HEATINC VENTILATINC AIR CONDITIONING CUIDE 1941 In most cases of design of resilient machine mounting the effect of frictional resistance is small, and Equation 1 may be used. In such cases it is only necessary to know the natural frequency of the elastic pad or platform used under the desired loading and the transmissibility for any vibrational frequency of the machine may be obtained. However, this formula gives the theoretical maximum insulation which may be obtained and should be used with a liberal factor of safety. (A factor of 2 is common practice when the ratio is converted to decibels.) If the pad is to be of any value in the prevention of solid-borne vibra tions, the value of transmissibility must be considerably smaller than unity. If the fundamental frequency of vibration generated by the machine happens to coincide with the natural frequency of the mass of the machine resting on the elastic pad, a condition of resonance will be established, and the machine will exert a greater force upon the foundation than it would if the pad were completely removed. It is necessary, therefore, that the elastic support be sufficiently compliant, and the mass of the machine sufficiently heavy, that the natural frequency of the mass m upon its elastic support will be low in comparison with the frequencies which are generated by the machine. Thus, if the principal vibrations in the machine be of the order of 100 vibrations per second, the natural frequency of the machine mounted on its elastic support should not exceed about 50 vibrations per second, and for best results preferably 20. When the forced frequency is low, it is frequently impossible to insulate for the fundamental forced frequency due to connecting pipe work and other relevant factors. In cases of this kind an effective installation of sound insulation may be obtained with a mounting which functions far above the fundamental forced frequency. For example, a compressor operating at 500 rpm has a forced frequency of 8.3 vibrations per second. By designing a mounting having a natural frequency of 20 to 25 vibrations per second, it is possible to isolate practically all of the noise. Controlling Noise Through Room Wall Surfaces The ventilating equipment is usually housed in a separate room where the noise produced by the mechanical operation of the equipment can be isolated from the rest of the building. If the vibration of the machinery is absorbed by flexible mounting and is not transmitted to the building, the only noise to be eliminated by the walls of the room will be the air borne mechanical. noise. Acoustical measurements on average brick, tile, lath, and plaster walls indicate that the usual wall of these types is sufficient to satisfactorily attenuate this air-borne mechanical noise4. Attention should be given to the equipment room door, since this door may leak badly and allow sound to escape into parts of the building which should be quiet. Where the equipment noise is particularly severe, double doors should be used and in all cases, the doors of the equipment room should be fitted with tight thresholds and weather-stripping. The door itself may transmit considerable sound if it is thin but it will not transmit a tenth as much as will be transmitted by a J-in. crack between the door and the threshold. ^Acoustical Problems in the Heating and Ventilating of Buildings, by V. O. Knudsen (A.S.H.V.E. Transactions, Vol. 37, 1932, p. 211). 596 CHAPTER 32. SOUND CONTROL In cases where the equipment noise is extraordinarily high, it may be necessary to treat acoustically the walls and ceiling of the equipment room. If the equipment room is not entirely closed, partition walls may be necessary. NOISE TRANSMITTED THROUGH THE DUCTS After noise reaches the air stream in the ducts it can be controlled by lining the ducts on the inside with a sufficient quantity of sound absorbing material. Lagging material of similar characteristics placed on the out side of ducts serves to prevent noise originating outside the ducts being carried inside the ducts and into the air stream. A case where outside lagging is desirable occurs when ducts originate at the fan in the equipment room and pass through this room on the way to the room being conditioned or ventilated. Unless the ducts are lined some of the mechanical noise from the equipment room air may be trans mitted through the wall of the duct, thus reaching the air stream and be carried into the room. In such cases, that portion of the duct which is exposed to the sounds in the equipment room should be lagged with material such as cork, pipe covering or other sound damping material to prevent the sound from entering the duct at this point. Numerical data are not available to permit a simple and practical calculating procedure to determine thickness of covering which should be used for this purpose. Measurements in one laboratory have shown that the loss through a sheet of No. 22 gage metal is 24 db. When a sheet of rock wool insu lation 1 in. thick and weighing 1.4 lb per square foot is added to this, the insulation value is increased to 29 db. In general, however, adding a layer of insulation or pipe covering does not materially increase the sound insulation value unless the material is dense, or unless it is surfaced with another sound impervious layer such as metal or board. Inside lining material used in the case previously mentioned would serve as an absorber of the sound transmitted through the duct walls, and thus act as a means of preventing the transfer of noise into the air stream. Inside lining may also be used in ducts to absorb noise which reaches the air stream from equipment such as fans, sprays and coils; noise due to eddying currents set up by elbows, dampers and similar obstructions; and noise trans mitted from room to room where there is a common duct system. Calculating Amount of Duct Lining To use the lining effectively it must be properly located, well installed and be applied in sufficient quantity to reduce the noise level of the air stream to the level desired. It has been shown theoretically6 that the reduction, in decibels per linear foot, of sound transmitted through a duct lined with sound absorbing material is related in a rather complicated manner to the size and shape of the duct, to the frequency of the sound, and to the sound absorbing characteristics of the lining. Experimental evidence likewise indicates that there is no simple formula involving the above variables which will apply accurately to all cases. "Sound Propagation iu Ducts Lined with Absorbing Materials, by L. J. Sivian (Journal Acoustical Society of America, Vol. 9, p. 135, 1937). 597.