Document x16XkaxpXndkvOQG5ByKV2mq1
694
CHAPTER 32
1951 Guide
3. Variation in Fan Size:.
At Constant RPM--Constant Air Density
Constant Fan Proportions--fixed Point of Rating
(o) Q:
Varies as cube of wheel diameter.
(6) P:
Varies as square of wheel diameter.
(c) Tip Speed: Varies as wheel diameter.
Id) Power:' Varies as fifth power of diameter.
4. Variation in Air Density:
Constant Volume--Constant System
Fixed Fan Size--Constant Fan Speed
(a) Q:
Constant.
" (b) P:
Varies as density..
(c) Power: Varies as density.
5. Variation in Air Density:
Constant Pressure--Constant System
Fixed Fan Size--Variable Fan Speed
() Q:
Varies inversely as square root of density.
() P: (c) RPM: (d) Power:
Constant.
.
Varies inversely as square root of density.
Varies inversely as square root of density.
6. Variation in Air Density:
Constant Weight of Air--Constant System
Fixed Fan Size--Variable Fan Speed
(a) Q:
Varies inversely as density. -
(b) p-
Varies inversely as density..
(c) RPM:
Varies inversely as density.
(d) Power: . Varies inversely as square of density.
Examples 1 to 4 illustrate the application of the preceding fan laws.
Example i. A certain fan delivers 12,000 cfm at a static pressure of 1 in. of water when operating at a speed of 400 rpm and requires an input of 4 hp. If in the same installation 15 000 cfm are desired, what will be the speed, static pressure, and power?
15,000 _ Speed = 400 X jjggg = 500 rpm
(5--00\1* = 1.56 in.
*(sy-Power
7.81 hp
Example 8. A certain fan delivers 12,000 cfm at 70 F and normal barometric pres
sure (density 0.075 lb per cubic foot) at a static pressure of 1 in. of water when operat ing at 400 rpm, and requires 4 hp. If the air temperature is increased to 200 F (den
sity 0.0602 lb) and the speed of the fan remains the same, what will be the static
pressure and power?
Static pressure = 1 X
0.80 in.
0.0602
Power = 4X
= 3.20 hp
0.075
.
Example 3. If the speed of the fan of Example 8 is increased so as to produce a static pressure of 1 in. of water at the 200 F temperature, what will be the speed,
capacity, and power?
Fans
695
Speed = 400 X : / 0.075 i. 446 rpm 0.0602
Capacity - 12,000 X //0 075 = 1133,392 cfm (measured at 200 F) y 0.0602
V:Power = 4 X /b.075 4.46 hp 0.0602
Example 4- If the speed of the fan' of the previous examples is increased so as to deliver the same weight of air at 200 F as at 70 F, what will be the speed, capacity, static pressure, and power?
0.075 Speed = 400 X r---- -- 498 rpm
0a0oQ2
Capacity = 12,000 X 0.075 0.0602
14,945 cfm (measured at 200 F)
IMJ/O
Static pressure = 1 X ----- = 1.25 in. 0.0602
(0O.0M75obV) - 6.20 hp
The fan laws stated may be combined to give other overall values. One useful combination is the product of laws 1 and 3 which gives the following relations:
Capacity varies as the ratio of size cubed, times the ratio of the rpm. Pressure varies as the ratio of size squared, times the ratio of the rpm squared. Horsepower varies as the ratio of the size to fifth power, times the ratio of the rpm cubed.
Example 6: Assuming that a fan with a 36 in. diameter blast wheel will deliver 12,000 cfm at 70 F at 1 in. static pressure, requiring 4.0 brake hp when operating at 400 rpm, what is the. capacity; pressure and horsepower of a homologous fan having a 45 in. wheel at the same speed?
( X 1 )45\* /400\ 36/ 400 X 12,000 = 23,400 Cfm
(45V /400V 36/ X \400/ X 1 = 1-56
Horsepower
=
/45\` j
X
/(40--0\*1
X
4
=
12.2
hp
FAN PERFORMANCE CURVES
Fan performance, curves are the graphical presentation (for constant speed and air density) of the relation of total pressure, static pressure, power input,-and mechanical .and static efficiency, to actual volume, for the desired range of volumes, Figs. 2, 3 and 4 illustrate, performance (some times called characteristic) curves of various types of fans.
- Centrifugal fans* may be roughly divided into three.classes: (1).those with the tip of the blades curved forward in.the direction of rotation; (2) those with straight radial blades; and (3) those with the tip of the blades in-