Document x1J3ZN1JJ1dVpapLkQkxDg1vG
604
CHAPTER 34
1965 Guide And Data Book
mrt* owner1
system piping as described in Chapter 10, 1964 Guide And
Data Book. To assure a pressure drop sufficient for adequate
`'-distribution, but at the
time to provide against excessive
pumping head where large water quantities are handled, water
. coils.are provided with various water-circuit arrangements.
For instance, a typical coil 18 tubes high and 6 tubes deep in
the direction of air flow can be arranged for 6, 9, 18, 24,
or 36 parallel water circuits, as conditions may require.
.-^Orifices .-in individual tubes are occasionally-employed, but-
' are usually unnecessary as the resistance of individual- water
; circuits is generally sufficient to effect a satisfactory distri-
y button. In precooling coils using well water, where there
may be considerable sand and other foreign matter in the
water, provision for cleaning of individual.tubes.is impor
tant in order to assure a continuation of rated perform
ance after the cooling units have been in service for a period
of time. It is important, to arrange'water coils for complete
drainage (see Fig. 2). The drains are usually provided1 in'the
water piping at the coil header.
r"
Direct-Expansion Coils
1^ f=--
6-eweutT*
"Lrri
a-CMeurrs
Fig. 2 .... Various Water Grant Arrangements "
fins for each tube.- All of these, as well as other less common
types, are in iise, the selection for a particular installation
being based on economic considerations, space require
ments, and performance of individual derigria of coils.' A
most important* factor in the performance of extended-
surface coils is the bond between the fin and the tube. .An
intimate contact between the tube and the fin` must be
maintained permanently to ensure nmmpHpH heat transfer
from fin to tube.
. In some coils, fins are wound on the tubes under pressure;
in order.to upset:the mpfal slightly at the fin root/ and'are
then given a coating of solder-while the fin and tube are still'
revolving, for-.the purpose ;of assuring a uniform mating of
solder..In other types, the!spiral fin may be knurled into-a:
shallow groove on the exterior of.the tube. The tube may be
expanded after the fins are assembled, or the tube-hole flanges;
of a flat or configurated fin-may be made to override thoscin.
the` preceding fin and so compress them upon the tube.;
There .are also types .of.i construction where-the fin-`is.
formed out of the material of the tube itself.
-
I Cooling coils for water-or for volatile refrigerants most;
frequently-hare aluminum fins and copper tubes, although
copper (fins on copper tubes-are-also used. There ate many;
makes of.cooling coils of.the lightweight extended-surface,
type for both heating and cooling with tubes commonly
M, and 1 in. outside diameter, and with fins spaced
three per inch up to'fourteen-per inch. The tube spacing gen
erally varies from about $ to in. on centers, depending
upon*the width of individual fins and'on other considerations
of performance. Fin spacing should be chosen for the duty;to
be performed, with special attention being paid to air.friction,
possibility of lint accumulation and, especially at lower tem
peratures, the'consideration of frost accumulation.
~
Water Coils
*_ .
- jj
The performance of water coils, for heating or cooling, de pends on the elimination of air from the system and proper distribution of water.`Air elimination is token care'of in the
Coils for volatile refrigerants present more complex prob
lems of fluid distribution than water, brine, or steam.coils..
It is desirable' that the coil be effectively and uniformly,
cooled throughout, and necessary that the compressor.be
protected from entrained, unevaporated refrigerant. There'
are two types, namely, flooded systems, and thermal-,
expansion-valve systems, as shown in Figs. 3 and 4. In a
flooded coil, the circulation is similar to that in a water tube
boiler. The liquid is maintained atthe proper level by the
action of a float regulator,- refrigerant pump, or both;' as
shown in Fig. 3. The thermal-expansion-valve system depends
upon the thermal valve to feed automatically just as much'
liquid to the coils as is required to evaporate all-refrigerant
entering the coil and maintain the superheat at the coil-1
suction-outlet within predetermined limits, which vary.bom'
about 6 to 10 deg. The thermal-valve arrangement is in com
mon-use for the type of coils covered by this chapter, while.
. the flooded system is rarely used.
. .With the flooded system considerably more refrigerant is
circulated than in expansion valve systems (up to 5.times
rate of evaporation) and liquid refrigerant may leave thei
coiL The refrigerant distribution through the tubes depends
on properly selecting the length of the feeds, and the head of.
liquid imposed upon the liquid inlets. The flow of refrigerant
from <the. liquid inlets must be horizontal and upwartL Ilie
possibility of gas trapping must be avoided. No auxiliary dis->
tributing devices are required.
