.' A most important* factor in the performance of extended- surface coils is the bond between the fin and the tube. .An intimate contact between the tube and the fin` must be maintained permanently to ensure nmmpHpH heat transfer from fin to tube. . In some coils, fins are wound on the tubes under pressure; in order.to upset:the mpfal slightly at the fin root/ and'are then given a coating of solder-while the fin and tube are still' revolving, for-.the purpose ;of assuring a uniform mating of solder..In other types, the!spiral fin may be knurled into-a: shallow groove on the exterior of.the tube. The tube may be expanded after the fins are assembled, or the tube-hole flanges; of a flat or configurated fin-may be made to override thoscin. the` preceding fin and so compress them upon the tube.; There .are also types .of.i construction where-the fin-`is. formed out of the material of the tube itself. - I Cooling coils for water-or for volatile refrigerants most; frequently-hare aluminum fins and copper tubes, although copper (fins on copper tubes-are-also used. There ate many; makes of.cooling coils of.the lightweight extended-surface, type for both heating and cooling with tubes commonly M, and 1 in. outside diameter, and with fins spaced three per inch up to'fourteen-per inch. The tube spacing gen erally varies from about $ to in. on centers, depending upon*the width of individual fins and'on other considerations of performance. Fin spacing should be chosen for the duty;to be performed, with special attention being paid to air.friction, possibility of lint accumulation and, especially at lower tem peratures, the'consideration of frost accumulation. ~ Water Coils *_ . - jj The performance of water coils, for heating or cooling, de pends on the elimination of air from the system and proper distribution of water.`Air elimination is token care'of in the Coils for volatile refrigerants present more complex prob lems of fluid distribution than water, brine, or steam.coils.. It is desirable' that the coil be effectively and uniformly, cooled throughout, and necessary that the compressor.be protected from entrained, unevaporated refrigerant. There' are two types, namely, flooded systems, and thermal-, expansion-valve systems, as shown in Figs. 3 and 4. In a flooded coil, the circulation is similar to that in a water tube boiler. The liquid is maintained atthe proper level by the action of a float regulator,- refrigerant pump, or both;' as shown in Fig. 3. The thermal-expansion-valve system depends upon the thermal valve to feed automatically just as much' liquid to the coils as is required to evaporate all-refrigerant entering the coil and maintain the superheat at the coil-1 suction-outlet within predetermined limits, which vary.bom' about 6 to 10 deg. The thermal-valve arrangement is in com mon-use for the type of coils covered by this chapter, while. . the flooded system is rarely used. . .With the flooded system considerably more refrigerant is circulated than in expansion valve systems (up to 5.times rate of evaporation) and liquid refrigerant may leave thei coiL The refrigerant distribution through the tubes depends on properly selecting the length of the feeds, and the head of. liquid imposed upon the liquid inlets. The flow of refrigerant from <the. liquid inlets must be horizontal and upwartL Ilie possibility of gas trapping must be avoided. No auxiliary dis-> tributing devices are required. .[.The path of each refrigerant feed-from the distributor to; thesuction header is called, a circuit. The length of each cir cuit should be chosen to provide good heat transfer and return- of oil, as well as a reasonable pressure drop across the circuit.. Cod^ (' t ( ( J rtpiatcr ) S ) ) Fig. 3 ,,,. Direct-Expansion Coil with Flooded System . Air-Cooling and Dehumldifying Colls The external loading conditions, the tube size, and other fac tors, influence the practical length of a circuit Because of the various factors involved, the practical length and the ar rangement of the circuits is developed from laboratory tests and the d<rign of coils for units produced in volume are usually verified by additional tests. To insure reasonably uniform refrigerant distribution in multicircuit coils, it is common practice to'provide a dis tributing means, between valve - and coil1 liquid inlets, to divide the refrigerant equally among the feeds. Such a distributor must be effective for distributing both liquid and vapor, because the entering refrigerant is a mixture of the two. Fig. 5 shows four typical types of distributors. In distributor A, the liquid'and gas mixture from the thermal valve is led tangentially into a chamber. The coil feed con nections extend outward radially at the top of this chamber. In distributor*,* the refrigerant is discharged at a high veloc ity through a central jet against the end plate, forming a uni form mixture of gas and liquid within the distributor, from which individual connections are led as shown. In type C, the refrigerant enters at high velocity from the' thermal valve and; is discharged against the end plug in which the individual1 liquid feeds are closely arranged. Type D shows a typical pressure-drop type distributor. The liquid-vapor mix ture flows into the nozzle, which is sized to match the load so that adequate miring of the two phases is maintained to feed equal portions of the mixture to the individual circuits. Beyond the nozzle, the refrigerant stream is deflected by a conical pin towards the individual circuits which are spaced evenly around the base of the cone. These distributors can be used in either vertical or horizontal position There.are a1sq other types of headers such as the .weir type. The individual liquid connections from the distributor to the coil inlet are commonly made of small diameter tubing, and are all of the name length and diamatgr In order to impose the same friction between tire distributor and the coil. Since the thermal valves act in response to the.superheat at the coil outlet, this super heat should be produced with the least possible sacrifice of active evaporating surface. Control of Coils Chapter 13 discusses methods of controlling air-cooling coils to meet system or space requirements, and factors that should be considered in siring automatic valves for. water coils. Chapter, 46 discusses refrigerant flow control devices and factors to be considered in their use with direct expansion coils. It is general practice to obtain superheat by suitable design of the coil rather than by use of external heat exchang ers or other auxiliary devices. The majority of direct p-rpanrinn coils are equipped with thermal valves; Sometimes a ringla thermal valve is used per coil while, in other cases, two or more thermal valves are em ployed by each coil. The function of the thermal valve is to control the refrigerant flow rate through its coil circuit so Rg. 4....Direct-Expansion Coll with Thermal Valve System 605 Fig. 5 .... Refrigerant Feed Distributing Heads that the refrigerant vapor at the coil outlet is properly super heated.' By themselves, thermal valves do not provide ac curate control. of the total .system, refrigeration capacity under partial load conditions. .v. For regulating.the refrigeration'load requirements for.the conditioned space, a common method of controlling coil ca pacity is by use of solenoidoperated refrigerant liquid valves located upstream fromjthe-thermal valves as shown in Fig. 6 and 7. One or more thermal valves may be operated'by a single solenoid valve. The solennid valves are usually controlled by a thermostat located'ihjthe return air or in the'conditioned space. For coils with multiple thermal valves, there are two arrangements; (1) face control in which the coil is divided across its face, as shown in Fig.'6, and (2) depth (or row) control as shown in Fig., 7. Face control is used in most cases and provides. substantially* equal loading on all thermal valve fed circuits within the coil. Face control has the dis advantage of permitting re-evaporation of condensate on the coil and bypassing air | into the `conditioned space, during partial load conditions when some of the thermal valves are on an off cycle. Depth control is seldom-available as standard equipment and is usually supplied on,special order. Depth control produces unequal loading oh;the thermal valve cir cuits, but this is not necessarily a disadvantage if thermal valves are properly sized and designed to overcome this effect. Depth control riiminafafr- air*bypassing during partial load operation and minimizes condensate re-evaporation. Row Arrangement ` * In all heat tranrfer processes," the relative 'directions of flow of the fluids influence the performance of the heat-