.[.The path of each refrigerant feed-from the distributor to;
thesuction header is called, a circuit. The length of each cir
cuit should be chosen to provide good heat transfer and return-
of oil, as well as a reasonable pressure drop across the circuit..
Cod^
('
t
( (
J rtpiatcr )
S
)
)
Fig. 3 ,,,. Direct-Expansion Coil with Flooded System .
Air-Cooling and Dehumldifying Colls
The external loading conditions, the tube size, and other fac tors, influence the practical length of a circuit Because of the various factors involved, the practical length and the ar rangement of the circuits is developed from laboratory tests and the d<rign of coils for units produced in volume are usually verified by additional tests.
To insure reasonably uniform refrigerant distribution in multicircuit coils, it is common practice to'provide a dis tributing means, between valve - and coil1 liquid inlets, to divide the refrigerant equally among the feeds. Such a distributor must be effective for distributing both liquid and vapor, because the entering refrigerant is a mixture of the two. Fig. 5 shows four typical types of distributors. In distributor A, the liquid'and gas mixture from the thermal valve is led tangentially into a chamber. The coil feed con nections extend outward radially at the top of this chamber. In distributor*,* the refrigerant is discharged at a high veloc ity through a central jet against the end plate, forming a uni form mixture of gas and liquid within the distributor, from which individual connections are led as shown. In type C, the refrigerant enters at high velocity from the' thermal valve and; is discharged against the end plug in which the individual1 liquid feeds are closely arranged. Type D shows a typical pressure-drop type distributor. The liquid-vapor mix ture flows into the nozzle, which is sized to match the load so that adequate miring of the two phases is maintained to feed equal portions of the mixture to the individual circuits. Beyond the nozzle, the refrigerant stream is deflected by a conical pin towards the individual circuits which are spaced evenly around the base of the cone. These distributors can be used in either vertical or horizontal position There.are a1sq other types of headers such as the .weir type. The individual liquid connections from the distributor to the coil inlet are commonly made of small diameter tubing, and are all of the name length and diamatgr In order to impose the same friction between tire distributor and the coil. Since the thermal valves act in response to the.superheat at the coil outlet, this super heat should be produced with the least possible sacrifice of active evaporating surface.
Control of Coils
Chapter 13 discusses methods of controlling air-cooling coils to meet system or space requirements, and factors that should be considered in siring automatic valves for. water coils. Chapter, 46 discusses refrigerant flow control devices and factors to be considered in their use with direct expansion coils. It is general practice to obtain superheat by suitable design of the coil rather than by use of external heat exchang ers or other auxiliary devices.
The majority of direct p-rpanrinn coils are equipped with thermal valves; Sometimes a ringla thermal valve is used per coil while, in other cases, two or more thermal valves are em ployed by each coil. The function of the thermal valve is to control the refrigerant flow rate through its coil circuit so
Rg. 4....Direct-Expansion Coll with Thermal Valve System
605
Fig. 5 .... Refrigerant Feed Distributing Heads
that the refrigerant vapor at the coil outlet is properly super
heated.' By themselves, thermal valves do not provide ac
curate control. of the total .system, refrigeration capacity
under partial load conditions.
.v.
For regulating.the refrigeration'load requirements for.the
conditioned space, a common method of controlling coil ca
pacity is by use of solenoidoperated refrigerant liquid valves
located upstream fromjthe-thermal valves as shown in Fig. 6
and 7. One or more thermal valves may be operated'by a single
solenoid valve. The solennid valves are usually controlled by
a thermostat located'ihjthe return air or in the'conditioned
space. For coils with multiple thermal valves, there are two
arrangements; (1) face control in which the coil is divided
across its face, as shown in Fig.'6, and (2) depth (or row)
control as shown in Fig., 7. Face control is used in most cases
and provides. substantially* equal loading on all thermal
valve fed circuits within the coil. Face control has the dis
advantage of permitting re-evaporation of condensate on the
coil and bypassing air | into the `conditioned space, during
partial load conditions when some of the thermal valves are
on an off cycle. Depth control is seldom-available as standard
equipment and is usually supplied on,special order. Depth
control produces unequal loading oh;the thermal valve cir
cuits, but this is not necessarily a disadvantage if thermal
valves are properly sized and designed to overcome this
effect. Depth control riiminafafr- air*bypassing during partial
load operation and minimizes condensate re-evaporation.
Row Arrangement `
*
In all heat tranrfer processes," the relative 'directions of flow of the fluids influence the performance of the heat-